Chapter 3 Operating the ETC ONE PLUS
ETC I Communication Setup
16
ETC ONE PLUS Network Communicator
Label
Parameter
Options
Default
Description
Send Delay
Transmission
delay
0-1000 ms
5 ms
The minimum time
after the last request
character is received to
start the transmission.
Chr.Tmout
Inter-character
timeout
0-1000 ms
4 ms
The maximum time the
line is allowed to idle
before closing a
connection in the
Modbus RTU protocol
Port Mode
Client/Server
Client/Master
Server/Slave
Server/slave To configure the ETC I,
it must be set to
Server/Slave
In normal use to be set
to Client/Master
RX Tmout
ETC I COM2 Ethernet setup
The ETC I COM2 setup shall be configured as follows depending on attached
communication module type The ETC I COM2 port shall be configured as
follows, using PAS
™
:
1.
Select Communication Setup
2.
Select Serial Ports Setup
3.
COM2 setup
4.
Select Ethernet interface in case of ETHERNET module
Ethernet Connections
To setup your Ethernet connections:
1.
Define the network IP parameters via the ETC ONE PLUS Network
Setup. If you use the ETC ONE PLUS eXpertPower client connections
via the Ethernet network, define a non-zero default gateway address, so
the client connections will be directed to the Ethernet.