140
It is used to set the voltage value of the undervoltage fault UV of the inverter. 100.0% of the inverters with different
voltage levels correspond to different voltage points, respectively:
Single-phase 220V or three-phase 220V: DC200V
Three-phase 380V: DC350V
99 Monitoring Parameters
The 99 parameter group is used to monitor the running status information of the inverter. The user can view it
through the operation panel, or read the value of the parameter group through communication in order to view the
data on the spot or monitor the data of the host computer. Among them, 99-00 to 99-31 are the same as the
monitoring parameters defined in 08-03/08-04.
See the table below for details.
Parame
ter
Name
Unit
Parame
ter
Name
Unit
99-00
Running frequency(Hz)
0.01Hz
99-23
Reserved
99-01
Setting frequency(Hz)
0.01Hz
99-24
Line speed
1m/Min
99-02
Bus voltage(V)
0.1V
99-25
Current power-on time
1Min
99-03
Output voltage(V)
1V
99-26
Current running time
0.1Min
99-04
Output current(A)
0.01A
99-27
PULSE Input pulse frequency
1Hz
99-05
Output power(kW)
0.1kW
99-28
Communication setting value
0.01%
99-06
Output torque(%)
0.10%
99-29
Reserved
99-07
MI Input status
1
99-30
Main frequency X display
0.01Hz
99-08
MO Output status
1
99-31
Auxiliary frequency Y display
0.01Hz
99-09
AVI1 Voltage(V)
0.01V
99-32
View any memory address value
1
99-10
AVI2/ACI Voltage(V)
0.01V
99-33
Reserved
99-11
Reserved
99-34
Reserved
99-12
Calculation value
1
99-35
Target torque (%)
0.10%
99-13
Length
1
99-36
Reserved
99-14
Load speed
1
99-37
Reserved
99-15
PID setting
1
99-38
Reserved
99-16
PID feedback
1
99-39
V/f separation target voltage
1V
99-17
PLC stage
1
99-40
V/f separation output voltage
1V
99-18
PULSE Input pulse
frequency(Hz)
0.01kHz
99-41
Visual display of MI input status
1
99-19
Feedback speed(Unit 0.1Hz)
0.1Hz
99-42
Visual display of MO input status
1
99-20
Remaining running time
0.1Min
99-43
MI function status visual display 1
1
99-21
AVI1 voltage before calibration
0.001V
99-44
MI function status visual display 2
1
99-22
AVI2/ACI voltage before
calibration
0.001V
Summary of Contents for S3100A Series
Page 1: ...S3100Aseries inverter General Open loop Vector Control IM User manual User Manual ...