SEC3002 FIRE ALARM CONTROL PANEL
Page 18 of 24
5.2.5 Advanced functions
Besides some essential system configurations mentioned above, this ADVANCE category
provides supplementary functions for system commissioning including loop learn, data
load/backup, file reset and update of the system.
Loop learn
This function activates the panel’s automatic loop learn facility. As it prompts below, the loop
learn process may take about 120s and it cannot be stopped during the period.
When the auto-learn completes successfully, a comparison between the loop learn result and
the initial data will be given. And as it prompts, selecting Confirm will get entry to the
detector/module setup window with the Reg and Product Type data overwritten by the new
auto-learned data, which means the previous system configuration will be changed. So take
care about this before you continue with it. See the picture below.
Additionally, other attributes about the device will be set as default settings, for example, the
devices will be all assigned to zone 1 which can be modified as designed later.
When the time counted is over, the loop learn fails and it prompts timeout error.
Save data to U-disk
This function will copy the file of system configuration to the U-disk you insert at the top right
USB port of the front panel.
Note
: Choose a U-disk of capacity within 32G and make sure its file system is FAT32 or FAT16,
otherwise format it on computer. The remaining capacity of the U-disk should be above 2M for data
backup
.