PROGRAMMING GUIDE
SINUS PENTA
153/486
Figure 19: Curve (voltage; speed) implemented by AO1 (Example 2)
0
1
2
3
4
5
6
7
8
9
10
-500
-400
-300
-200
-100
0
100
200
300
400
500
( rpm )
( V )
Example 3:
Table 39: Programming AO1 (ABS 0 ÷ 10V)
Parameterization of Analog Output AO1
Parameter
Value
Description
P176
ABS 0÷10V
AO1 Analog output
P177
1: Speed
Selected variable for AO1 analog output
P178
–500 rpm
Min. value of AO1 selected variable
P179
+500 rpm
Max. value of AO1 selected variable
P180
0.000 V
AO1 Analog output offset
P181
0 ms
Filter for AO1 analog output
P182
0.0 V
Min. AO1 output value with reference to
P178
P183
10.0 V
Max. AO1 output value with reference to
P179
Figure 20: Curve (voltage; speed) implemented by AO1 (Example 3)
0
1
2
3
4
5
6
7
8
9
10
-500
-400
-300
-200
-100
0
100
200
300
400
500
( rpm )
( V )
NOTE
The programming mode above would imply a straight line passing through (–500rpm; 0V)
and (+500rpm; 10V), but based on the selected mode and considering the variable as an
absolute value, the min. point for output AO1 will be (0 rpm; 5 V).