24
Address Point
ID
Description
Low and High Scales
2
Units
2, 4
Type R/W
Notes
+8 0x1408
Total kvar import
0-Pmax
U3
UINT32
R
+9 0x1409
Total kvar export
0-Pmax
U3
UINT32
R
+10 0x140A
3-phase average L-N/L-L voltage
0-Vmax
U1
UINT32
R
1
+11 0x140B
3-phase average L-L voltage
0-Vmax
U1
UINT32
R
+12 0x140C
3-phase average current
0-Imax
U2
UINT32
R
7496-7500
1-Second Auxiliary Values
+0 0x1500 Not
used
UINT16 R
+1 0x1501
In (neutral) Current
0-Imax
U2
UINT16
R
+2 0x1502 Frequency
0-Fmax
0.01Hz UINT16 R
+3 0x1503 Voltage
unbalance
0-300
%
UINT16 R
+4 0x1504 Current
unbalance
0-300
%
UINT16 R
7536-7565
Present Volt, Ampere and Power Demands
+0 0x1600
V1/V12 Volt demand
0-Vmax
U1
UINT16
R
1
+1 0x1601
V2/V23 Volt demand
0-Vmax
U1
UINT16
R
1
+2 0x1602
V3/V31 Volt demand
0-Vmax
U1
UINT16
R
1
+3 0x1603
I1 Ampere demand
0-Imax
U2
UINT16
R
+4 0x1604
I2 Ampere demand
0-Imax
U2
UINT16
R
+5 0x1605
I3 Ampere demand
0-Imax
U2
UINT16
R
+6 0x1606
kW import block demand
0-Pmax
U3
UINT16
R
+7 0x1607
kvar import block demand
0-Pmax
U3
UINT16
R
+8 0x1608
kVA block demand
0-Pmax
U3
UINT16
R
+9 0x1609
kW import sliding window demand
0-Pmax
U3
UINT16
R
+10 0x160A
kvar import sliding window demand
0-Pmax
U3
UINT16
R
+11 0x160B
kVA sliding window demand
0-Pmax
U3
UINT16
R
+12 0x160C Not
used
UINT16 R
+13 0x160D Not
used
UINT16 R
+14 0x160E Not
used
UINT16 R
+15 0x160F
kW import accumulated demand
0-Pmax
U3
UINT16
R
+16 0x1610
kvar import accumulated demand
0-Pmax
U3
UINT16
R
+17 0x1611
kVA accumulated demand
0-Pmax
U3
UINT16
R
+18 0x1612
kW import predicted sliding window demand
0-Pmax
U3
UINT16
R
+19 0x1613
kvar import predicted sliding window demand
0-Pmax
U3
UINT16
R
+20 0x1614
kVA predicted sliding window demand
0-Pmax
U3
UINT16
R
+21 0x1615
PF (import) at Max. kVA sliding window demand
0-1.000
0.001
UINT16
R
+22 0x1616
kW export block demand
0-Pmax
U3
UINT16
R
+23 0x1617
kvar export block demand
0-Pmax
U3
UINT16
R
+24 0x1618
kW export sliding window demand
0-Pmax
U3
UINT16
R
+25 0x1619
kvar export sliding window demand
0-Pmax
U3
UINT16
R
+26 0x161A
kW export accumulated demand
0-Pmax
U3
UINT16
R
+27 0x161B
kvar export accumulated demand
0-Pmax
U3
UINT16
R
+28 0x161C
kW export predicted sliding window demand
0-Pmax
U3
UINT16
R
+29 0x161D
kvar export predicted sliding window demand
0-Pmax
U3
UINT16
R
+30 0x161E Not
used
UINT16 R