16.26 Alarm setting
Permits configuration of all alarms.
Select the appropriate alarm number (from the alarm list). The alarm text for the alarm
will be displayed and the alarm priority can be set; "A-alarm", "B-alarm", "C-alarm" or
"not active". The extra stop function gives, for each alarm, the option to stop or not stop
the unit on alarm activation.
Run Error supply air
Priority: B-alarm
Extra stop function
Active
Alarm text
The alarm text that should be shown in the display when there is an alarm can be
changed using CASE flexotron®. For more information, see the CASE flexotron®
manual.
Alarm list
The alarm text and priority columns show the factory set values.
.No
Alarm text
Pri
Description
1
Run Error Supply Air
Fan
B
Malfunction Supply air fan
2
Run Error Extract Air
Fan
B
Malfunction Extract air fan
3
Run Error P1-Heater
B
Malfunction pump, Heating circuit
4
Run Error P1-Cooler
B
Malfunction pump, Cooling circuit
5
Run Error P1-
Exchanger
B
Malfunction pump, Liquid connected exchanger
6
Filter guard
B
Filter guard pressure switch activated
7
Flow switch
B
Flow switch activated
8
External frost guard
A
External Frost protection thermostat activated
9
Deicing pressure
guard
-
Exchanger de-icing pressure switch activated
10 Fire alarm
A
Fire alarm activated
11 External switch
C
"External switch" activated
12 External alarm
B
External alarm activated
13 Supply Air control
error
B
Supply air temp deviates too much from the
setpoint for too long.
14 Humidity control error -
The room humidity deviates too much from the
setpoint.
15 High supply air temp
B
Supply air temp too high
16 Low supply air temp
B
Supply air temp too low
17 Supply air temp max
-
Maximum limiting of supply air temp active
18 Supply air temp min
-
Minimum limiting of supply air temp active
19 High room temp
B
Room temp too high during room temp control
20 Low room temp
B
Room temp too low during room temp control