MMI 810.1 / 811.1
Gas burner automatic
safety control
For 2-stage forced draught and combi oil/
gas burners
Possible flame detectors:
- Ionization probe
- Infrared flicker detector
INTRODUCTION
The gas burner automatic safety control MMI controls
and monitors blown gas- and combined burners of any
nominal thermal load (tested and certified according to
EN 298).
The automatic safety controls MMI 810.1 models 13, 33 and
35 can also be utilized for burners on fixed hot air heaters
(Direct air heaters according to DIN 4794).
Various types and model designations differentiate the
automatic safety controls with respect to the programme
times, as well as with regard to differing national standards.
TYPES AVAILABLE
MMI 810.1
Mod. 13 *
Art. Nr. 0620720
Mod. 33
Art. Nr. 0620220
Mod. 35
Art. Nr. 0620920
Mod. 43
Art. Nr. 0622520
Mod. 55
Art. Nr. 0621320
MMI 811.1
Mod. 35
Art. Nr. 0621120
Mod. 63
Art. Nr. 0620420
* Must only be used on boilers or other applications where
the 10 second pre-purge time is sufficient to provide at
least 3 volume changes of the combustion chamber.
CONSTRUCTIONAL FEATURES
The automatic control is housed in a non-inflammable,
transparent, plug-in type plastic case and contains:
–
Synchronous motor with speed reducer gears as the
drive for the switching cam
–
Switching cam with informative programme display in
colour
–
12 times cam drive for controlling the programme
sequence
–
Plug-in type circuit boards with the electronic components
The following important indicating - and operating elements
are located on the front panel of the automatic control:
– Illuminated pushbutton for indication of malfunctions
and reset
– Programme display in colour
– Screw for central mounting
For external resetting, the remote reset device FR 870
(art. No. 70700) can be utilized. (Refer to doc. 750).
TECHNICAL DATA
Operating voltage
220 / 240 V (-15... +10%)
50 Hz (50 - 60 Hz)
Differing frequency
Results in a proportional
deviation of the time.
Rating fuse
max. 10 A rapid, 6 A slow
Power consumption
10 VA
Max. load per output:
- term. 3
2A, cos
ϕ
0.2
- term. 4, B
2A, cos
ϕ
0.4
- term. 5, 6
1A, cos
ϕ
0.4
total load
5A, cos
ϕ
0.4
Amplifier sensitivity
1
µ
A
Minimum required
Ionization current
5
µ
A
Flame detector cable
max. 20 m cable length
Air pressure monitor
working contact 4 A, 230 V
Waiting time for
malfunction remedy
None
Flame detector
- Ionization probe
- Infrared flicker detector
IRD 1020
Weight, incl. base
350 g
Mounting position
any
Insulation standard
IP 44
Admissible ambient
temperature for controller
and flame detector
-20
°
C… +60
°
C
Classified acc. to EN 298
BTLLXN
0708.21-01-e/04/99
program
MMI 810.1
811.1
timings (sec.)
Modell
13
33
35
43
55
35
63
Waiting time
at start ca.
tw
6
9
9
9
9
9
6
Max. reaction
time for air
proving switch tlw 3.5
6
6
6
17
6
5
Pre-purge time tv1
3
24
24
40
20
24
55
Pre-ignition
time
tvz
2
3
3
3
15
3
3
T. ignition time
tz
5
6
8
6
20
8
5.5
Safety time
ts
3
3
5
3
5
5
3
Time delay
term.6/term.C tv2
6
10
10
10
10
10
6