Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
5-10
I/O modules PCD1|PCD2
PCD2.E110, PCD2.E111, PCD2.E112 and PCD2.E116
5
5.2.1
PCD2.E11x, 8 digital inputs
Application
Low-cost input module for source or sink operation with 8 inputs, electrically
connected. Suitable for most electronic and electromechanical switching elements
at 24 V
DC
. The PCD2.E111 differs from the PCD2.E110 in its shorter input delay,
typically 0.2 ms.
Technical data
Number of inputs:
8
electrically connected,
source or sink operation
Input voltage E110 :
E111
:
E112
:
E116
:
Special
:
24 VDC (15…30 VDC) smoothed or pulsed
24 VDC (15…30 VDC) smoothed,
max. 10 % residual ripple
12 VDC (7.5…15 VDC) smoothed,
max. 10 % residual ripple
5 VDC (1…7 VDC) smoothed,
max. 10 % residual ripple
other values on request
Input current:
6 mA at 24 VDC
Input delay
E110 :
E111
:
E112
:
E116:
typically 8 ms
typically 0.2 ms
typically 9 ms
typically 0.2 ms
Resistance to interference:
acc. to IEC 801-4
2 kV under capacitive coupling
(whole trunk group)
Internal current consump-
tion: (from +5 V bus)
1 … 24 mA; typically 12 mA
Internal current consump-
tion: (from V+ bus)
0 mA
External current consump-
tion:
max. 48 mA (all inputs=1) at 24 VDC
Terminals:
Pluggable 10-pole screw terminal block
(4 405 4847 0), for wires up to 1.5 mm²