6.2.2 - MODULE CC1 CONFIGURATION
• The communication and control module manage the circulator and
the communication interface between the system and the generator.
It is equipped with 2 micro-switches, No. 1 and No. 2.
Micro-switch No. 1
:
In “
ON
” position, the circulator starts automatically if the outdoor
temperature is below 0°C to prevent the hydraulic circuit from
freezing. This position is recommended if the outdoor module is
installed in a location exposed to freezing temperatures (not
recommended).
The factory default setting for this micro-switch is “
OFF
”.
Micro-switch No. 2
:
Must be set to
“
ON
”
(activates the water flow safety on the
system).
6.2.3 - SYSTEM PARAMETERISATION
• Make sure that the control unit selector is “
OFF
”.
• Check the parameterisation and adapt it accordingly based on the
type of installation.
The parameters are set on the control box (refer to the system's installation manual).
6.3 - ADDITIONAL HYDRAULIC CIRCUIT VERIFICATIONS
6.3.1 - FORCED CIRCULATOR OPERATION
• In order to conduct the final verifications of the hydraulic circuit, force
the pump to start as follows (installation power ON):
- Set the system control unit to “
OFF
”.
- Press and hold the
button for 5 seconds.
The circulator starts.
The circulator indicator light
flashes.
- Check that the “
H
2
O
” flow indicator is illuminated.
6.3.2 - VERIFICATIONS
• Purging of circuits.
• Hydraulic pressure (2 bar).
• Water flowrate: the unit is equipped with 1/4 SAE pressure taps at the circulator inlet and outlet (see paragraph 2.1.1),
so that the pressure loss can be measured using a hydraulic pressure gauge. Use the circulator curves below to
determine the water flow rate.
In order for the apparatus to work properly, the nominal flow rate must be respected.
6.3.3 - CIRCULATOR CURVES
Micro-switches
No. 1 and No. 2
0
10
20
30
40
50
60
70
80
90
1
1.52
2.53
SPW-W366
1.72
SPW-W486
2.3
SPW-W606
2.7
SPW-W366
SPW-W486
SPW-W606
Water flowrate (m
3
/h)
Manometric delivery head (kPa) of the circulator
Speed 1
Speed 2
Speed 3