![Satechi pm130e Reference Manual Download Page 56](http://html1.mh-extra.com/html/satechi/pm130e/pm130e_reference-manual_1200398056.webp)
56
Address Point
ID
Description
Options/Range Units
Type
R/W
Notes
identification (F30, F32, F34, F36),
Bit 8=1 – freeze with reset,
Bit 9=1 – local freeze,
Bit 10=1 – cyclic data transmission,
Bit 11=1 – general interrogation,
Bits 12:15 – interrogation group =
0-15 (0=no group assigned)
+1
Start information object address
1-65535
UINT16
R/W
+2
Number of elements in the range
1-128
UINT16
R/W
49524-49526
Object address range #1
49527-49529
Object address range #2
…
…
49617-46619
Object address range #32
IEC 60870-5 Assignable Point Map and Events Setup
49716-49971
UINT16
R/W
+0
Point ID
See Section 3.4
UINT16
R/W
+1
Information object type and flags
Bits 0:7 – static object type
identification (F3, F5, F7),
Bits 8:9 – relation (0=delta, 1=
more than, 2 = less than)
Bit 10=1 – class 1 assignment
UINT16
R/W
+2,3 Deadband/threshold
See
Section 3.4 for the point range
and resolution
INT32
R/W
49716-49719
Mapped static/event point #1
49720-49723
Mapped static/event point #2
…
…
49968-49971
Mapped static/event point #64
DNP Options Setup
51158-51183
+0
Default Binary Input Static object variation
F24 (default 0)
UINT16
R/W
+1 Reserved
UINT16
R/W
+2
Default Binary Counter object variation
F24 (default 3)
UINT16
R/W
+3
Default Frozen Binary Counter object variation
F3 (default 4)
UINT16
R/W
+4-5 Reserved
UINT16
R/W
+6
Default Analog Input object variation
F24 (default 3)
UINT16
R/W
+7-10 Reserved
UINT16
R/W
+11
16-bit BC scaling
0=
×
1 (default), 1=
×
10, 2=
×
100,
3=
×
1000
UINT16
R/W
+12
16-bit AI scaling
0=scaling is OFF, 1=scaling is ON
UINT16
R/W
+13-5 Reserved
UINT16
R/W
+16
Select/Operate Timeout
2 to 30 seconds (default 10 sec)
UINT16
R/W
+17
Multi Fragment Interval
5 to 500 ms (default 10 ms)
UINT16
R/W
+18-21
Reserved
Read as 65535
UINT16
R/W
Provided