SINUS PENTA
PROGRAMMING GUIDE
374
/
486
41.2.
List of Parameters C225 to C235
Table 115: List of parameters C225 to C235
Parameter
FUNCTION
Access
Level
MODBUS
Address
Default
Values
C225
Procedure in case of Power Down
ENGINEERING
1225
3:Alarm
C226
Power Down enable delay
ENGINEERING
1226
10 ms
C227
Stop ramp time in Power Down
ENGINEERING
1227
20 sec
C228
Start increment of ramp gradient in P.D.
ENGINEERING
1228
0.10%
C229
Improved sensitivity of DC bus control
ENGINEERING
1229
1
C230
Voltage level of DC bus in Power Down
ENGINEERING
1230
339V for class 2T
679V for class
4T(380;480V)
707V for class
4T(481;500V)
813V for class 5T
976V for class 6T
C231
PI Proportional constant for automatic
deceleration
ENGINEERING
1231
0.050
C232
PI Integral time for automatic deceleration
ENGINEERING
1232
0.5 sec
C234
Ramp action at the end of Power Down
ENGINEERING
1234
0: Stop
C235
Motor speed at the end of Power Down
ENGINEERING
1235
0 rpm
C225 Procedure in Case of Power Down
C225
Range
0
÷
3
0: Disabled
1: Yes
2: YesV
3: Alarm
Default
3
3: Alarm
Level
ENGINEERING
Address
1225
Function
Type of power down:
0:
Disabled
The Power Down function is disabled.
1:
Yes
In case of mains loss after a time longer than the time set in
C226
starting from the mains loss detection, the deceleration ramp set in
C227
is
performed.
2:
YesV
In case of mains loss, deceleration is automatically regulated by
a PI regulator (see
C231
and
C232
), so that voltage level in DC link is kept
constant at the reference value set in
C230
.
IFD control: because no torque demand regulation is available, the deceleration
ramp gradient is adjusted depending on the gradient value set in
C227
.
3:
Alarm
In case of power failure, the
A064 Mains Loss
alarm trips after
the time set in
C226
.
NOTE
If a drive is DC-powered by a Regenerative Penta (or an equivalent drive stabilizing DC
bus voltage), Power Down cannot occur (
C008
= xT Regen, where x can be 2, 4, 5, or 6 ).