18
KNX-BSA12L
• KNX-BSA12H
SATEL
Switch-on delay when down
– time that must elapse from the moment of receiving the
“START” control signal by the motor to the moment when its rotor reaches the speed
enabling the blind/shutter to travel down (50
– 16384 [milliseconds]; default = 100).
Shutter / awning / window
The parameters described below are only available for the manual detection of travel time.
Travel time in two directions
– defines how the shutter travel time will be determined:
no
– based on the measurement of time of travel in one direction, e.g. from the upper to
the lower end position. Default value.
yes
– based on the measurement of time of travel in two directions, from the upper to the
lower end position and from the lower to the upper end position.
Travel time
– shutter travel time from one to the other end position, see Fig. 4, 6 and 7
(0 -
480000 [milliseconds]). The field is available when the “no” option is selected for the
“Travel time in two directions” parameter.
For precise determination of the shutter operating parameters, it is recommended that
measurements of travel time in two directions be taken.
Travel time up
– shutter travel time from the lower to the upper end position, see Fig. 4, 6
and 7 (0 - 480000 [milliseconds]). The field is avai
lable if the “yes” option is selected for
the “Travel time in two directions” parameter.
Travel time down
– shutter travel time from the upper to the lower end position, see Fig. 4, 6
and 7 (0 -
480000 [milliseconds]). The field is available if the “yes” option is selected for
the “Travel time in two directions” parameter.
Additional travel to end position
– allows you to adjust the position of the blind/shutter
when moving to the end position (0
– 125 [%]; default = 25). In the case of manual
detection, the blind/shutter end positions are defined in the module, based on the taken
measurements of the travel time. If the blind/shutter reaches the position stored in the
module as its end position, the module output is turned off. Entering a value greater than
“0” in the field means that after the blind/shutter reaches the end position, the module
output will remain on for the time needed to move the blind/shutter by this value. Entering
the value
“0” in the field means that after the blind/shutter reaches its end position,
the module output will be turned off.
Venetian blind
The parameters described below are only available in the case of manual detection of travel
time.