18
Santa Fe Oasis105 Installation & Operation Instructions
Santa-Fe-Products.com | 800.533.7533
Service - Troubleshooting
Display
Code
Error Name
Possible Reason
Troubleshooting
Procedure
Service
Required
E6
Temperature
too high
Sensor reading incoming air temp
is over 120°F
• Dehumidifier will circulate
air for 15 minutes every
hour.
• Dehumidifier will not
operate until incoming air
temp sensor reads below
120°F
No
E7
Temperature
too low
Sensor reading incoming air temp
is under 40°F
• Dehumidifier will circulate
air for 15 minutes every
hour.
• Dehumidifier will not
operate until incoming air
temp reads above 40°F.
No
E8
Communication
from power
board is not
being received
1. There is a cable connection
issue
2. Defective power board
The power board will
continue to run unit
using the last settings
but changes to operation
cannot be made until
communication is
restored.
Yes, only if
operational
changes are
required
E9
Over pressure
refrigeration
system
1. High pressure sensor has
tripped due to excess pressure
in the refrigeration system
2. Incoming air temp is too high
Power board will be in
system protection mode.
Yes, only
if the error
persists
when
operating
below 90°F
incoming
air