– 6 –
SM830079
(1)
Unit Specifications
2. SPECIFICATIONS
MODEL No.
Indoor Unit
XS1852
Outdoor Unit
C1852 , CL1852
POWER SOURCE
230 - 208 V / 1 Phase / 60 Hz
PERFORMANCE
Cooling
Capacity
BTU / h
18,000
17,500
kW
5.27
5.13
Air circulation (Hi)
cu.ft. / min.
540
510
Moisture removal (High)
Pints / h
5.5
5.4
ELECTRICAL RATINGS
Voltage rating
VAC
230
208
Available voltage range
VAC
187 - 253
Running amperes*
A
8.2
8.77
Max. running amperes**
A
9.7
10.6
Power input
W
1,780
1,740
Power factor
%
97
98
S.E.E.R
BTU / Wh
10.6
10.6
Max. starting amperes
A
44.7
44.6
Maximum fuse size
A
20
FEATURES
Controls
Microprocessor
Low ambient control
Built-in 0
°
F (Only for CL1852)
Timer
ON / OFF 24-hours & Program
Fan speed Indoor / Outdoor
3 and Automatic control / 1 (3 : CL1852)
Air deflection
Horizontal / Vertical
– / Automatic
Air filter
Washable, easy access
Remote controller (Accessory)
RCS - 5PS4U
Refrigerant control
Capillary tube
Refrigerant tubing connections
Flare type
Drain pump (drain connection)
Max. head 9-27/32 in. above drain connection
Compressor
Rotary
Operation sound
Indoor - Hi / Me / Lo
dB - A
37 / 35 / 31
Outdoor - Hi
dB - A
52
REFRIGERANT TUBING
Limit of tubing length
ft.
(m)
65 (20)
Limit of tubing length at shipment
ft.
(m)
33 (10)
Limit of elevation difference
ft.
(m)
Outdoor unit is higher than indoor unit: 23 (7)
between the two units
Outdoor unit is lower than indoor unit: 23 (7)
Refrigerant tube
Narrow tube
in. (mm)
1 / 4 (6.35)
outer diameter
Wide tube
in. (mm)
5 / 8 (15.88)
Refrigerant amount at shipment
lbs. (kg)
R22 : 4.45 (2.02)