32
KNX-BSA12L
• KNX-BSA12H
SATEL
Channel communication objects
No.
Object name
Object function
Data type
Flags
34
Channel A
Channel error
alarm
1 bit,
DPT 1.011
C, R, T
The object allows sending a telegram to the KNX bus with error information when the
channel A reports incorrect position, mechanical jam of the blind/shutter, no power / supply
circuit fault, motor overheating or obstacle detection by smart motor. In the event of an
error, the object assumes a value of “1”. The telegram is sent after the event occurs and
cyclically at defined intervals. You can disable the cyclic sending by entering “0” in the
“Interval of cyclic device error (alarm) sending” field in the tab for defining channel
operating parameters (e.g. “A: Venetian blind”).
Telegram:
1 = error in the channel,
0 = channel is workin correctlly.
Flag: C
– communication, R – read, W – write, T – transmit, U – update.
Functions
Channel communication objects
No.
Object name
Object function
Data type
Flags
24
Channel A
Scene
1 byte
DPT 17.001
DPT 18.001
C, W
The object will be enabled if you select “Enable” for the “Scene” parameter in the tab for
configuring the channel
settings (e.g. “A: Venetian blind”). The object enables sending
a 1-byte telegram, which can call up a scene or activate the scene learning function.
Such a telegram contains the scene number (1-64) and information about whether the
scene is to be called, and whether learning is to be enabled during which the current value
set in the channel will be saved for the scene with this number. To enable the function of
scene learning by the channel, select “yes” for the “Learning scenes from bus” parameter in
the
“Scene” tab for the channel A.
See