MMI 810.1 / 811.1

Gas burner automatic
safety control

For 2-stage forced draught and combi oil/
gas burners

Possible flame detectors:
- Ionization probe
- Infrared flicker detector

INTRODUCTION

The gas burner automatic safety control MMI controls
and monitors blown gas- and combined burners of any
nominal thermal load (tested and certified according to
EN 298).
The automatic safety controls MMI 810.1 models 13, 33 and
35 can also be utilized for burners on fixed hot air heaters
(Direct air heaters according to DIN 4794).
Various types and model designations differentiate the
automatic safety controls with respect to the programme
times, as well as with regard to differing national standards.

TYPES AVAILABLE

MMI 810.1

Mod. 13 *

Art. Nr. 0620720

Mod. 33

Art. Nr. 0620220

Mod. 35

Art. Nr. 0620920

Mod. 43

Art. Nr. 0622520

Mod. 55

Art. Nr. 0621320

MMI 811.1

Mod. 35

Art. Nr. 0621120

Mod. 63

Art. Nr. 0620420

*  Must only be used on boilers or other applications where

the 10 second pre-purge time is sufficient to provide at
least 3 volume changes of the combustion chamber.

CONSTRUCTIONAL FEATURES

The automatic control is housed in a non-inflammable,
transparent, plug-in type plastic case and contains:

Synchronous motor with speed reducer gears as the
drive for the switching cam

Switching cam with informative programme display in
colour

12 times cam drive for controlling the programme
sequence

Plug-in type circuit boards with the electronic components

The following important indicating - and operating elements
are located on the front panel of the automatic control:
– Illuminated pushbutton for indication of malfunctions

and reset

– Programme display in colour
– Screw for central mounting

For external resetting, the remote reset device FR 870
(art. No. 70700) can be utilized. (Refer to doc. 750).

TECHNICAL DATA

Operating voltage

220 / 240 V (-15... +10%)
50 Hz (50 - 60 Hz)

Differing frequency

Results in a proportional
deviation of the time.

Rating fuse

max. 10 A rapid, 6 A slow

Power consumption

10 VA

Max. load per output:
- term. 3

2A, cos 

ϕ 

0.2

- term. 4, B

2A, cos 

ϕ 

0.4

- term. 5, 6

1A, cos 

ϕ 

0.4

total load

5A, cos 

ϕ 

0.4

Amplifier sensitivity

µ

A

Minimum required
Ionization current

µ

A

Flame detector cable

max. 20 m cable length

Air pressure monitor

working contact 4 A, 230 V

Waiting time for
malfunction remedy

None

Flame detector
- Ionization probe
- Infrared flicker detector

IRD 1020

Weight, incl. base

350 g

Mounting position

any

Insulation standard

IP 44

Admissible ambient
temperature for controller
and flame detector

-20

°

 C… +60

°

 C

Classified acc. to EN 298

BTLLXN

0708.21-01-e/04/99

program

MMI 810.1

811.1

timings (sec.)

Modell

13

33

35

43

55

35

63

Waiting time
at start ca.

tw

6

9

9

9

9

9

6

Max. reaction
time for air
proving switch tlw 3.5

6

6

6

17

6

5

Pre-purge time tv1

3

24

24

40

20

24

55

Pre-ignition
time

tvz

2

3

3

3

15

3

3

T. ignition time

tz

5

6

8

6

20

8

5.5

Safety time

ts

3

3

5

3

5

5

3

Time delay
term.6/term.C tv2

6

10

10

10

10

10

6