background image

 

 

2

 

ETC ONE PLUS Network Communicator

 

 

LIMITED WARRANTY 

The manufacturer offers the customer a 24-month functional warranty on the 
instrument  for  faulty  workmanship  or  parts  from  date  of  dispatch  from  the 
distributor. In all cases, this warranty is valid for 36 months from the date of 
production. This warranty is on a return to factory basis. 

The  manufacturer  does  not  accept  liability  for  any  damage  caused  by 
instrument  malfunction.  The  manufacturer  accepts  no  responsibility  for  the 
suitability of the instrument to the application for which it was purchased. 

Failure to install, set up or operate the instrument according to the instructions 
herein will void the warranty. 

Only  a  duly  authorized  representative  of  the  manufacturer  may  open  your 
instrument. The unit should only be opened in a fully anti-static environment. 
Failure  to  do  so  may  damage  the  electronic  components  and  will  void  the 
warranty. 

The  greatest  care  has  been  taken  to  manufacture  and  calibrate  your 
instrument.  However,  these  instructions  do  not  cover  all  possible 
contingencies  that  may  arise  during  installation,  operation  or  maintenance, 
and  all  details  and  variations  of  this  equipment  are  not  covered  by  these 
instructions.   

For additional information regarding installation, operation or maintenance of 
this  instrument,  contact  the  manufacturer  or  your  local  representative  or 
distributor. 

WARNING 

Read the instructions in this manual before performing installation, and take 
note of the following precautions: 

 

Ensure that all incoming AC power and other power sources are turned 
OFF before performing any work on the instrument. Failure to do so may 
result in serious or even fatal injury and/or equipment damage.  

 

Before connecting the instrument to the power source, check the labels 
on the back of the instrument to ensure that your instrument is equipped 
with the appropriate power supply voltage, input voltages and currents. 

 

Under no circumstances should the instrument be connected to a 
power source if it is damaged. 

 

To  prevent  potential  fire  or  shock  hazard,  do  not  expose  the 

instrument to rain or moisture. 

 

The secondary of an external current transformer must never be allowed 
to  be  open  circuit  when  the  primary  is  energized.  An  open  circuit  can 
cause  high  voltages,  possibly  resulting  in  equipment  damage,  fire  and 
even serious or fatal injury. Ensure that the current transformer wiring is 
secured using an external strain relief to reduce mechanical strain on the 
screw terminals, if necessary. 

 

Only qualified personnel familiar with the instrument and its associated 
electrical equipment may perform setup procedures. 

 

Do  not  open  the  instrument  under  any  circumstances  when  it  is 
connected to a power source. 

 

Do not use the instrument for primary protection functions where failure 
of the device can cause fire, injury or death. The instrument can only be 
used for secondary protection if needed.  

Read  this  manual  thoroughly  before  connecting  the  device  to  the  current 

carrying  circuits.  During  operation  of  the  device,  hazardous  voltages  are 
present on input terminals. Failure to observe precautions can result in serious 
or even fatal injury or damage to equipment. 

All trademarks are property of their respective owners.  
Copyright SATEC Ltd. 

 2008  

Summary of Contents for ETC One Plus

Page 1: ...ETC One Plus Network Communicator Installation and Operation Manual BG0596 Rev A1 ...

Page 2: ...ower and other power sources are turned OFF before performing any work on the instrument Failure to do so may result in serious or even fatal injury and or equipment damage Before connecting the instrument to the power source check the labels on the back of the instrument to ensure that your instrument is equipped with the appropriate power supply voltage input voltages and currents Under no circu...

Page 3: ...ration 14 Operational Mode 14 Program Service Mode 14 Using the ETC ONE PLUS 14 Slave Network Connection 14 Master Network Connections 14 ETC I Communication Setup 15 ETC I COM1 setup 15 ETC I COM2 Ethernet setup 16 ETC I COM2 GPRS setup 18 Setting Up eXpertPower Client 19 Using PAS Software 20 Configuration Database 20 Setting up Communications 20 Setting Up the ETC ONE PLUS 21 Authorization 22 C...

Page 4: ...fer data from to ETHERNET or Cellular module to from serial communication port COM1 COM1 shall operate as a Client Master and COM2 which is tied to Ethernet or Cellular network shall be configured with its IP address to route data server to predefined MODBUS Slave devices MODBUS address from 1 to 31 Features COM1 as RS 485 master ports for connecting slave devices to serial networks COM2 as Ethern...

Page 5: ...nical Installation ETC ONE PLUS Network Communicator 5 Chapter 2 Installation Mechanical Installation Refer to the figures provided in this section to properly perform the mechanical installation Figure 2 1 ETC ONE PLUS Dimensions ...

Page 6: ...work communicator on the wall 1 Position the device on the wall according to hole locations as shown in figure 2 2 2 Affix the device using washers and nuts Figure 2 2 Surface mointing DIN Rail Mounting The ETC One Plus can be mounted on a standard 35 mm DIN rail as shown in figure 2 3 Figure 2 3 DIN Rail mointing ...

Page 7: ...ng power sources are shut OFF Failure to observe this practice can result in serious or even fatal injury and damage to equipment 1 Turn off the ETC One Plus ETC I power supply 2 Remove the module connector cover from the ETC I to access the module connector as shown in figure 2 4 below Figure 2 1 ETC I module connector location Figure 2 2 ETC I module assembly ...

Page 8: ...ent Power Source Connection Before connecting your device to the power source check the label on the the device to ensure that it is equipped with the appropriate power supply AC power supply Connect the line wire to terminal L and the neutral wire to terminal N DC power supply Connect the positive wire to terminal L and the negative wire to terminal N Figure 2 5 Power Source Connection Communicat...

Page 9: ...way port is used for connecting the ETC ONE PLUS to the RS 422 RS 485 slave network with up to 32 devices For device COM port setup see Communication Setup in Chapter 3 The COM1 port can also be used as a slave port to communicate with PAS COM1 RS 485 Connection Figure 2 6 COM1 RS 485 2 Wire Connection ...

Page 10: ...cator COM2 ETHERNET Connection Plug the end of the Ethernet cable that came with your device into the wall Ethernet jack or into the Ethernet hub jack and the other end into the RJ45 jack at the front of the ETC ONE PLUS ETHERNET module Figure 2 7 Serial and Ethernet Connections ...

Page 11: ...Chapter 2 Installation Electrical Installation ETC ONE PLUS Network Communicator 11 COM2 CELLULAR connection Figure 2 8 Serial and Cellular 3G Connections ...

Page 12: ...connection Connecting a device with the factory set IP address to the Ethernet network can disrupt communications if the IP address exists on the network Change the IP address in your ETC ONE PLUS as instructed in Section 4 before connecting a device to the network See Internet Connections in Chapter 3 and configuring the Network in Chapter 5 for instructions on how to program your device for netw...

Page 13: ...reen device status LEDs that show the present device status and activity on communication ports The ETC ONE PLUS has four status indicator LEDs that show present device operation status and give diagnostics indication as described in table below LED Name Color Status Description RDY Green 2 sec Off After Power up or Reset the LED is Off Flashing 1 2 sec On 1 2 sec Off Device operational and is fun...

Page 14: ... ONE PLUS is connected to serial RS 485 slave networks via the COM1 gateway ports The COM1 is automatically set to master mode to operate as a gateway port in normal operation See Configuring Serial Ports in Chapter 5 for information on programming serial ports The communication protocol to be used for serial networking via the ETC ONE PLUS is defined by the Network TCP service port setting See Co...

Page 15: ... PAS through COM1 MODBUS RTU To exit the programming mode dis energize the device power and reenergize it back Make sure the yellow PROG Led is turned OFF ETC I COM1 setup The ETC I COM1 port shall be configured as follows using PAS 1 Select Communication Setup 2 Select Serial Ports Setup 3 COM1 setup Label Parameter Options Default Description Protocol Communicatio ns protocol MODBUS RTU MODBUS R...

Page 16: ...ETC I it must be set to Server Slave In normal use to be set to Client Master RX Tmout ETC I COM2 Ethernet setup The ETC I COM2 setup shall be configured as follows depending on attached communication module type The ETC I COM2 port shall be configured as follows using PAS 1 Select Communication Setup 2 Select Serial Ports Setup 3 COM2 setup 4 Select Ethernet interface in case of ETHERNET module E...

Page 17: ...our ETC ONE PLUS has both the Ethernet and modem network interfaces the eXpertPower client uses one of these for connections to the eXpertPowerTM server The default Ethernet network gateway address defines which one of the networks is used If the default gateway address is not defined i e it is set to 0 0 0 0 the ETC ONE PLUS uses the dial out modem connection via your local Internet provider If y...

Page 18: ...ETC I COM2 GPRS setup The ETC I COM2 setup shall be configured as follows depending on attached communication module type The ETC I COM2 port shall be configured as follows using PAS 1 Select Communication Setup 2 Select Serial Ports Setup 3 COM2 setup 4 Select GSM GPRS interface in case of 3G module ...

Page 19: ...ces Connections to the eXpertPowerTM server are handled on a periodic basis To set up communications with the eXpertPowerTM server the ETC I can be configures as follows using PAS 1 Select Communication Setup 2 Select Expertpower Client Setup Parameter Options Default Description XPW Server IP Address 207 232 60 18 The IP address of the eXpertPower server XPW Server Port 0 65535 5001 The TCP servi...

Page 20: ...e To create a new database for your ETC ONE PLUS 1 Select Configuration from the Tools menu and then click the Sites button on the right hand side 2 From the Look in box select the directory where the new database will be stored By default it is the Sites directory Type a site name for your device in the File name box click New and then click OK 3 On the Instrument Setup tab select ETC ONE PLUS in...

Page 21: ...her site database select it from the file panel and then click OK To re use setups from another site copy them to your present site database Click Open select the desired site database and then click OK The opened setup is copied to your site database You can also copy all setups from one site database into another site s database Select a device site from the list box on the toolbar from which yo...

Page 22: ...on the PAS toolbar select the device site from the list box on the toolbar and then select Upload Setups from the Meter Setup menu Authorization If communications with your ETC ONE PLUS is secured you are prompted for the password when you send new setup data to the device Enter the password and click OK If your authorization was successful you are not prompted for the password again until you clo...

Page 23: ...ecurity To change the password check the On line button on the PAS toolbar select Administration from the Monitor menu and then select Change Password To change the password 1 Type in a new 8 digit password 2 Repeat the password in the Confirm box 3 Check the Enable network protection box to enable password checking 4 Click Send Changing Time and Date Select the ETC ONE PLUS site from the list box...

Page 24: ...DST switch dates DST start month DST start week DST start weekday Month week weekday Week 1st 2nd 3rd 4th or Last last week of the month First Sunday in April The date when Daylight Savings Time begins The DST switch point is specified by the month week of the month and weekday By default DST starts at 2 00 AM on the first Sunday in April of each year DST end month DST end week DST end weekday Mon...

Page 25: ...C ONE PLUS Network Communicator 25 Configuring Device Routing Table The ETC I pass through gateway routing table is predefined in the firmware as follows MODBUS Slave devices to be polled shall have fixed address 1 31 the ETC I MODBUS Master address shall be 32 or higher 99 ...

Page 26: ... to the meter through PAS Firmware can be downloaded via the MODBUS RTU or MODBUS TCP protocol through any communication port To download a new firmware file to your device 1 Ensure that the communication port you are connected through to the meter operates in Modbus mode 2 If you are connected to the meter through a serial interface it is recommended to set the port baud rate to 115 200 bps See S...

Page 27: ...Wait until PAS completes upgrading your device It takes about 3 4 minutes at 115 200 bps to download the file to the meter 7 After upgrading firmware is completed the meter restarts so communications can be temporarily lost You may need to wait a short duration until PAS restores a connection with your device ...

Page 28: ...Hz IEC 60068 2 27 AS 60068 2 27 19 Shock Shock level 30 g Time duration 18 ms Shape Half sine Number of shocks 18 Construction Case enclosure Reinforced Polycarbonate Packaging case Carton and Stratocell Polyethylene Foam brackets Labels Polyester film UL94 V0 Power Supply AC DC Power Supply Rated input 40 300VAC 50 60Hz 40 300VDC Burden 5VA Frequency range operation 25 400 Hz Isolation Input to g...

Page 29: ...ar 3G Cellular Port Optional module 2G 3G GSM Network Protocols MODBUS TCP Port 502 Number of simultaneous connections 4 Antenna Connector type SMA RS 232 422 485 Port Optional module RS 232 or RS 422 485 optically isolated port Isolation 3000V AC 1 min Baud rate up to 115 2 kbps Protocols MODBUS RTU Slave Connector type removable 5 pins for RS 422 485 and DB9 for RS 232 Torque terminal screw 0 5 ...

Reviews: