FIBER OPTIC INTERFACE 

INT-FI

 

 

int-fi_en 04/12 

 
The INT-FI interface allows for conversion and transmission of data by means of optical 
fibers. It is dedicated to interacting with the communication buses of INTEGRA alarm control 
panels or the RS-485 bus of ACCO access control system. The interface enables the 
maximum distance between the devices to be increased up to 4 km. 
This manual refers to the INT-FI interface with firmware version 1.02. 

Note: Interfaces with firmware version 1.02 are not compatible with those with earlier 

versions of firmware. Keep this in mind and, if necessary, update the firmware in 
interfaces with older firmware versions. 

1.  Features 

  Conversion of signals sent through the keypad / expander buses of INTEGRA alarm 

control panel and the RS-485 bus of ACCO access control system. 

  4 connectors for two fiber pairs.  

  Terminals for connecting electric signals from three communication buses of INTEGRA 

control panels (one keypad bus and two expander buses) or one RS-485 bus of ACCO 
access control system. 

  Operation in different configurations, depending on jumper settings. 

  Test mode to enable checking the correctness of data transmission. 

  LEDs indicating the selected configuration. 

  Up to 2 km transmission distance between two fiber optic interface units. 

  A possibility to extend the fiber optic distance up to 4 km in case of daisy chain topology 

(see Fig. 6). 

  Support for popular multimode fibers. 

 Updateable firmware. 

  Immunity of data transmission through optical fibers to electromagnetic interference. 

  Galvanic isolation of devices ensured. 

Summary of Contents for INT-FI

Page 1: ...gnals sent through the keypad expander buses of INTEGRA alarm control panel and the RS 485 bus of ACCO access control system 4 connectors for two fiber pairs Terminals for connecting electric signals...

Page 2: ...e SATEL manufactured cable DB9FC RJ KPL set 2 interface configuration pins By default all jumpers are placed across the pins M S R B 4 M S R B 3 M S R B 2 M S R B 1 Fig 2 Interface configuration metho...

Page 3: ...ngth of optical fibers connected to B connectors 7 LED indicating power supply presence and program operation 8 terminals COM common ground DTM keypad bus data CKM keypad bus clock DT1 first expander...

Page 4: ...EGRA control panel The unit on the control panel side is configured as Master M S jumper removed and the unit on the keypad expander side is configured as Slave M S jumper set The unit working on the...

Page 5: ...RS 485 bus of ACCO access control system The jumpers in both INT FI units are removed The unit working on ACCO KP PS side can be powered from the module main board The other unit can be supplied loca...

Page 6: ...ecommended if there is a need for running optical fibers of different length or in two different directions from the control panel Both pairs of optical fibers transmit signals to from the control pan...

Page 7: ...SATEL INT FI 7 Fig 6 An example of daisy chain topology the second INT FI unit works as a repeater...

Page 8: ...both interfaces see section Description of Electronics Board 4 Switch on power supply 5 Check the data transmission status by the LED indicators in both devices Note If the length of fiber cable exce...

Reviews: