55
Address Point
ID
Description
Options/Range Units
Type
R/W
Notes
47072-47075
V1 transformer correction
47076-47079
V2 transformer correction
47080-47083
V3 transformer correction
47084-47087
Reserved
47088-47091
I1 transformer correction
47092-47095
I2 transformer correction
47096-47099
I3 transformer correction
IEC 60870-5 Options Setup
49460-49494
+0
Maximum length of variable frame, octets
32-255
UINT16
R/W
+1
Link address length, octets
1-2
UINT16
R/W
+2
Cause of transmission length, octets
1-2
UINT16
R/W
+3
Length of common address of ASDU, octets
1-2
UINT16
R/W
+4
Length of information object address, octets
1-3
UINT16
R/W
+5
Select-before-operate timeout, s
0-30
UINT16
R/W
+6
Short pulse duration, ms
100-3000
ms
UINT16
R/W
+7
Long pulse duration, ms
100-3000
ms
UINT16
R/W
+8,9
Time synchronization period, s
1-86400, 0=not active
s
UINT32
R/W
+10
Local counter freeze period, min
1-60, 0=not active
min
UINT16
R/W
+11
Cyclic data transmission period, ms
100-30000, 0=not active
ms
UINT16
R/W
+12,13
Client IP address for cyclic data transmission
0-0xFFFFFE, 0=not active
UINT32
R/W
+14,15
Client IP address for spontaneous transmission
0-0xFFFFFE, 0=not active
UINT32
R/W
+16,17 Not
used
0
UINT32
R/W
+18 Not
used
0
UINT16
R/W
+19
Respond with class 1 data to class 2 requests
0=disabled, 1=enabled
UINT16
R/W
+20
Single point start mapped address
1-4095
UINT16
R/W
+21
Single point default static object type
F30
UINT16
R/W
+22
Single point default event object type
F31
UINT16
R/W
+23
Double point start mapped address
1-4095
UINT16
R/W
+24
Double point default static object type
F32
UINT16
R/W
+25
Double point default event object type
F33
UINT16
R/W
+26
Measured value start mapped address
1-4095
UINT16
R/W
+27
Measured value default static object type
F34
UINT16
R/W
+28
Measured value default event object type
F35
UINT16
R/W
+29
Integrated totals start mapped address
1-4095
UINT16
R/W
+30
Integrated totals default static object type
F36
UINT16
R/W
+31
Integrated totals default event object type
F37
UINT16
R/W
+32
Voltage units
0=V, 1=kV
UINT16
R/W
+33
Current units
0=A, 1=kA
UINT16
R/W
+34
Power units
0=kW, 1=MW
UINT16
R/W
IEC 60870-5 Class 2 Data and Counters Setup
49524-49619
+0
Information object type and flags
Bits 0:7 – static object type
Provided
by
Northeast
Power
Systems,
Inc.