Alarm Control Panel

CA-4v1

 

ca4v1_en 08/08

 

MANUAL 

GDA

Ń

SK

 

POLAND 

Summary of Contents for CA-4v1

Page 1: ...Alarm Control Panel CA 4v1 ca4v1_en 08 08 MANUAL GDA SK POLAND...

Page 2: ...cting the supply voltage For the replacement use only the fuses which have identical parameters as the original ones It is recommended that the manufacturer s required housings and power supply units...

Page 3: ...tem with bypassing the programmed zones stay arming one time code for single arming and disarming the system additional servicing code for accessing basic programming functions of the panel extended c...

Page 4: ...of the site and select a circuit which is permanently alive to power the control panel The circuit is to be protected with an appropriate fuse CAUTION The control panel is power supplied from the 230V...

Page 5: ...by indicating the fuse which protects the control panel supply circuit The panel on board DC power supply default setting is 13 6 13 8V and should not be changed Connection of keypad The CA 4v1 contro...

Page 6: ...pering circuit which should be used to protect them The OUT1 and OUT2 outputs control the ground terminal The 12V voltage is led through F2 and F3 fuses to OUT1 and OUT2 terminals The OUT1 and OUT2 te...

Page 7: ...maining situations the sound signal is repeated every second 1 short the entry delay time countdown 2 short the panel detected a trouble TROUBLE LED is on sound signal can be temporary switched off by...

Page 8: ...anceling the alarm the armed mode is deactivated PANIC alarm Press and hold the key for about 3 seconds The function can be blocked see ADDITIONAL FUNCTIONS Access code programming functions 1 2 3 4 T...

Page 9: ...incorrect access codes the TROUBLE LED will indicate PANIC type alarm Pressing any of the keys except will classify the previous alarm The panel logs the last three instances of alarm condition Pressi...

Page 10: ...e additionally bypassed should be entered After programming the panel the key should be pressed Programming Programming the panel enables its users to adjust it to specific requirements of an alarm sy...

Page 11: ...vating sequence 5 Example the exit delay time is to be set to 30 seconds 3 0 FUNCTION 6 programming the entry delay time from 0 to 99 seconds Activating sequence 6 Example the entry delay time is to b...

Page 12: ...COM terminal when the panel is armed Value 999 means that OUT2 will set the voltage to 12V when the panel is armed The bias resistor for example 1k that limits the input current from terminal OUT2 mus...

Page 13: ...r supply outputs 400mA delayed fuse protection outputs OUT1 and OUT2 1A delayed fuse protection battery protection 3 15A delayed fuse protection number of zones 4 zone type end of line resistor EOL re...

Page 14: ...us alarm exit the function ARMED 3 wrong access codes TROUBLE PANIC type alarm F1 AUX F2 OUT1 F3 OUT2 F4 battery 7 Identifying trouble type LEDs indicate the type of trouble available only when TROUBL...

Page 15: ...SATEL sp z o o ul Schuberta 79 80 172 Gda sk POLAND tel 48 58 320 94 00 info satel pl www satel pl...