Satel INTEGRA 128 Plus Programming Manual Download Page 38

36 Programming 

SATEL 

Audible alarm after verification

 [Bell on 2nd] – if this option is enabled, the alarms from 

zones with the P

RE

-

ALARM 

or W

ITH VERIFICATION 

option enabled will only trigger loud alarm 

signaling after verification. The unverified alarms will not trigger loud alarm signaling. 

Partition timer 

Partitions can be controlled with an additional timer, which can be programmed: 

 in the keypad, using the function available in the user menu ([

code

]  

O

PTIONS 

PROGRAMMING 

P

ARTITION TIMERS

); 

  in the DLOADX program 

connected to the control panel

,

 

in the "Structure" window, 

"System" tab, after clicking on the partition name and then on the "Partition timer" button. 

3.3  Zones 

The zone is a separated portion of the protected area which can be supervised by a detector 
or detectors. A zone can only be assigned to one partition. 
The system supports the following zones: 

 

hardwired

 – on the control panel electronics board, in keypads and expanders. 

The number of available hardwired zones is determined by the control panel during 
identification procedure. 

 

wireless

 – when the ACU-100 or ACU-250 controller is connected. The number of 

available wireless zones depends on the number of wireless devices registered in the 
system and is determined during the procedure of adding the devices. 

 

virtual

 – zones which physically do not exist, but have been programmed as F

OLLOW 

OUTPUT

 or are controlled by means of a keyfob. 

3.3.1  Assigning zones to a partition 

The zones can be assigned to a partition: 

  using the keypad, in the service mode, by means of the Z

ONES

 function (

S

TRUCTURE

 

S

YSTEM

 

P

ARTITIONS

 

S

ETTINGS

 

[

Part. Name

Z

ONES

) – see: S

ELECTION FROM THE 

MULTIPLE

-

CHOICE LIST

 p. 21

  using the D

LOAD

X program: 

1.  in the "Structure" window, "System" tab, after clicking on the partition name. Click on 

the "Add" button to display the list of zones which can be assigned to the selected 
partition. Click on the zone which is to be assigned to the partition. 

2.  in the "Zones" window, "Zones" tab, "Part." column, enter the number of partition to 

which the given zone is to be assigned. 

3.3.2  Programming the EOL resistor values 

The value of end-of-line resistors is programmable within the range from 500 

 to 15 k

 (the 

sum of preset values may not exceed 15 k

). 

The value of EOL resistors for the zones on mainboard can be programmed: 

  using the keypad, in the service mode, by means of EOL

 

R1

 RESISTOR

, EOL

 

R2

 RESISTOR

 

and EOL

 

R3

 RESISTOR

 functions (

S

TRUCTURE

 

H

ARDWARE 

EOL

 

R1

 RESISTOR

 / 

EOL

 

R2

 RESISTOR

 / 

EOL

 

R3

 RESISTOR

); 

  using the D

LOAD

X program, in the "Structure" window, "Hardware" tab, after clicking on the 

control panel mainboard. 

The value of EOL resistors programmed for the mainboard zones applies also to the 
zones in LCD keypads: 

 

INT-KLCD and INT-KLCDR with electronics version 3.2 and firmware version 2.11 
(or later), 

Summary of Contents for INTEGRA 128 Plus

Page 1: ...SATEL sp z o o ul Schuberta 79 80 172 Gda sk POLAND tel 48 58 320 94 00 info satel pl www satel eu integra_plus_p_en 08 13 Firmware Version 1 12 Alarm Control Panels PROGRAMMING...

Page 2: ...y upgrade the quality of its products which may result in alterations of their technical specifications and firmware The current information on the introduced modifications is available on our website...

Page 3: ...will be enabled for 9 24H TAMPER type zones New options TAMPER IF NO COMMUNICATION WITH ABAX DEVICE 2H DO NOT REPORT TIME SERVER TROUBLE Timers An exception may apply to a specific year or be valid ev...

Page 4: ...GPRS programming 30 3 System structure 32 3 1 Objects 32 3 2 Partitions 32 3 2 1 Creating partitions 32 3 2 2 Programming partitions 33 3 2 3 Partition parameters 33 3 3 Zones 36 3 3 1 Assigning zones...

Page 5: ...codes 72 9 1 7 Test transmissions 73 9 2 Starting the reporting 73 9 2 1 Telephone reporting 73 9 2 2 Reporting via Ethernet network 73 9 2 3 GPRS reporting 74 10 Messaging 75 10 1 Voice PAGER messag...

Page 6: ...mmed by means of the DLOADX program the installer has been granted a temporary access to the control panel using the SERVICE ACCESS function the control panel can be programmed by any method The stand...

Page 7: ...e MASTERS function by entering the service code confirmed by pressing the key within about 20 seconds after ending the service mode started from pins 2 1 3 Hiding the service mode The installer can hi...

Page 8: ...64 Options 2 cds to arm 2 cds to d arm Codes on 2 arm 1st code 30s Timer priority Fin exit time Infin ex time Def block time Al can disarm Exit delay Auto arm delay Al verify time Bell on 2nd Guard ar...

Page 9: ...d Expanders id Keypads addr EOL R1 resistor EOL R2 resistor EOL R2 resistor Options Tel options Mon TELEPHONE Mon GPRS Mon ETHM 1 Messaging SMS messaging Modem answer Ext mod answ Voice answer Remote...

Page 10: ...warn trb Blk aft w code Troubl memory Hide alarms Events limit View clear al L no ABAX tamp Do not arm If verif al If tamper If monit trbl If batt trbl If outs trbl If other trbl Times Global entry d...

Page 11: ...ss no exit Bell delay Alarm if armed Clear alarm Restore disarm Alarm Arm 2 3 delay Auto reset 3 Auto reset 1 Auto rst clr Pre alarm Attend verif No restore ev Abort delay Part tmp block No viol monit...

Page 12: ...keypads Master users Arm mode sel Dialing mode triggering Partitions Burg tst part triggering Fire tst part triggering Output Temperature 1 Temperature 2 Timers Bypass timers Clear in parts Troubles...

Page 13: ...1 SIA evr bl s1A TELIM 0ton s1A SIA evr bl s1B TELIM 0ton s1B Need ack id s2 Id 6 chars s2 Source name s2 Partit name s2 SIA evr bl s2A TELIM 0ton s2A SIA evr bl s2B TELIM 0ton s2B Station 1 Tel 1 num...

Page 14: ...t assign Id assignment Partitions select partition Zones select zone LCD keypads select keypad Expanders select expander TELIM codes Event codes Identifier n n identifier number Zones select zone Part...

Page 15: ...sizer Pager message Telephones Fire alarms Synthesizer Pager message Telephones Medical alarms Synthesizer Pager message Telephones Duress alarms Synthesizer Pager message Telephones Tampers Synthesiz...

Page 16: ...rs all select user from the list of all users Users t code select user from the list of users with telephone code Note Text Valid From For Who can erase System status Partitions Zones Troubles Supply...

Page 17: ...e s Exit time sig Alarm signal New trbl sign Key sounds Trbl in p arm Zone violation Auto arm delay Unkn card sig Ev 3 unk cards Al 3 unk cards Dspl mode chg Show code ent Show disarming Show arm Cont...

Page 18: ...ask Gateway DHCP DNS DNS Port WWW Port DloadX Port others Port integr Key DloadX Key others Connect DloadX Connect GuardX Connect Intern Connect GSM PING test Integrate Coded integr Tamper in part Fai...

Page 19: ...door1 Dependent door2 Doors on fire Master users Users Code card only INT SCR Code card Code or card Follow output n n number of output Alarms Fire alarm Medical alarm Panic alarm Silent panic 3 wron...

Page 20: ...dical alarm Panic alarm Silent panic 3 wrong codes Options BI outs ctrl MONO outs ctr Part blocking Guard control Changing code Signaling Code entered Chime zones Confirmation Backlight Auto backlight...

Page 21: ...tamper does not apply to CA 64 DR Hardw signal 3 wrong codes BI outs ctrl MONO outs ctr Part blocking Guard control Code not dis Code in arm C long not dis Signalling Alarm latch Alarm time Entry tim...

Page 22: ...o autorst 3t Tamper in part EOL R1 resistor EOL R2 resistor CA 64 EPS CA 64 ADR CA 64 OPS CA 64 PP No autorst 3t Tamper in part AC loss delay CA 64 EPSi v 2 00 2 01 No autorst 3t Tamper in part EOL Rp...

Page 23: ...ge the currently displayed symbol to another one To scroll the list of items use the down or up key For some functions pressing the or key will switch the keypad into the graphic programming mode The...

Page 24: ...o the left The key deletes the character on the left side of the cursor Characters available after next keystroke key mode ABC key mode abc 1 1 1 1 2 2 B C 2 2 a b c 3 3 D E F 3 3 d 4 4 4 4 5 5 5 5 6...

Page 25: ...after next keystroke 1 1 2 a b c 2 3 d e f 3 4 g h i 4 5 j k l 5 6 m n o 6 7 p q r s 7 8 t u v 8 9 w x y z 9 0 _ 0 Table 3 Characters available when entering names The lower case letters are available...

Page 26: ...way of communication with the control panel Buttons button opens the Structure window button opens the Options window button opens the Zones window button opens the Outputs window button opens the Tim...

Page 27: ...e in the SM SETTINGS submenu using the DLOADX program in the Identifiers and tel no window the command for opening this window is available in the COMMUNICATION menu you can also use the Ctrl R key co...

Page 28: ...The local programming function must be disabled if the control panel is to communicate through the RS 232 port with an external analog modem GSM module or ETHM 1 module e g during remote programming...

Page 29: ...not apply to the external GSM or ISDN modem enable the DOUBLE CALL option if the control panel is to answer the connection only after the second call this does not apply to the external GSM or ISDN mo...

Page 30: ...programmed in the GSM module initializing communication with the DLOADX program through modem the control panel will call via the GSM module the programmed computer telephone number xxxxxx yyyy or xx...

Page 31: ...ways 1 Initiating connection from the DLOADX program This method enables establishing a connection with the control panel from any location 2 Initiating connection by the control panel The control pan...

Page 32: ...able connection establishing method is selected in the Identifiers and tel no window Connection field 1 Click on the button in the DLOADX program 2 A drop down menu will be displayed Select TCP IP Dlo...

Page 33: ...sage initiating the connection Initiating a connection 1 Click on the button in the DLOADX program 2 A drop down menu will be displayed Select TCP IP DloadX GSM GPRS 3 A window will open Enter the fol...

Page 34: ...pad will automatically display the functions to allow you to assign partitions to objects and to name the objects using the DLOADX program in the Structure window System tab after clicking on the syst...

Page 35: ...LOADX program in the Structure window System tab after clicking on the partition name 3 2 3 Partition parameters Shown in square brackets is the parameter name as presented in the LCD keypad The user...

Page 36: ...e time intervals set by the indicated timers Controlled by timer 1 32 Tim 1 32 ctrl Controlled by timer 33 64 Tim 33 64 ctrl the partition which is armed in time periods determined by selected timers...

Page 37: ...d from different keypads Valid within 30 sec 1st code 30s if this option is enabled and two codes are required for arming disarming the second user has to enter the code within 30 seconds of entering...

Page 38: ...l zones which physically do not exist but have been programmed as FOLLOW OUTPUT or are controlled by means of a keyfob 3 3 1 Assigning zones to a partition The zones can be assigned to a partition usi...

Page 39: ...ng In case of the EOL and 2EOL configurations the R3 resistor value is irrelevant In case of the EOL configuration the resistor value is a sum of the values programmed for the R1 and R2 resistors 3 3...

Page 40: ...led by the zone the zone always controls the partition it belongs to If value 0 is programmed the zone will only control the partition to which it belongs Exit delay refers to the 89 FINISHING EXIT DE...

Page 41: ...zone You can program values from the 3 ms to 96 ms range every 3 ms Pulses count the number of pulses after which the zone will be violated You can program values from 0 to 7 If the value 0 is program...

Page 42: ...n is equivalent to the partition exit 7 DAY NIGHT if disarmed the zone will signal violation acoustically in keypads and on the 9 DAY ALARM 12 SILENT ALARM and 116 INTERNAL SIREN outputs When armed th...

Page 43: ...NO REPORTING and STORE EVENT ONLY IF ARMED enable the zone to be used for other applications e g supervising the keybox 48 24H AUXILIARY PROTECTION LOOP 49 24H AUXILIARY GAS DETECTOR 50 24H AUXILIARY...

Page 44: ...ure 86 ENTRY EXIT FINAL similarly as the 0 ENTRY EXIT but the zone restore during exit delay countdown will terminate the exit delay countdown and arm the system 87 EXIT FINAL similarly as the 6 EXIT...

Page 45: ...the alarm is not cleared or the partition is not armed disarmed violations of the zone will not trigger any alarm Auto reset 1 with this option enabled the zone can trigger only 1 alarm As long as th...

Page 46: ...he 47 NO ALARM ACTION zone type the information to be written depends additionally on the NO REPORTING option No reporting option for the 47 NO ALARM ACTION zone type with the STORE TO EVENT LOG optio...

Page 47: ...ch determine the operating mode of the counter zones zone types 16 31 The counter parameters can be programmed using the keypad in the service mode by means of the COUNTERS function ZONES COUNTERS usi...

Page 48: ...til exiting the TEST function When the TEST function is re started the output must be selected again If wireless sirens are used in the system and any output is selected for signaling after selecting...

Page 49: ...t for the status indicating outputs 4 2 Output functions 0 NOT USED 1 BURGLARY signals all burglary and panic alarms from zones keypad expander tamper keypad Panic etc 2 FIRE BURGLARY signals the burg...

Page 50: ...e 8 EXTERIOR type zones when they are armed provided the SURVEILLANCE TIME has been programmed for the zone violation of the counting zones 16 31 type zones when armed 10 DURESS ALARM action carried o...

Page 51: ...PORTING ACKNOWLEDGEMENT indicates the acknowledgement of reporting 38 SERVICE MODE STATUS indicates that the service mode is entered 39 TEST VIBRATION DETECTORS intended for testing the vibration dete...

Page 52: ...of AC power supply to the modules with power supply unit when the trouble lasts long enough to be saved to the event log the delay is programmed individually in each module 83 OUTPUTS OFF active when...

Page 53: ...the roll shutters It becomes active after violation of selected zones or arming of selected partitions upon starting the arming procedure It can also be triggered from the keypad by means of the user...

Page 54: ...tage supply 12V voltage cut off inactive status 12V voltage cut off 12V voltage supply low current output option enabled normal polarity option disabled reversed polarity active status shorted to grou...

Page 55: ...m mode whose activation will activate the output Telephone usage type indicate which cases of using the telephone communication by the alarm control panel will activate the output 4 5 Clearing alarm i...

Page 56: ...e forcing output is active The user can edit the parameters of control timers using the TIMERS user function available in the CHANGE OPTIONS submenu 4 8 Output groups Fig 7 Window Output groups in the...

Page 57: ...and 64 as the controlling ones The output 1 will be turned on if the output 63 or 64 is active 3 Program the output 62 which does not exist physically as 26 TIMER type Program the timer which is to co...

Page 58: ...nt description in the event log the SATEL GSM module must be connected to the control panel Answering modem Modem answer with this option enabled external initiation of the communication between modem...

Page 59: ...reset number of rings e g answering machine fax etc Pulse 1 1 5 off 1 2 this option applies to dialing the telephone numbers by using the pulse mode Before you enable it make yourself familiar with th...

Page 60: ...terference may cause problems with communication No module restart reports No rest mon when the option is enabled and the Contact ID or SIA format is used for reporting no event codes referring to mod...

Page 61: ...F BATTERY TROUBLE REQUIRED SYSTEM RESET AFTER VERIFIED ALARM DO NOT ARM IF TROUBLE DO NOT ARM IF OUTPUTS TROUBLE DO NOT ARM IF REPORTING TROUBLE the TAMPER ALARM ALWAYS LOUD option is disabled for all...

Page 62: ...is no communication with a wireless device of the ABAX system for 2 hours 5 4 Arming options Warn while arming if trouble Arm warn trb if this option is enabled the user will be informed of the existi...

Page 63: ...sending information about short time voltage dips e g during a phone call or decays 5 6 Service options and parameters In the keypad the options are available in SM SETTINGS submenu Disable service m...

Page 64: ...user enter the address of time server supporting the NTP protocol Time synchronization is possible when the ETHM 1 module is connected Do not report time server trouble No t serv trbl with this optio...

Page 65: ...artitions Fire alarms the partitions the fire alarm from which will be indicated on the keypad by LED text message or a sound CHIME signal Chime zones list of the zones whose violation will generate a...

Page 66: ...m messages you can define whether the keypad is to display text messages about alarms in partitions Part al msg from zones Zone al msg Code card in case of the INT KLCDR keypads you can define the met...

Page 67: ...ons are armed Signal new trouble New trbl sign with this option enabled the keypad can audibly signal the occurrence of a new trouble if the TROUBLE MEMORY UNTIL REVIEW system option is enabled Show c...

Page 68: ...ithout the need to enter the user code Sound volume the function enables the volume level of sound signal in the keypad to be set Available in the INT KLCD INT KLCDR INT KSG and INT TSG type keypads K...

Page 69: ...highest sensitivity 10 the lowest sensitivity Card close parameter available for the INT KLCDR keypad Allows to select a function to be executed upon presenting the card Card holddown parameter avail...

Page 70: ...f the timers indicated as the controlling ones for the 120 THERMOSTAT type output can be edited by the user even if the USER EDITS option is disabled see section 120 THERMOSTAT OUTPUT PARAMETERS p 53...

Page 71: ...od of time After the time expires the control panel will make further attempts to send the event The reporting parameters can be programmed using the keypad in the service mode by means of the functio...

Page 72: ...he control panel will accept a long kiss off acknowledgment signal for receiving events in case of Ademco Express and Contact ID formats Enable this option in the event of telephone reporting if the m...

Page 73: ...l resume the attempt of establishing telephone connection with the monitoring station after this time expires or a next new event occurs Up to 30 minutes can be programmed Programming the value 0 mean...

Page 74: ...ypes will be reported to the given station It is not possible to assign events for the CONTACT ID FULL and SIA FULL formats 9 1 4 SIA IP If events are to be sent in the SIA IP format you must program...

Page 75: ...the number should check the telephone line for dialing signal NO DIAL TONE TEST option 3 Determine whether the event codes will be sent to both monitoring stations or to one of them only STATION 1 OR...

Page 76: ...module is only connected to the control panel dialer terminals TIP and RING the GPRS reporting settings will be ignored The EXTERNAL MODEM and MODEM ISDN GSM ETHM options must be enabled in the contro...

Page 77: ...ntrol panel the messaging will be interrupted The control panel will resume the messaging function after the event codes are reported to the monitoring station You can program the messaging using the...

Page 78: ...DE option has been enabled a user can be assigned to the telephone Thus if the INT VG module is connected to the control panel the user will be automatically granted access to the voice menu after ack...

Page 79: ...l is to play back the voice message after going off hook or 15 seconds after the dialing is completed global option NO ANSWER TONE TEST determine whether the voice message is to be played back once or...

Page 80: ...ers and options See also section TELEPHONE OPTIONS p 56 Shown in square brackets are the names used in keypads Answer if all chosen partitions are armed On armed part you can indicate the partitions w...

Page 81: ...FLASHX program 3 Click on the button to select the file with control panel new firmware 4 Click on the button to indicate the port to be used for communication with the control panel and start the fir...

Page 82: ...tput status and zone 256 has been added p 55 Description of REPORTING ETHM 1 option has been modified p 56 Description of RETURN TO MENU FROM MENU TEST has been modified p 58 Description of GRADE 3 op...

Reviews: