![SBC PCD1 Series Manual Download Page 153](http://html1.mh-extra.com/html/sbc/pcd1-series/pcd1-series_manual_1205032153.webp)
Saia-Burgess Controls AG
Manual
Manual PCD 1 / PCD 2 Series
│ Document 26
/
737 E
N22 │ 2013-11-26
5
Input/output (I/O) modules
5-17
Digital input modules, electrically isolated
5.3.1 PCD2.E500, 6 digital inputs for 115 - 230 V
AC
Application
Module with 6 electrically isolated inputs for alternating current. The inputs are set up
for source operation and
have one common “COM” terminal
. Only the positive half-
wave of the alternating current is used.
Technical data
Number of inputs
6 electrically isolated from the CPU,
Source operation,
all inputs to the module in the same phase
Input voltage
115/230 V 50/60 Hz, sinusoidal
(80 to 250 V
AC
)
Input current
115 V
AC
:
5 … 6 mA (wattless current)
230 V
AC
:
10 … 12 mA (wattless current)
Input delay
switch-on:
switch-off:
typically 10 ms; max. 20 ms
typically 20 ms; max. 30 ms
LED
supplied directly from input current
Resistance to interference acc. to
IEC 801-4
4 kV under direct coupling
2 kV under capacitive coupling
(whole trunk group)
Electrical isolation voltage
2000 V
AC
, 1 min
Electrical isolation resistance
100 MOhm / 500 V
DC
Optocoupler isolation voltage
2.5 kV
Galvanic separation of outputs to Saia PCD
®
.
The channels themselves not are separated.
Internal current consumption:
(from +5 V bus)
< 1 mA
Internal current consumption:
(from V+ bus)
0 mA
External current consumption:
Terminals:
Pluggable 10-pole screw terminal block
(4 405 4847 0), for wires up to 1.5 mm²
Switch on/off level:
1
0
250 VAC
80 VAC
40 VAC
0 VAC