A9097B Intelligent Sounder Beacon Base
Read through these instructions before using this device to ensure correct installation and use!
I.
Overview
A9097B Intelligent Sounder Beacon Base is addressable , low power consumption and loop powered to reduce installation
cost. The Intelligent Sounder Beacon Base can be used with a detector. The detector can be mounted directly on the base.
It can be used with a bus-type fire alarm control panel. After receiving a start command given by the fire alarm control
panel following an accident, the Sounder Beacon Base will begin to work. At this moment, the Sounder Beacon Base will give
a dazzling visual alarm signal and a harsh audible alarm signal, to remind the persons on the scene of the accident, the fact that
a fire has occurred on the site, quickly and necessity to take related evacuation measures, thus preventing the fire accident from
becoming a major one.
The Sounder Beacon Base may be used to give audible alarms and flashing alarms at the scenes of accidents. It is
applicable to places like high-rise residential buildings, public places, hotels, amusement buildings, factories, shopping centers,
hospitals, schools, office buildings and stock exchanges, and particularly to the places with a low visibility or the possibility of
generation of smoke.
II. Product features
Meet EN54-3.
It is installed by rotating, it can be installed conveniently and reliably.
It uses multiple super bright red LEDs as light sources for visual display, ensuring a striking display effect.
Set the detector base and Sounder beacon as a whole, it can be equipped with A9030T smoke detector and A9020T
heat detector, single point connection for detector, sounder and LED beacon (saving on both time and installation
costs) , debugged and maintained conveniently.
III.Technical Specification
1. Executive Standard: EN54-3 Type A Sounder
2. Loop input: DC24V(20-28V),
≤
2mA(monitoring status),
≤
8mA(alarm status)
3. Power consumption:
≤
0.2W@DC24V
4. Sound output:
≥
73dB(A)@ 1m
5. Flash rate: 1~2Hz
6. Flash color: RED
7. Protection class: IP21C
8. Operating temperature: -10
℃~
+55
℃
Relative Humanity:
≤
95% (non-condensing)
9. Material Body: Flame retardant PC/PC+ABS
10.Dimension:
φ
115mm×H44mm (with bracket) , See Fig.1
11. Weight: about 169g
2
Fig.1
IV. Use and engineering application
1.
Wiring:See Fig.2.The Sounder Beacon Base is subject to a two-wire non-polarity connection: Terminals 1 and 3 are
respectively connected with the terminals L1 and L2 of the loop bus of a compatible fire alarm control panel.
Terminals 2 and 4 are respectively connected with the terminals 2 and 4 of A9020T(Heat Detector) or
A9030T(Smoke Detector).
TERMINALS
TO NEXT DEVICE
1 PAIR FIRE CABLE
FROM CONTROL PANEL
1 PAIR FIRE CABLE
Fig.2
2.
Coding address: The Sounder Beacon Base must be encoded address by a special coder (CODER-F900E) before the
installation. Fig.3 shows the wiring diagram of the Sounder Beacon Base and coder. After wiring, press the “#” key
to select “324” mode, set the coder with the coding function, then select the correct address number and press the
“RUN/STOP” key to complete the address code setup. (Note: See the User’s Manual of the coder for the detailed
operation.)
Fig.3