background image

The Savant

®

 CLI-8000 and CLI-8000A eight zone Thermostat Processing Units 

(TPU) are at the heart of the Savant

®

 Centralized Climate Control system. Through 

communications with a number of remote sensors and optional user interfaces, the 

Thermostat Processing Unit can manage up to eight heating, ventilation, and air 

conditioning (HVAC) systems. The system is easily integrated with most leading 

HVAC systems and can be designed as one part of a complete Savant

®

 Control 

System solution.
The CLI-8000 version is configured using the keypad and display located on the front 

panel. 
The CLI-8000A version is configured using a climate application loaded onto an 

Android™ based tablet (Android is a trademark of Google Inc). The tablet, which is 

installed into the front cover of the TPU, incorporates a touch screen interface with an 

elegant climate control application for setting up, viewing, and controlling each 

climate zone independently.
Once installed and configured, either system the can be integrated to add monitoring 

and control through an iOS device such as iPad

®

 or iPod

®

.

This Quick Reference Guide provides the information necessary to install the 

CLI-8000/8000A as well as information on wiring to each of the optional and required 

components of the Savant HVAC solution. 

Box Contents

(1) CLI-8000 or CLI-8000A (Includes all mating connectors from front panel)

(1) Samsung Galaxy Tab 3 (CLI-8000A only)

(1) Quick Reference Guide (this document)

Related Components

Savant

®

 Host

Savant

®

 Controller SSC-0008-XX, SSC-0025-XX

External 120V AC to 24V AC Transformer, PWR-2440-XX

Optional Remote Sensors

Savant

®

 SST-TEMP1 - Remote Indoor Sensor

Savant

®

 SST-OTEMP1 - Remote Outdoor Sensor

Savant

®

 CLI-THFM1 - Remote Humidity/Temperature Smart Sensor

Savant

®

 CLI-PLEN1C - Commercial Plenum Sensor (Heat duct sensor) 

Savant

®

 CLI-PLEN1R - Residential Plenum Sensor (Heat duct sensor) 

Savant

®

 CLI-SLAB1 - SLAB Sensor (Floor Heating Sensor)

Note:

 Each zone on the CLI-8000/8000A supports communications with up to four 

temperature sensors and two humidity sensors.

Specifications

Environmental

Environmental

Temperature

32° to 104°F

Humidity

10% to 90% Relative Humidity (non-condensing)

Dimensions and Weight

Dimensions and Weight

Height

12.17 inches (309.12 mm) with cover

Height

11.05 inches (280.67 mm) without cover

Width

15.48 inches (393.19 mm) with cover

Width

14.23 inches (361.44 mm) without cover 

Depth

2.81 inches (71.37 mm) with cover

Depth

2.71 inches (68.83 mm) without cover

Weight

8.75 lb. / 4.0 kg

Power

Power

Power (Input)

24V AC (40VA) from external transformer

Power Draw 

(Maximum)

CLI-8000 = 12W @ 24V AC

Power Draw 

(Maximum)

CLI-8000A = 24W @ 24V AC

Cable Requirements

Cable Requirements

Relay Bank to 

HVAC system

18 American Wire Gauge (AWG)

Standard HVAC wiring  (RH, RC, W1, W, Y1, Y2, O, G, Aux)

Cable Requirements (Sensors)

Cable Requirements (Sensors)

Data Sensor 

Bus (1-Wire)

24 AWG (Cat 5) 600 feet (182 m) maximum (cumulative)

Remote Sensor 24 AWG (Cat 5) 500 feet (152 m) maximum

Compliance

Compliance

Safety and 

Emissions

FCC Part 15

RoHS

Compliant

Additional Info

Additional Info

RS-232

Baud Rate = 19200

CLI-8000/8000A Front Panel View

Item

Item

Description

A

Ethernet

Reserved for Future Use

B

HVAC Relays

Each relay bank or zone gets wired to an HVAC 

system. The CLI-8000/8000A supports wiring up to 

eight individual HVAC systems.

C

RS-232

Connect cable from the RS-232 port to a Savant 

Controller. Communication between the controller 

and the CLI-8000/8000A is achieved over the 

RS-232 connection. RS-232 supports 19200 baud.

D

Station Bus

Reserved For Future Use

E

Console

Mini USB (Mini-B) female connector (Serial UART); 

Debug terminal

F

DSB/1-Wire

The DSB/1-Wire Connector connects to the Data 

Sensor Bus, which is a serial bus based on the 1-

Wire protocol. The CLI-THFM1 smart sensor 

communicates over the Data Sensor Bus through 

this connection. Up to two smart sensors per zone 

can be configured with a total of eight per system.

G

Display/Keypad

Monitors and configures the system. Use the keypad 

to scroll through the available menus and configure 

each zone.

H

Remote Sensors

Indoor, Outdoor, Slab, and Plenum two-wire 

temperature sensors are connected here. A 

maximum of two per zone is supported. 

I

Input Power

(Access)

Remove the power input access screw and remove 

the associated panel. This will give user access to 

the power supply board for wiring the 24V AC input 

power.

J

Zone LEDs

The Zone LED’s indicate which zone has been 

selected via the keypad for configuration. 

K

Input Power
(24V AC)

System is powered by 24V AC power source. Power 

cable is fed through 

½

 inch cable restraint (not 

included) installed at bottom of box. Input power is 

wired to a two position screw terminal block on the 

power supply board.

L

Analog Control

Reserved for Future Use

M

USB

The USB port connects to the optional Android™ 

based tablet. Communication between the tablet and 

the CLI-8000A version of TPU is achieved through 

the USB port.

N

Smart Connect

Maintenance functions such as firmware upgrades 

are achieved through the Smart Connect 

connection. Requires SCA-CONF-XX or SCA-

CONFL-XX Smart Connect cable.

Thermostat Processing Unit

(CLI-8000-00 / CLI-8000A-00)

Quick Reference Guide

Scan this QR code for additional 

product information.

009-1090-01

CLI-8000-00

CLI-8000A-00

009-1090-01

31314

Savant Confidential and Proprietary

1

of 2

Reviews: