Page 2: ...anual is the basic instruction document for your proper use and display of its superior performance and safe operation Please read it carefully and keep it properly and please hand it to the end user...
Page 3: ...HAPE AND INSTALLATION DIMENSIONS 14 2 4 THE SHAPE AND MOUNTING DIMENSIONS OF THE OPERATING PANEL UNIT MM 15 2 5 KEYBOARD TRAY 15 2 6 TERMINAL WIRING 16 2 7 CONTROL CIRCUIT TERMINAL FUNCTION 17 2 8 PER...
Page 4: ...METERS 25 4 1 FUNCTION PARAMETER TABLE 25 CHAPTER 5 FAULT DIAGNOSIS AND TROUBLESHOOTING 45 5 1 FAULT QUERY AT FAULT 45 5 2 LIST OF FAULT AND ALARM INFORMATION 46 5 3 TROUBLESHOOTING PROCEDURES 50 CHAP...
Page 5: ...s and type of the product complies with the order If any questions please contact the supplier of SINUS MINI series inverter or directly contact the Model specification SINUS MINI 0001 2S Inverter Ser...
Page 6: ...nvironmental temperature less than 60 degrees Celsius This product with the dangerous voltage and it is under the control of the movement mechanism with potential risk if you do not comply with the pr...
Page 7: ...shutdown and major accidents Therefore please take the necessary external protection measures or backup devices This product can only be used in accordance with the use of the manufacturer Without pe...
Page 8: ...9 8 3 14 1 24 2 Brake unit Built in as standard Protection class IP30 Cooling mode Self cooling Forced air convection cooling SINUS MINI 2T Three phase AC 220V constant torque heavy load application...
Page 9: ...unit Built in as standard External braking unit needed Protection class IP30 Cooling mode Self cooling Forced air convection cooling SINUS MINI 5T Three phase AC 460V constant torque heavy load appli...
Page 10: ...R function When the network voltage fluctuates the output voltage fluctuation is very small and almost constant V F standard feature PID control acceleration and deceleration time is adjustable variab...
Page 11: ...evices are connected to the inverter as transducer with short and thick reliably connected to public places or public star connection grounding bus motor please contact the nearest ground please do no...
Page 12: ...r in the motor line near the inverter output terminals adding zero phase reactor in the control line near the inverter control terminal can effectively reduce the electromagnetic interference and the...
Page 13: ...n the following table Environment Requirement Installation environment Installation indoor without direct sunlight Work temperature 10 40 Storage Temperature 20 60 Environment temperature No condensat...
Page 14: ...avoid and inverter installed in the same cabinet it is strictly prohibited to brake resistance and other high heating equipment installed in the inverter inlet 2 2 Mechanical installation SINUS MINI s...
Page 15: ...ulti inverters 2 3 Inverter shape and installation dimensions Voltage level Inverter model Outline construction and installation dimension mm Weight kg W H D W1 H1 Mounting hole d Single phase 220V SI...
Page 16: ...2 SINUS 0006 4T Three phase 460V SINUS 0002 5T 78 188 126 55 178 4 1 5 SINUS 0003 5T SINUS 0004 5T SINUS 0005 5T 96 225 137 65 215 4 2 SINUS 0006 5T 2 4 The shape and mounting dimensions of the operat...
Page 17: ...I1C 0 20mA DC 1 2 short circuit default AI1V 0 10V DC 3 2 1 J5 2 3short circuit AI1C 0 20mA DC 1 2 short circuit default AI1C 0 20mA DC 3 2 1 2 3short circuit AO1C 0 2mA DC 1 2 short circuit default A...
Page 18: ...sing external signal to drive DI1 DI5 OP should be connected to external power supply The factory defaults J7 to the 24V connection Analog input AI1 GND Analog input terminal 1 1 Input voltage range D...
Page 19: ...s no terminal resistance 485 485Negative side of differential signal GND 485Shielding GND of communication Internal isolation from COM NOTE If the user adjustable potentiometer in 10V and GND potentio...
Page 20: ...g status indicator ON running state OFF stop state Flashing stopping state green FWD REV Positive and negative indicator light ON forward running OFF reverse running red TUNE TC Tuning Fault indicator...
Page 21: ...given via operation panel the key is used to control the start of inverter 2 After setting the parameter auto tuning start parameter auto tuning for inverter start up STOP RESET Stop Reset Key STOP RE...
Page 22: ...s STOP RESET key The drive restores to normal operation upon clearing the fault and the fault code is displayed again if the fault has not been cleared 3 5 Panel Operation Method 3 5 1 Panel Operation...
Page 23: ...SHIFT key with single direction shifting function to shift the flashing bit of parameters that is modification bit After finishing the parameters setup press the MENU key twice to exit programming sta...
Page 24: ...ters can be displayed by SINUS MINI drive via key 3 7 Motor auto tuning procedure Before selecting vector control mode user should input motor parameters correctly SINUS MINI drive can get motor s sta...
Page 25: ...g F0 02 to vector control Setting V F curve input F4 00 Setting torque boost F 4 07 Setting F0 02 to 0 open loop vector control Refer to F5 06 and F5 07 for torque input channel selection Set speed li...
Page 26: ...ction code Property This function code can be changed during operation This function code can only be changed during stopping status The setting of this function code is read only and cannot be change...
Page 27: ...decrease key 0 F0 07 Auxiliary frequency range selection 0 Relative maximum frequency 1 Relative primary given 0 F0 08 Auxiliary frequency setting range 0 100 100 F0 09 Setting Frequency selection 0...
Page 28: ...0 F0 19 parameter initialization 0 No operation 1 Clear fault information 2 Recover factory settings without motor parameters 3 Recover factory settings include motor parameters 4 Lock parameters Note...
Page 29: ...ved Reserved 0 F1 11 Reserved Reserved 0 F1 12 Restart after power failure 0 disabled 1 enabled 0 F1 13 Delay time for restarting after power failure 0 0 20 0s 2 0 F1 14 dynamic braking start voltage...
Page 30: ...quency 2 0 00 600 0 Hz 0 00 F2 11 Multi frequency 3 0 00 600 0 Hz 0 00 F2 12 Multi frequency 4 0 00 600 0 Hz 0 00 F2 13 Multi frequency 5 0 00 600 0 Hz 0 00 F2 14 Multi frequency 6 0 00 600 0 Hz 0 00...
Page 31: ...frequency hysteresis 0 0 600 0 Hz 0 00 F2 33 Droop control 0 00 10 00Hz 0 00 F3 00 Motor rated power 0 4 999 9KW Drive s rated power F3 01 Motor rated voltage 0 440V 380V F3 02 Motor rated current 0...
Page 32: ...2 times torque 4 User defined V F 0 F4 01 Base voltage 0 440V 380 F4 02 Base frequency 10 00 600 0 Hz 50 00 F4 03 Intermediate voltage 1 0 F4 04 32 F4 04 Intermediate voltage 2 F4 03 100 50 F4 05 Int...
Page 33: ...ved F5 10 Reserved Reserved F6 00 FWD REV mode 0 Two line operation mode 1 1 Two line operation mode 2 2 3 line operation mode 1 3 3 line operation mode 2 0 F6 01 Up down rate 0 10 99 99Hz s 1 00 F6 0...
Page 34: ...al for program operation 20 Start traverse operation 21 Pause traverse operation 22 DC braking command 23 Acc Dec disabled command 24 switch between panel control mode and external terminal control mo...
Page 35: ...12 External stopping command 13 Preset counting value arriving 14 Specified counting value arriving 15 Low voltage lockup signal 16 Overload pre alarm 17 Drive failure signal 18 Zero speed running 19...
Page 36: ...uency 100 0 F7 05 AI2 filter time 0 05 5 00s 0 50 F7 06 Minimum AI2 0 0 100 0 0 0 F7 07 Frequency corresponding to F7 06 0 00 100 0 Maximum output frequency 0 00 F7 08 Maximum AI2 0 0 100 0 100 0 F7 0...
Page 37: ...I feedback 8 AI1 9 AI2 1 F8 01 reserved 1 F8 02 Minimum AO1 0 0 100 0 0 0 F8 03 Minimum value corresponding to F8 02 0 0 100 0 0 0 F8 04 Maximum AO1 0 0 100 0 100 0 F8 05 Maximum value corresponding t...
Page 38: ...10 timing T10 0 3600 0 0 F9 12 Stage 11 timing T11 0 3600 0 0 F9 13 Stage 12 timing T12 0 3600 0 0 F9 14 Stage 13 timing T13 0 3600 0 0 F9 15 Stage 14 timing T14 0 3600 0 0 F9 16 Stage 15 timing T15 0...
Page 39: ...cteristic 0 FA 01 PID reference selection 0 Panel Digital setting 1 External analog signal AI1 2 External analog signal AI2 3 Communication 0 FA 02 Feedback channel selection 0 External analog signal...
Page 40: ...g 0 3600s 0 FA 18 Sleeping frequency 0 00 400 0Hz 0 00 FA 19 Delay time of waking 0 0 60 0s 0 0 FA 20 Waking value 0 0 100 0 100 0 FB 00 Traverse mode 0 Auto mode 1 Manual mode 0 FB 01 Preset traverse...
Page 41: ...equency 0 FC 02 Local address 1 32 0 is the broadcast address 1 FC 03 Communication timeout detect 0 No detection 2 0 10 0s 0 FC 04 Response delay 2 1000ms FC 05 EEROM Store selection 0 Store 1 no sto...
Page 42: ...current limiting 0 Disabled 1 Enabled during Acc Dec disabled at constant speed 2 Enabled during Acc Dec enabled at constant speed 1 FD 10 Auto reset 0 Disabled 1 5 Times of fault reset 0 FD 11 Auto...
Page 43: ...inverter by changing the F0 11 0 FE 01 Terminal start delay 0 1 20 0s 0 FE 02 Terminal stop delay 0 1 20 0s 0 FE 03 MODBUS respond 0 The Modbus protocol responds to the write command 1 The Modbus pro...
Page 44: ...0 Frequency setting 1 Preset line speed 2 DC Bus voltage 3 Reserved 4 Analog input AI1 5 Analog input AI2 6 I O status 7 external counting value 8 PI reference 9 PI feedback 0 FH 02 Line speed factor...
Page 45: ...ntrol Inverter User Manual 44 FH 11 Frequency setting at last fault FH 12 Running frequency at last fault FH 13 I O state at last fault FH 14 Total operating time FH 15 Software version of CPU Board F...
Page 46: ...lated information about the failure such as output frequency frequency setting output current rotating direction operating condition and the 3 latest faults which is shown in the table below Fault cod...
Page 47: ...torque boost Power level of inverter is small Replace with inverter with proper model 2 oc2 Over current protection when deceleration operation Low grid voltage Check input power supply Rotating iner...
Page 48: ...Motor short to ground Check motor wiring Rotating inertial of load is too large Choose appropriate energy braking components Deceleration time is too short Lengthen deceleration time 12 ou3 Over volta...
Page 49: ...ncrease the motor overload protection time V F curve ratio is set too large Adjust V F curve setting and torque increment DC braking current is set too high Reduce the DC brake current 20 LP Input pow...
Page 50: ...loop feedback failure Analog close loop feedback failure Improper setting of FA parameter group Modify setting of FA parameter group feedback signal lost Check feedback signal 28 ER07 Tuning error Imp...
Page 51: ...d further expansion of the fault NO YES Seek for technical help Seek for technical help END Identify the fault code per 4 4 4 Common Characters Displayed by LED AND whether the fault code can be Ident...
Page 52: ...Environment Temperature Thermometer 10 40 C Derated at 40 to 50 C and the rated output current shall be decreased by 1 for every temperature rise of 1 C Humidity Humidometer 5 95 no condensing Dust o...
Page 53: ...SINUS MINI High performance Vector Control Inverter User Manual 52...
Page 54: ...permission b Fire flood abnormal voltage other disasters and secondary disaster c Hardware damage caused by dropping or transportation after procurement d Improper operation e Trouble out of the equi...