6-10
Saia-Burgess Controls AG
27-621 ENG07 – Manual – Web Panel MB - PCD7.D450WTPx and PCD7.W470WTPx
Internal special functions
Handling: precautionary measures
7
6.6
Internal special functions
6.6.1
Container
variable
for
WVGA
MB
panel
The
configuration
file
UBTERMINAL.TXT
is
not
accessible
via
the
FTP
connection,
because
this
file
is
located
in
the
(write-
protected)
subdirectory/PLC_SYS/CONFIG/.
Containers
allow
the
application
to
exchange
data
with
the
firmware.
All
container
variables
havethe
prefix
"uBT_".
Pay
attention
to
upper/lower
case!!!
Config
file
entry
Container
(source HN 10.03.10)
Type
Default
Min
value
Min length
Max
value
Max
length
Description
R/W
uBT_AlarmFrequency
Decimal value string
1000
125
8000
Frequency setting for the acoustic alarm (Hz)
(based on 125,250,500,1000,2000,4000,8000)
Set before using the alarm.
A change in frequency while the alarm is sounding will take ef
fect only when the next
alarm is called.
No
uBT_AlarmStart
Decimal value string
0
0
30000 = 30 sec.
Define a value to start or stop the pulsed, acoustic alarm.
The acoustic alarm can be started by setting an interval time
(0 - 30,000 mSec) for the pulsed signal.
A 50% pulse/pause ratio is used, i.e. the pulse time is equal to the pause time.
Changes made while the alarm is already sounding are ignored.
At a setting of 0, however
, the alarm is immediately deactivated.
The alarm is stopped immediately by touching the screen.
R/W
uBT_AlarmV
olume
Decimal value string
10
0
20: 100%
Volume of the acoustic alarm (0 - 20).
As pulse width modulation is used, this setting has an ef
fect on the perceived pitch of the
alarm.
Set before using the alarm!
A change in volume while the alarm is sounding will take ef
fect only when the next alarm
is called.
R/W
uBT_AutoRepeat
Boolean value string
0
0
1
Via the Soft Input Panel SIP
(on-screen keyboard), use:
SIP
keyboard:
AutoRepeat on (1), of
f (0 )
No
uBT_BackLight
Boolean value string
1
0
1
Read/W
rite 1, 0
Remote control for backlight OFF
. The backlight is switched OFF if the
value was previously ‘1’. When the screen is touched, the backlight is switched back on
again immediately
.
Read/W
rite 0, 1
Remote control for backlight ON.
The backlight is switched ON if the
value was previously ‘0’.
There may be a delay when switching of
f.
Remote control via PPO
Container coupling, only
.
Use on painters for buttons and edit fields is not supported.