68 Programming
SATEL
The timers can be programmed:
using the keypad, in the service mode, by means of the functions available in the T
IMERS
submenu;
using the D
LOAD
X program, in the "Timers" window.
The following can be programmed for each timer:
individual name (up to 16 characters);
activation/deactivation time:
– individually for each day of the week;
– daily – the timer will be turned ON/OFF according to these settings, unless it has been
programmed for a specific day of the week;
arming mode that will be activated by the timer;
4 exceptions – time periods when the timer will be activated/deactivated at a different time.
If a year is programmed for an exception, the setting will only be valid for the current year.
If no year is programmed (the 9999 sequence is entered in the keypad instead of the
year), the exception will be valid every year.
Additionally, the U
SER EDITS
option is available for each timer. If it is enabled, the user can
edit the above mentioned timer parameters using the T
IMERS
user function available in the
C
HANGE OPTIONS
submenu.
Parameters of the timers indicated as the controlling ones for the 120. T
HERMOSTAT
type output can be edited by the user even if the U
SER EDITS
option is disabled (see:
section 120. T
HERMOSTAT OUTPUT PARAMETERS
p. 53).
8. User schedules
User schedules should be defined for the needs of the S
CHEDULE
type users (see: U
SER
MANUAL
). You can program the user schedules:
using the keypad, in the service mode, by means of the functions available in the U
SER
SCHEDULES
submenu;
using the D
LOAD
X program, in the "Timers" window, "User Schedules" tab.
For each user schedule, you can:
program an individual name (up to 16 characters);
indicate the timers which will determine when the user will have access to the system.
9. Reporting
The control panel can send event codes to the monitoring station:
via telephone line;
over the Ethernet network – if ETHM-1 module is connected,
using GPRS technology – if the SATEL GSM module is connected.
The control panel will make an attempt to send an event code according to the following
order:
1. over the Ethernet,
2. using GPRS technology,
3. by telephone (main and reserve telephone number).
The procedure will be terminated when the event is successfully sent to the monitoring
station by means of one of above mentioned transmission methods. Otherwise, the control