
2-26
Design of W-3WAY ECO-i SYSTEM Unit Specifi cations
1
2
3
4
5
6
7
8
(1) When linking outdoor units in a network (S-net link system), disconnect the terminal extended from the
short plug (CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor
units except any one of the outdoor units.
(When shipping: In shorted condition.)
Otherwise the communication of S-net link system is not performed. For a system without link (no con-
nection wiring between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 3-1)
3. Electrical Wiring
Outdoor unit
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
more than 3.3 ft
more than 3.3 ft
Branch
point
16 or fewer
Indoor unit
Indoor unit
Indoor unit
Indoor unit
less than 3.3 ft
Indoor unit
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Outdoor unit
Indoor unit
NO
NO
Branch point
Outdoor unit
Outdoor unit
Outdoor unit
Prohibited
Prohibited
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
CAUTION
(3) Do not install inter-unit control wiring such as star branch
wiring. Star branch wiring causes mis-address setting. (Fig.
3-2)
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer. (Branches
less than 3.3 ft are not included in the total branch number.) (Fig. 3-3)
Fig. 3-1
Fig. 3-2
Fig. 3-3
TD831139̲Sec2̲p24-30.indd 26
TD831139̲Sec2̲p24-30.indd 26
2008/04/17 15:59:26
2008/04/17 15:59:26