Appendix
80
BA_EQJW126F001_EN001
OT deactivation value in rated operation
0.0 to 50.0 °C
OT deactivation value in reduced operation
–20.0 to 50.0 °C
OT activation value in rated operation
–20.0 to 5.0 °C
Gradient, return flow
0.2 to 3.2
Level, return flow
–30.0 to 30.0 °C
Base point for return flow temperature
5.0 to 90.0 °C
Max. return flow temperature
5.0 to 90.0 °C
Parameters
PA1
Range of values
Day set point for flow temperature
5.0 to 130.0 °C
Night set point for flow temperature
5.0 to 130.0 °C
Set point boost of primary heat exchanger
control
0.0 to 50.0 °C
Set point for binary demand processing
5.0 to 130.0 °C
Function block parameters
CO1
Range of values
F03 - 1: KP (limiting factor)
0.1 to 10.0
F05 - 1: Start temperature
20 to 60 °C
F05 - 1: Temperature rise per day
0.0 to 10.0 °C
F05 - 1: Maximum temperature
25.0 to 60.0 °C
F05 - 1: Maintaining time of max. temp.
0 to 10 days
F05 - 1: Temperature reduction per day
0.0 to 10.0 °C
F09 - 1: Cycle time
0/1 to 100 min
F09 - 1: KP (gain)
0.0 to 25.0
F12 - 1: KP (proportional gain)
0.1 to 50.0
F12 - 1: Tn (reset time)
1 to 999 s
F12 - 1: TV (derivative-action time)
0 to 999 s
F12 - 1: TY (valve transit time)
5 to 240 s
F12 - 0: Hysteresis
1.0 to 30.0 °C
F12 - 0: Min. ON time
0 to 10 min
F12 - 0: Min. OFF time
0 to 10 min
F13 - 1: Max. deviation
2.0 to 10.0 °C
Summary of Contents for equitherm EQJW126F001
Page 5: ...Contents BA_EQJW126F001_EN001 5 12 5 Customer data 80 ...
Page 9: ...BA_EQJW126F001_EN001 9 Operation Fig 1 Icons ...
Page 27: ...BA_EQJW126F001_EN001 25 Functionsoftheheatingcircuit 24 BA_EQJW126F001_EN001 ...
Page 28: ......
Page 34: ...26 BA_EQJW126F001_EN001 Functionsof theheatingcircuit limits the value ...
Page 38: ...Functionsof theheatingcircuit 32 BA_EQJW126F001_EN001 ...
Page 45: ...Functionsoftheheatingcircuit BA_EQJW126F001_EN001 39 ...
Page 49: ......
Page 57: ...BA_EQJW126F001_EN001 47 Operationalfaults 46 BA_EQJW126F001_EN001 ...
Page 58: ......
Page 60: ...Operationalfaults 48 BA_EQJW126F001_EN001 available ...
Page 63: ......
Page 68: ...54 BA_EQJW126F001_EN001 Electrical connection block CO6 F04 1 is activated ...
Page 74: ...Electrical connection 56 BA_EQJW126F001_EN001 ...
Page 79: ...Installation BA_EQJW126F001_EN001 61 60 BA_EQJW126F001_EN001 ...
Page 80: ......
Page 92: ......