Vol. 0404E1                                                               2004. 04. 15 

 

Thyristor Power Regulators and 

Remote Controller 

 

 

 

USER MANUAL

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for TPR 3E PLUS

Page 1: ...Vol 0404E1 2004 04 15 Thyristor Power Regulators and Remote Controller USER MANUAL...

Page 2: ...er Description 4 1 Indicating 4 3 Changing Parameters 4 4 Parameters 4 5 Wiring and Operating According To Control Signal z Remote Control 14 5 1 Wiring for Remote Controller 5 2 TPR 3E PLUS Parameter...

Page 3: ...this unit with machineries warehouse medical equipments vehicle train airplane nuclear power or safety device etc it requires installing fail safe device It may result in serious damage fire or human...

Page 4: ...d outdoors It might shorten the life cycle of the product or give an electric shock 7 When control signal wire connection 20AWG 0 5mm2 should be used and screw blot on terminal block with 0 74N m stre...

Page 5: ...ition of external volume or internal limit setting 4 Various alarm mode over current line failed Un load over temp load unbalance 5 Relay alarm output 6 Programmable Soft start 7 Anti fluctuation by i...

Page 6: ...ents by high current and voltage circuits to limit the possible affects of noise 3 2 Wiring 1 Power Prior to applying power ensure the supply voltage is connected to the correct terminals as ordered s...

Page 7: ...run contact the external V R and the alarm output contact the interface terminals and power supply Figure 1 Control signal terminal block Note 1 Keep isolated between control signal line and power li...

Page 8: ...ss emergency stop 6 G1 7 G2 8 G3 Connecting external V R 1 Suitableness for output limit 2 Suitableness for non signal control V R 1k 1W A type 9 10 Alarm output Relay alarm contactor 250Vac 3A R load...

Page 9: ...city R and T line Top LED is control signal input sign Unit Middle LED is load current capacity sign of line R Unit A Bottom LED is load current capacity sign of line T Unit A 4 3 Changing Parameters...

Page 10: ...ng parameter 7 Once finished changing parameter values pressing PAR key for more than 2 seconds returns the controller to normal operation and the process value will be displayed Waiting approximately...

Page 11: ...N OFF Turn off On Turn on 5 11 Select input Analog Interface AnA Analog 4 20mA COm Interface 12 Address for interface 0 31 RS 485 address 13 Speed for interface 2400 4800 9600bps RS 485 speed 14 Delay...

Page 12: ...urrent input signal 2 ON OFF Contact Input Signal Output will be un continuous ON OFF by dry contact signal Maximum output voltage limit by output limit parameter OUt or external V R Figure 3 Wiring f...

Page 13: ...input signal 4 RS 485 Interface Optional TPR 3E PLUS will be control by RS 485 interface signals Apply power to the TPR 3EPLUS and go to parameter Symbol Smd Set up the control signal input Symbol CO...

Page 14: ...condition Display power current value 5 1 Wiring for Remote Controller RC 1000 1 Short distance installation In case of Install distance is less than 10m Use main unit power Terminal Vcc 2 Long distan...

Page 15: ...nected Remote Controller Table 5 Parameter Setting No Symbol Setting Data Range Set Value Description PASS 11 Select input Analog COm Refer to set remote Controller for control type 12 Address 0 31 1...

Page 16: ...ss 1 Speed 9600 BPS Delay Time 1 Figure 6 Front of Remote Controller Table 4 Remote Controller Parameter List No Symbol Setting Data Range Operation PASS 0 Indicating Changeable display of input signa...

Page 17: ...nly OFF Cut off output 8 Input filter 0 10 sec Against for fluctuation 9 Wait time for un load 0 254 sec If set to 0 stop the function 10 Operation for internal buzzer OFF ON OFF Disable On Enable 5 1...

Page 18: ...Cooling Under 100A Natural Cooling Above 120A Fan z Alarms Over Current Partial Line Failure Load Unbalance Unload Thyristor Overheating z Alarm Output AC 250V 1A R Load z Insulation Test Between Powe...

Page 19: ...SANUP ELECTRIC CO 1407...