Hardware Manual for the PCD2.M5 Series│Document 26/856; Version EN 12│2014-07-24
Saia-Burgess Controls AG
Digital combined input/output modules
Input/output (I/O) modules
6-41
6
6.6.1 PCD2.B100, 2 2 o 4 digital inputs/outputs (selectable)
Application
Economical combined input/output module with:
● 2 inputs 24
V
DC
/8 ms for source operation, electrically connected
● 2 transistor outputs 0.5 A/5 …
32 V
DC
, electrically connected, not short-circuit-
protected, and
● 4 combined I/Os 24
V
DC
/ 8 ms or 0.5 A/5
…
32 V
DC
on shared I/O terminals.
Technical data on inputs
Number of inputs:
6 (2 + 4), electrically connected,
source operation
Input voltage:
24 V
DC
smoothed or pulsed
2 inputs E0 and E1
low-range:
high range:
-30
…
+5 V
+15
…
+32 V
4 inputs E/A2...E/A5
low-range:
high range:
-0.5
… +5 V *)
+15
…
+32 V
All 6 inputs:
low-high switching threshold:
Switching threshold 1-0:
Hysteresis:
Input current (at 24 V
DC
):
Switching delay 0-1 (at 24 V
DC
):
Switching delay 1-0 (at 24 V
DC
):
13 V typically
6 V typically
7 V typically
7 mA typically
8 ms typically
8 ms typically
*) Negative voltage is restricted by the protective diode (I
max
= 0.5 A)
Technical data on outputs
Number of outputs:
6 (2 + 4)
electrically connected,
source
operation
not
short-circuit-protected
Current:
5...500 mA steady load
Voltage range:
5
…
32 V
DC
*)
Voltage drop:
< 0.3 V at 500 mA for O6 and O7
< 0.7 V at 500 mA for I/O2...I/O5
Total current per module:
3 A steady load
Switch-on delay:
typically 10 µs
Switch-off delay:
50 μs typically (100 μs max.), (ohmic load 5..500 mA),
longer for inductive load because of protective diode.
*)
If the state of a combined output is to be read off,
voltage U
ext
must be at least 17 V
DC
, as the state and the LED are displayed via the
input.