EQJW 125: Heating controller
Resistance values for the Ni1000 sensors
58
7001029003 A
© Fr. Sauter AG
10
Resistance values for the Ni1000 sensors
The temperature sensors required depending on the use of the EQJW 125
must conform to DIN 43760.
Temperature (°C)
Resistance value ( ) Ni1000
90
1549
80
1483
70
1417
60
1353
50
1291
40
1230
30
1171
20
1112
10
1056
0
1000
–10
946
–20
893
–30
842
–40
791
Tab. 8: Resistance value Ni1000
The resistance value of the nickel measuring resistor changes in relation to
the temperature. The temperature coefficient is always positive, i.e. the
resistance increases as the temperature rises. See the table of values
(DIN 43760). Within the specified tolerances, the sensors can be exchanged
without calibration.