background image

5

Control Panel

The control panel is shipped with a protective plastic
film. This film can be left on or removed. To clean, use a
damp cloth and mild detergent.

Outdoor Coil

The coil on the outdoor side of the unit should be
checked periodically and cleaned if clogged with dirt or
soot from the atmosphere. If extremely dirty, it may need
to be professionally steam cleaned.

Base Pan

In some installations, dirt or other foreign matter may be
blown into the unit from the outside and settle in the
base pan (the bottom of the unit). Check the base pan
periodically and clean it out, if necessary.

Tips for Energy Saving

Do not

• Block the air intake and outlet of the unit. If they are

obstructed, the unit will not work well, and may be
damaged.

• Let direct sunlight into the room. Use sunshades,

blinds or curtains. If the walls and ceiling of the room
are warmed by the sun, it will take longer to cool the
room.

Do

• Keep the air filter clean. (Refer to “Care and

Cleaning.”)
A clogged filter will impair the performance of the unit.

• To prevent conditioned air from escaping, keep win-

dows, doors and any other openings closed.

• Keep the ventilator closed for economy and maximum

cooling.

PROBLEM

POSSIBLE CAUSE

AIR CONDITIONER 
DOES NOT 
OPERATE

AIR CONDITIONER 
“DOES NOT COOL 
OR HEAT AS IT 
SHOULD”

“BURNING” ODOR 
AT START OF 
HEATING 
OPERATION

OPERATING 
SOUNDS

AIR IS NOT 
ALWAYS COOL 
DURING COOLING
OPERATION

AIR IS NOT 
ALWAYS HOT 
DURING HEATING
OPERATION

Troubleshooting

• The power cord is not plugged in or

circuit breaker is tripped.

• The unit is waiting for the compressor

overload protector to reset.

• Curtains, blinds or furniture blocking

the front of the air conditioner are
restricting the air flow.

• Thermostat control may not be set

high/low enough. Turn the control to a
lower or higher position. (NOTE: In
some installations, the thermostat
control cannot be turned all the way to
the highest end or lowest end. This is
normal. Do not attempt to force the
control beyond its stopping points.)

• A dirty air filter is blocking air flow.

The filter should be cleaned at least
once every 2 weeks. See the instruc-
tions in the cleaning section.

• The room may have been very hot or

very cold when the air conditioner
was first turned on. Allow time for it
to cool down or warm up.

• The ventilation control may be set to

the OPEN position, allowing outside
air to enter the room.

• Dust on the surface of the electrical

heater can cause a “burning” odor at
the beginning of the heating opera-
tion. This odor should quickly fade.

• Relay clicks may be heard when the

compressor or fan cycles on and off.
This is normal.

• The fan runs continuously when the

unit is operating unless the Fan Cycle
Switch under the control panel is set
to CYCLE. In this case, the fan cycles
on and off with the electrical heater
or compressor.

• The Fan Cycle Switch may be set to

Fan Cont (continuous). This causes
the fan to blow room air even when
the compressor is off. The continuous
air flow provides better overall tem-
perature control.

• The Fan Cycle Switch may be set to

Fan Cont (continuous). This causes
the fan to blow room air even when
the electrical heater is off. The contin-
uous air flow provides better overall
temperature control.

US STW PTAC  8/8/01 5:34 PM  Page 5

Summary of Contents for STW-2 Series

Page 1: ...l refers to a hazard or unsafe practice which can result in severe personal injury or death This symbol refers to a hazard or unsafe practice which can result in personal injury or product or prop erty damage Alert Symbols The following symbols used in this manual alert you to potential ly dangerous conditions to users service personnel or the appli ance Contents Page IMPORTANT Please Read Before ...

Page 2: ... liquid near the air conditioner it is very dangerous Do not turn the air conditioner on and off from the power mains switch Use the mode selector switch Do not stick anything into the air outlet of the unit This is dan gerous because the fan is rotat ing at high speed Do not let children play with the air conditioner Do not cool or heat the room too much if babies or invalids are present Air Inta...

Page 3: ...at hold the louvers in place Turn the louver section 180 end for end replace the screws and replace the front grille The textured face of the louver section must be facing toward the room side Front grille Louver screws The direction of the heated or cooled air may be adjusted by removing and turning the louvers around 37 OFF VERTICAL 20 OFF VERTICAL Other Features Ventilation Control The ventilat...

Page 4: ... off the air conditioner before cleaning Air Filters The air filters should be cleaned at least once every two weeks Clogged filters reduce cooling heating and air flow Keeping these filters clean will Decrease cost of operation Save energy Prevent clogged heat exchanger coils Reduce costly compressor problems To remove the air filters Pull up 2 air filters Front To clean the air filters Vacuum of...

Page 5: ...ircuit breaker is tripped The unit is waiting for the compressor overload protector to reset Curtains blinds or furniture blocking the front of the air conditioner are restricting the air flow Thermostat control may not be set high low enough Turn the control to a lower or higher position NOTE In some installations the thermostat control cannot be turned all the way to the highest end or lowest en...

Page 6: ...hange the internal wiring or any part of the system DO NOT turn the air conditioner on and off by plugging and unplugging Use the Operation switch SELEC TOR Follow National Electrical Code NEC and local codes ordinances and regulations All wiring including installation of receptacles must be in accordance with these codes The NEC requires permanent connection for installa tions over 250 volts Prot...

Page 7: ...the outdoor panel as a grip and push out 3 Install the rear grille from the room side according to the instructions packed with the grille Protective panel Slit Stiffener 3 INSTALLATION 1 Remove the front grille by pulling out at the bot tom to release it then lift it up to clear the rail along the chassis top 1 2 2 Slide the chassis into the wall case and secure with four screws through the chass...

Page 8: ...m the Electrical Junction Box 3 Split and strip the wires as shown above 4 Install the Bottom Plate using the provided field supplied conduit and power supply conductors to the unit with screw B 5 Connect Power Supply wires to the stripped inner wires with the wire nuts 6 Dress the wiring inside the compartment and attach the cover plate with screw A 7 Reinstall the Front Grille 4 2 For 265V Units...

Page 9: ...itch on page 4 Set the limiting screws to the desired set ting and replace the control panel and the control knobs If the settings do not allow sufficient room temperature control the limiting screws may have to be repositioned Stop link Tapped holes 10 Thermostat shaft Coldest Warmest Temperature limiting screws location at shipment When the limiting screws are relocated it is recom mended that t...

Page 10: ... operable When the switch is set to CLOSED the unit is made inoperative Detailed hook up instructions are in the interface kit Follow the recommended wire sizing in the table below Two wires must be used from each FDC switch to each individual unit Good wiring practices e g twisted pairs SEPARA TION FROM POWER CIRCUITS must be followed to minimize induced voltages which may harm the con trol syste...

Page 11: ...ou have problems or questions concerning your Air Conditioner you will need the following information Model and serial numbers are on the nameplate of the cabinet Model No Serial No Date of purchase Dealer s address Phone number ...

Page 12: ...SANYO FISHER COMPANY A DIVISION OF SANYO NORTH AMERICA CORPORATION 21605 plummer Street Chatsworth CA 91311 U S A In Canada SANYO Canada Inc 300 Applewood Crescent Concord Ontario L4K 5C7 Canada ...

Reviews: