SEC3002 FIRE ALARM CONTROL PANEL
Page 9 of 24
DISABLE
Lit yellow when one or more loop devices, zones or outputs are
disabled
POWER FAULT
Lit yellow when the panel’s mains power, battery or charger is in
fault condition
DELAY
Steadily lit yellow when delay is configured as part of one or more
cause and effect rules. Flashes when there is a delay running
LOGIN
Lit yellow when the panel is in access level 2 or 3
SOUNDER FAULT
Lit yellow when there is loop sounder in fault condition
SOUNDER DISABLED
Lit yellow when loop sounders are disabled
SOUNDER SILENCED
Lit yellow when all sounders of the system have been silenced by
pressing the SILENCE/RESOUND button
SYSTEM FAULT
Lit yellow when the panel is unable to provide mandatory
functions
S.C. FLT/DIS
Lit yellow when the sounder circuit output (S.C.Out) is disabled and
flashes when it has a fault. Disable has priority over fault
F.P.E. DISABLED
Lit yellow to indicate the F.P.E. Out is disabled
4.2 Button controls
0~9, *, #
Used to enter numbers, letters and marks in a text box.
Plus, * button provides access to LOGIN and LOGOUT
windows at non-text-input state
TAB
Pressed to make the cursor move, or toggle between
different items or windows from left to right, up to down
◄
▼ ▲
►
For toggling, scrolling, or moving the input cursor
DELETE
Deletes the character left to the cursor
ENTER
Confirms a text input or a manual operation
COPY
Copies the content of text selected currently
PASTE
Pastes the content of text copied to current text box
LOGIN
Provides access to the prompt window for user’s login or
logout
MENU
Provides access to the panel’s user menus at access level
2&3
CANCEL
Used to cancel a navigation step or exit the current menu
VIEW STATUS
Displays the window of current alarm message (as
appropriate). Then press TAB,
◄
or
►
to go through fire,
disablement or fault messages.