Additionally, the ACX-201 expander module sends information about: 

  status of AUX1 and AUX2 power supply outputs – information on overload is sent when 

the AUX1 or AUX2 output load exceeds 0.5 A. 

  battery status – information on low battery is sent when the battery voltage drops below 

11 V for more than 12 minutes (3 battery tests). The expander will kept sending this 
information to the controller until the battery voltage rises and remains above 11 V for 
longer than 12 minutes (3 battery tests). 

  AC power status – information on the loss of power supply is sent when the AC power loss 

lasts for more than 30 seconds. The AC power restore is reported with the same delay. 

9.4  230 V AC wireless controllers 

Activation of the output to which the controller is assigned will result in energizing the 
230 V AC electrical circuit (if reverse polarity of the output has been programmed, the circuit 
will be deenergized). 
Depending on the operating mode, information on the button status (mode 0) or on the 
electric circuit status (mode 1 and mode 2) is sent to the zone to which the controller is 
assigned. Information on the button status is sent in real time. Information on the electric 
circuit status is sent during the response time. Pressing the button / closing the electric circuit 
means violation of the zone to which the controller is assigned. 

10.  APT-100 keyfobs 

The maximum number of supported keyfobs depends on the maximum number of the control 
panel users. 

The data related to keyfobs are stored in the controller. After the controller containing 
keyfob data is connected to the control panel, keyfobs will be automatically assigned 
to the existing users. 

10.1  Keyfobs in the INTEGRA / INTEGRA Plus system 

The user can have one APT-100 keyfob. If more than one ABAX wireless system controllers 
are connected to the INTEGRA / INTEGRA Plus control panels, the keyfob will be supported 
by all of them. The keyfob data are automatically saved to all controllers. 
When connecting the controller to the INTEGRA 128-WRL control panel or to the control 
panel to which the ABAX system controller is already connected, you should make uniform 
the data relating to APT-100 keyfobs. In the keypad service mode, the C

OPY 

ABAX

 KFOBS

 

function is available (

S

TRUCTURE 

H

ARDWARE 

E

XPANDERS 

C

OPY 

ABAX

 KFOBS

), which 

enables copying of the keyfob data. In the D

LOAD

X program, to write the APT-100 keyfobs 

data to a new controller, open the "Keyfobs ABAX" window and do the following: 

  INTEGRA 128-WRL – click on the "Write to all" button (the button is available, when the 

ABAX system controller is connected to the control panel). 

 other INTEGRA / INTEGRA Plus control panels – click on the "Read" button and 

immediately after reading the data, click on the "Write" button (after the data are read, you 
must not make any changes). 

The functions are executed by means of controlling the status of system zones. Using the 
keyfob, you can control up to 6 zones in the alarm system. These zones should not exist 
physically and the wiring type programmed in them must be different from N

O DETECTOR 

and 

F

OLLOW OUTPUT

. You can program any function for these zones. Pressing the keyfob button 

Summary of Contents for ACU-250

Page 1: ...ABAX WIRELESS SYSTEM CONTROLLER ACU 250 Firmware version 4 03 acu 250_en 02 14 SATEL sp z o o ul Schuberta 79 80 172 Gda sk POLAND tel 48 58 320 94 00 info satel pl www satel eu...

Page 2: ...r the warranty The SATEL s goal is to continually upgrade the quality of its products which may result in alterations of their technical specifications and firmware The current information on the intr...

Page 3: ...11 8 2 Programming in the INTEGRA INTEGRA Plus system 12 8 2 1 DLOADX program 12 8 2 2 LCD keypad 14 8 3 Programming in the VERSA system 14 8 3 1 DLOADX program 14 8 3 2 LCD keypad 14 9 Specific chara...

Page 4: ...ices the number of supported devices depends on the control panel Support for up to 248 APT 100 keyfobs the number of supported keyfobs depends on the control panel Two way encrypted radio communicati...

Page 5: ...munication bus and power cables 3 Pass the wires through the opening It is recommended to use a straight through unshielded cable When using the twisted pair type of cable the CLK clock and DAT data s...

Page 6: ...Fig 3 VERSA in the Versa Structure window Hardware tab after clicking on the controller name 5 1 Parameters options and functions Name individual name of device up to 16 characters Tamper signaled in...

Page 7: ...es supported by it Test mode in the ABAX system the test mode can be started in which LED indicators are enabled in the wireless devices the LEDs are disabled during normal operation information provi...

Page 8: ...has identified the controller you can begin installation of the ABAX system wireless devices Before installing a wireless device check the level of radio signal received by the device from controller...

Page 9: ...tem for wireless devices although 8 positions are actually taken up on the list of wireless devices see Table 2 In such a case it is recommended that the last devices be removed from the list and then...

Page 10: ...ll allow you to maintain the continuity of use of not the zones alone but the outputs as well Table 2 shows a situation in which the siren first output occupies position 8 and the second output positi...

Page 11: ...nsert the ASW 100 E ASW 100 F wireless controller into 230 V AC socket violate open the tamper contact in case of the other devices If an invalid serial number is entered it will be indicated by a sui...

Page 12: ...orm you that the expander identification function has been started 8 After identification of the devices the keypad will display a suggested name for the zone to which the device is assigned The name...

Page 13: ...ilable for the most of wireless detectors If enabled the te T U parameter available for a wireless device if the ARU 100 repeater is registered in the controller the controller is connected to the INT...

Page 14: ...ll cause alarm second zone the number of pulses which if registered by vibration detector will cause alarm the pulses need not meet the sensitivity criterion second zone Working parameters of the vibr...

Page 15: ...t ente D 102 r the digit 0 bottom reed switch or 1 side reed switch to determine which of the two reed switches is to be active For the roller shutter 1st digit number of pulse 2nd digit pulse validit...

Page 16: ...a selected repeater the name of the zone to which the repeater lues which can be programmed for individual parameters of wireless devices are presented in the ans of the DLOADX program he VERSA syste...

Page 17: ...he EN50131 3 standard all ABAX system Hold Up devices must be always in active mode Batteries ensure approx 3 years operation of the detectors assuming that the detectors are in passive state for part...

Page 18: ...ng connected with starting ending the test mode or the service mode is sent during the response time 9 3 Wireless expanders of hardwired zones and outputs The wireless expander of hardwired zones and...

Page 19: ...he data related to keyfobs are stored in the controller After the controller containing keyfob data is connected to the control panel keyfobs will be automatically assigned to the existing users 10 1...

Page 20: ...am Pressing a button combination of buttons in the keyfob can generate a keyfob use event For information on adding removing keyfobs by means of the keypad please refer to the control panel user manua...

Page 21: ...respond to the number of field with output selected for confirmation on the window right side i e it can be from the 1 to 8 range The names of outputs in fields designated with these digits will be sh...

Page 22: ...me way as for the INTEGRA and INTEGRA Plus control panels Functions can be assigned to the buttons combination of buttons in the following way 1 Click on the field corresponding to the selected button...

Page 23: ...ording to EN50130 5 II Operating temperature range 10 C 55 C Maximum humidity 93 3 Enclosure dimensions 24 x 110 x 27 mm Weight 35 g 12 Manual update history DATE FIRMWARE CHANGES MADE 2013 04 4 02 In...

Reviews: