PROGRAMMING GUIDE
SINUS PENTA
307
/
486
36.1.1.
C
OMMAND
S
OURCES
The drive commands
may be sent from the following sources:
0: Disabled
1: Terminal board A
2: Serial link (with MODBUS protocol)
3: Fieldbus (fieldbus on optional board)
4: Terminal board B
5: Keypad (remotable display/keypad)
The factory-setting enables only Terminal Board A (
C140
=1 and
C141
=1) as a command source (see also the DIGITAL
INPUTS MENU). Both Terminal board A and B refer to the same terminal board located on the control board, but allow
switching between one set of START, STOP, REVERSE commands sent to three terminals to a different set of
commands sent to three different terminals.
Most commands may be delayed (when enabled or disabled): refer to the TIMERS MENU.
Figure 49: Selecting the command sources
If the keypad is not selected as a command source or, when the keypad is selected, if the the
STOP
input function is
also enabled (
C150
≠
0), more than one command source may be enabled at a time by programming parameters
C140
,
C141
,
C142
accordingly. The logic function for the different command sources is as follows:
Source programmed in:
Enable Conditions:
If:
C179
(Source Selection) = 0: Disable
and (logic AND)
C179a
(Command Selection) = 0: Disable
If:
C179
= MDIx input
or (logic OR)
C179a
= MDIx input
C140
Always active
Active if MDIx = 0
C141
Always active
Active if MDIx = 1
C142
Always active
Always active
Table 90: Enable conditions of the control sources
•
AND
for the terminals allocated to the
ENABLE
functions (
MDI2&S
inputs
on physical terminals
, MDI2
via
serial command or fieldbus),
ENABLE-SW, External Alarms n.1, n.2, n.3
.
•
OR
for all other terminals
.