TRA 410, 421

Description of operation

8.2  Description of parameters for TRA 421

Symbol

Procedure

Changing parameters:

Select the “Parameters” menu by pressing and turning twice to the 

right.

The “Code” symbol flashes.

Press to confirm the selection.

Enter the four-digit service code by turning and pressing.

Factory setting: 1234

Press to confirm the entry.

The 

 symbol is displayed.

Press to confirm the entry.

The individual digits of the parameter number are entered by turn-

ing and pressing.

Press to confirm the entry.
Preset control algorithms for the following applications:

Factory setting: 0

0 = standard underfloor heating

1 = low-energy underfloor heating

2 = radiator

3 = passive convector (slow warm-up period)

4 = fan convector (fast warm-up period)

Activating/deactivating cooling lock

Factory setting: 0

0 = deactivated

1 = activated

Note: When the cooling lock is activated and the operating mode is 

set to cooling, the heating mode is also inactive.

Protects the locking of the operation with a code:

Factory setting: 0

0 = deactivated

1 = activated

Note: The locking must be activated in the “Operating modes” 

menu.

Change the code for locking operation.

Factory setting: 0000

Activating an external sensor.

Factory setting: 0

0 = internal sensor is operating

1 = external sensor is operating; internal sensor is deactivated

2 = input for external floor sensor is activated

Note: This is a comfort temperature. As soon as the floor temper-

ature has been reached, the internal sensor takes over controlling 

the room. Set the setpoint temperature of the external sensor in 

the “Settings” menu

Setting/correcting the floor temperature. 

Factory setting: 0 °C

A difference in the actual floor temperature can be corrected.

Setting range -2 °C to +2 °C.

Set the duration of the backlight of the display.

Factory setting: 15 seconds

Determines the time period for which the display is illuminated after 

operation.

Setting range: 0 to 30 seconds (in 5-second steps).

Summary of Contents for TRA 410

Page 1: ...ECC room thermostat TRA 410 TRA 421 Technical manual...

Page 2: ...2 19 TRA 410 421 P100015830 B...

Page 3: ...Liability limitation 6 2 3 Intended use 6 3 Setting the setpoint temperature 7 4 Functions settings parameterisation 8 5 Connection diagrams 9 6 Dimension drawing 10 7 Overview of display 11 8 Descrip...

Page 4: ...4 19 TRA 410 421 P100015830 B...

Page 5: ...l when it is dis connected from the power supply Only use the device when it is in a technically perfect condition Adhere to the ambient conditions specified in the fitting instructions 1 1 Meaning of...

Page 6: ...ctions Failure to observe the operating instructions Improper usage Use of untrained staff Unauthorised modifications Technical changes In all other cases the obligations agreed to in the supply contr...

Page 7: ...the setpoint temperature The setpoint temperature is set by turning the rotary knob to the left or the right 1 Turn the rotary knob to the LEFT The temperature is decreased Or 1 Turn the rotary knob t...

Page 8: ...ple operation and settings Standard display In the standard display all room temperature controllers show the current actual temperature and the active functions The TRA421 also has a clock function O...

Page 9: ...TRA410F210 TRA410F212 2 pt NTC 230 V 230 V L N 1 2 1 2 1 2 1 2 a b c d 2 pt NTC 24 V LS LS MM 1 2 1 2 1 2 1 2 a b c d TRA421F210 TRA421F212 2 pt NTC 230 V L L CO N NTC 22k out N 230 V 1 2 1 2 1 2 1 2...

Page 10: ...10 19 P100015830 B TRA 410 421 Dimension drawing 6 Dimension drawing...

Page 11: ...0 B Overview of display 7 Overview of display 1 2 1Display 2Rotary knob with turning and pressing mechanism TRA 410 TRA 421 Symbol Description P P Operating modes P P Settings P Parameters P P Heating...

Page 12: ...ale for time pro gramme one unit one hour P P Current temperature setpoint temperature P P C Correction of effect of wall temperature P P Celsius temperature unit P Fahrenheit temperature unit P P Min...

Page 13: ...nfirm the selection Note Decrease via the room thermostat or an external signal or time programme Both cannot be activated TRA 410 Decrease of 2 C Note When the decrease is selected the Decrease input...

Page 14: ...rm the entry P Set the setback temperature in the Cooling ECO mode Factory setting 23 C Press to confirm the selection Turn to set the setpoint temperature that you want Press to confirm the entry P S...

Page 15: ...he button to select the finishing point Press to confirm Turn to the right to call up the next time programme Turn to the left BACK to leave the time programme P P Correction of effect of wall tempera...

Page 16: ...k is activated and the operating mode is set to cooling the heating mode is also inactive Protects the locking of the operation with a code Factory setting 0 0 deactivated 1 activated Note The locking...

Page 17: ...ling mode is initiated in good time ahead of the de fined time 0 deactivated 1 activated Set the cycle time for the valve protection facility Factory setting 14 days Prevents the plug from sticking in...

Page 18: ...f f No external sensor present f f External sensor does not correspond to specifications f f Deactivate the external sensor in parameter setting 040 f f Check the external sensor and replace if necess...

Page 19: ...Fr Sauter AG Im Surinam 55 CH 4016 Basel Tel 41 61 695 55 55 Fax 41 61 695 55 10 www sauter controls com info sauter controls com Printed in Switzerland...

Reviews: