INSTALLER 
MANUAL 

 
 
 
 
 
 
 
 
 
 
 

SATEL sp. z o.o. 

ul. Budowlanych 66 

80-298 Gda

ń

sk  

POLAND 

tel. +48 58 320 94 00 

www.satel.eu 

perfecta-t_i_en 11/18 

 Firmware Version 

1.02 

      

Alarm Control Panel 

      

Summary of Contents for PERFECTA 16

Page 1: ...INSTALLER MANUAL SATEL sp z o o ul Budowlanych 66 80 298 Gdańsk POLAND tel 48 58 320 94 00 www satel eu perfecta t_i_en 11 18 Firmware Version 1 02 Alarm Control Panel ...

Page 2: ...s under the warranty SATEL s goal is to continually upgrade the quality of its products which may result in some changes of their technical specifications and firmware The current information on the introduced modifications is available on our website Please visit us http www satel eu Hereby SATEL sp z o o declares that this control panel is in compliance with the essential requirements and other ...

Page 3: ...Control panel power up start up procedure 16 6 10 4 Starting the service mode 16 6 10 5 Emergency procedure of the control panel start up 16 6 10 6 First steps after starting up the control panel 17 6 11 Programming addresses for the hardwired keypads 17 6 11 1 Programming the address by means of the service function 17 6 11 2 Programming the address without entering the service mode 18 6 12 Ident...

Page 4: ...ngle EOL and Double EOL configuration Electrical protection of all zones Maximum number of programmable zones 32 20 zone types Outputs 4 programmable hardwired outputs on the control panel mainboard 2 high current outputs 2 low current outputs OC type Maximum number of programmable outputs 16 outputs with numbers from 13 to 16 are dedicated outputs for operating the MSP 300 wireless sirens 23 perf...

Page 5: ...Event log 3584 events Users 15 users Capability to assign to the user code keyfob Authority level determining the scope of access to the system Timers 8 timers to automatically arm disarm the partitions control the outputs switching the lights on off watering the garden etc Programming Local programming keypad computer with the PERFECTA SOFT program installed connected to the control panel RS 232 ...

Page 6: ...ndicating the status of the partitions and the system 12 keys bearing designations according to telephone standard and intended for entering data 4 additional keys for menu navigation and arming disarming Backlit keys Tamper contact reacting to the enclosure opening or detaching from the wall 4 Expansion modules You can connect to the control panel the following expanders INT RX S 433 MHz keyfobs ...

Page 7: ...itions etc decrease the range of radio signal Keep this in mind when choosing the installation place for control panel The control panel and other alarm system components should be installed within the protected area 6 2 Estimation of the system current consumption At the security system planning stage you should sum up the currents consumed by all devices included in the system control panel main...

Page 8: ...rrectly e g the control panel will be unable to identify devices absence of devices will be reported etc When selecting the length of cables follow recommendations set out in sections on connection of particular types of devices Avoid running the cables in parallel to or in close vicinity of the 230 V AC wires as this may result in malfunctioning of the system 6 4 Installation of control panel The...

Page 9: ...starting the control panel see Emergency procedure of the control panel start up p 16 RS 232 TTL port battery connection cables red black LED indicating the status of control panel telephone communicator wireless system module only PERFECTA T 32 WRL mini jack socket for connecting microphone Description of terminals AC power input 18 V AC OUT1 OUT2 programmable high current outputs 12 V DC voltage...

Page 10: ... power supply The Table 1 shows the number of wires required for correct connection of the device to the expander bus if conductors with 0 5 mm diameter are used CLK DTA COM Distance Number of wires up to 300 m 1 1 1 300 600 m 2 2 2 Table 1 For most devices to be connected to the communication bus setting of a suitable address is required Two devices must not share the same address otherwise their...

Page 11: ...enclosure base 5 Using wall plugs screw anchors and screws fasten the enclosure base to the wall The wall plugs and screws must be selected so as to suit the mounting surface must be different for concrete and brick different for plaster or wood etc 6 Connect the keypad terminals to the corresponding terminals of the control panel see Fig 4 7 Put the cover on the catches and snap the enclosure shu...

Page 12: ...he module enables 433 MHz keyfobs to be assigned to the users up to 15 keyfobs Address 7 07h must be set in the module Fig 5 Connecting the INT RX S expansion module to the control panel Fig 6 Setting DIP switches in the INT RX S expansion module 6 5 3 Connecting the hardwired zone expanders You can connect 3 INT E zone expanders to the control panel Each expander allows adding 8 programmable wire...

Page 13: ...der Table 2 shows numbering of the expander zones depending on the address set If a number of expander zone coincides with a number of wireless zone the expander zone will not be supported Expander address decimally hexadecimally Zone numbers 12 0C 9 16 13 0D 17 24 14 0E 25 32 Table 2 The expander can be identified as INT E no dedicated power supply is connected to the expander or INT EPS dedicate...

Page 14: ... O expander to the control panel Fig 10 Setting DIP switches in the INT O expander Fig 11 Setting DIP switches in the INT ORS expander 6 6 Connecting detectors and other devices to the zones Zones of the control panel support the following wiring configurations NC wiring configuration that allows connecting a detector with NC normally closed alarm output Opening the circuit will trigger an alarm N...

Page 15: ... The ways to connect detectors to zones The detector outputs are designated with letters A alarm T tamper End of line resistors For the Single EOL configuration use a 2 2 k resistor to close the circuit For the Double EOL 2EOL configuration use two 1 1 k resistors 6 7 Connecting the sirens It is recommended that the control panel be started without connected sirens This will prevent accidental tri...

Page 16: ...erminal in the vicinity of equipment which generates noise during operation e g fans air conditioners refrigerators 6 9 Connecting the analog telephone line The control panel works only with the analog telephone line Telephone signals and alarm system signals must not be sent over a single multicore cable Otherwise the system can be damaged if a high voltage disruptive discharge from the telephone...

Page 17: ...rical installation of the facility Make sure that the circuit you choose for powering the control panel will be always alive The circuit must be provided with a 2 pole switch disconnector with at least 3 mm contact separation and or short circuit protection with a 16 A time delay fuse The owner or user of the alarm system should be instructed on how to disconnect the transformer from the mains e g...

Page 18: ...ence first the battery then the 230 V AC mains will ensure proper operation of the power supply unit and the electronic protection circuits thus preventing damage to the alarm system components caused by installation mistakes if any If it is necessary to de energize the control panel turn off the main power supply AC first and the backup power supply battery afterwards Observe the above described ...

Page 19: ... identification of devices connected to the communication bus of the control panel Control panel without wired keypads PERECTA T 32 WRL If no wired keypads are connected to the control panel then after starting the control panel with factory settings 1 Connect computer to alarm control panel 2 Use the PERFECTA SOFT program to add wireless keypads 3 Run the function of identification of devices con...

Page 20: ... Connect wires properly to the CLK and DTA keypad terminals 10 Power on the keypad 6 12 Identification of devices connected to the bus Devices connected to the communication bus will not be properly supported unless they have been identified by the control panel Identification of the devices is required after the first start up of the control panel and then each time after a new device is added or...

Page 21: ...ds up to 32 wireless detectors up to 4 wireless sirens After starting the control panel and identifying the devices used in conjunction with the control panel you can proceed to install the 433 MHz wireless devices Before installation of the wireless device 1 Insert battery into the device 2 Enroll the device in the control panel You can do so by using the PERFECTA SOFT program or LCD keypad 3 Che...

Page 22: ... outputs with a number from 13 to 16 The wireless siren will be assigned to this output after the adding procedure is finished 3 Click on 4 The wireless device adding panel will be displayed 5 In the Serial no field enter the serial number of the siren You will find it on the electronics board of the siren 6 Open momentarily the siren tamper switch 7 When the Device s data read message appears cli...

Page 23: ...ector you want to remove is assigned 3 Click on 4 In the window that will be displayed click on Delete to confirm that you want to remove the detector 5 Click to save changes to the control panel Removing wireless siren 1 Click on the Outputs tab 2 Click on the output to which the siren you want to remove is assigned 3 Click on 4 In the window that will be displayed click on Delete to confirm that...

Page 24: ... of zones that will be wireless ones oincides with the number of a wireless zone the wired If the number of a wired zone c zone will not be supported 7 2 Numeration of outputs 7 2 1 Hardwired outputs The outputs on control panel main board have numbers from 1 to 4 The outputs in expander have numbers from 5 to 12 7 2 2 Wireless outputs PERFECTA T 32 WRL numbers from 13 to 16 8 Specifications The w...

Page 25: ...zones 32 Hardwired programmable outputs 4 Maximum number of programmable outputs 16 Power supply outputs 2 Communication buses 1 Keypads up to 4 Partitions 2 Telephone numbers for messaging 8 Voice messages 16 Users 15 Timers 8 Event log 3584 Security grade according to EN50131 Grade 2 Environmental class accor Operating temperature ran humidity 93 3 Electronics board dimensio PERFECTA T 32 WRL 16...

Page 26: ...24 PERFECTA T SATEL Enclosure dimensions 139 x 124 x 22 mm Weight 246 g ...