Code
Function name
Setting range
Increment
Unit
Default
value
Changeable
during
operation
F403
Heater B count
1
to
5
1
–
1
✗
F404
Current gain
adjustment
1
to 9999
1
A
0
✓
F405
Voltage gain
adjustment
1
to 999.9
0.1
V
0
✓
F406
Power gain
adjustment
1
to 999.9
0.1
kW
0
✓
F407
CT selection
0: External CT
1: Built-in CT
–
–
0
✗
F408
Conversion
board model
check
(No setting)
–
–
–
–
F400: Feedback control method
Select the feedback control method. The selectable values depend on the connected
conversion board model. For details on the models, see “11.2.1 Model list.”
F401: Heater disconnection detection function
Select the heater disconnection detection function mode and enable/disable the function.
The heater disconnection detection function has two selectable modes: the standard version
and the highly functional version. This function can be temporarily disabled with this
parameter.
Select the setting that matches the desired combination of the mode and enabled/disabled
state.
Setting
Mode
Enabled/disabled
Condition
0
Standard
version
Disabled
When the conversion board model does not
support heater disconnection detection. Or,
when the circuit is connected for the standard
version, but the function needs to be disabled
temporarily.
1
Highly
functional
version
Disabled
When the circuit is connected for the highly
functional version, but the function needs to be
disabled temporarily. ※
2
Standard
version
Enabled
When the circuit is connected for the standard
version, and the function needs to be enabled.
3
Highly
functional
version
Enabled
When the circuit is connected for the highly
functional version, and the function needs to be
enabled.