Configuration
Diagnostic
2-19
2
2.5.5
Downloading the Device Configuration
The device configuration must first be downloaded into the Primary and Secondary
devices using a local “S-Bus USB” channel, to configure the S-Bus station num
-
bers and IP addresses. After this step you can use a n “S-Bus TCP/IP” Ethernet
channel.
Downloading the configuration to CPU0 of the Primary or Secondary device also
updates the configuration of CPU1 at the same time. It is not possible to update
the configuration of only CPU1, the Download Configuration command is disabled
for CPU1.
Configure the Online Settings
Before you can download the new configurations to the Primary, Secondary and
Redundant devices, you must ensure that the Online Settings are correct. First
use an S-Bus USB channel to download the configuration. Connect a single
device with the USB cable, select an “S-Bus USB” channel, PGU mode = ‘Yes’.
Open the device Configurator, and press the ‘Download Configuration’ button. This
updates the configuration for both CPUs (0 and 1) in the device. Repeat this for
the primary and secondary devices.
Once the configuration has been downloaded, open the Online Settings and set
PGU mode = ‘No’, and Auto Station = ‘No’.
Now you can either use two local S-Bus USB connections or an S-Bus TCP/IP
connection for communications with the two devices.
Using two USB connections
Two USB connections can be used to connect locally to both devices at the same
time, but normally you would use an S-Bus TCP/IP channel for this.
Connect the two USB cables to the Primary and Secondary CPU0. Open the On-
line Settings for the Primary and Secondary each devices, select the S-Bus USB
channel, ensure that PGU and Auto Station are both ‘No’. Enter the correct S-Bus
station number. To select the right USB channel, press the ‘Refresh USB list’ but-
ton, then open the ‘USB Serial Number’ list and choose the correct device. The
USB serial number is created from the device type and the device’s PCD serial
number, e.g. PCD3.M6880 8A56C170000.
If using Ethernet, enter the IP addresses you used in the device configuration for
the 1-Primary and 2-Secondary devices.
Test you connection by opening the Online Debugger (S-Bug) for each device.
Download Program to Standby System
the status of each device.