Step

Español

Français

8b

Pulsar 0 para ajustar el punto de arranque. 
Cuando la válvula está completa-mente cerrada 
resetear el punto de arranque a la fase de ex-
citación Ø1 usando el siguiente método: Tener 
la bobina desconectada, luego darle corriente 
y cargarla a 560 pulsos para cerrar la válvula. 
Durante el proceso de control.

Paramétrer 0 pulse pour ajuster le point de départ. 
Lorsque la vanne est complètement fermée, re- par-
amétrer le point de départ avec la phase d’excitation 
Ø1en utilisant la méthode suivante : Garder la bobine 
déchargée, ensuite charger la et appliquer 560 pulses 
pour fermer la vanne. Pendant le process de contrôle : 
Rajouter 8 pulses pour fermer la vanne.

8c

Para abrir la válvula usar los pulsos de excitac-
ión (tabla 1) de la posición 1 a la 8.

Pour ouvrir la vanne, utiliser la table d’excitation 1 
(table 1) de la position 1 à 8

8d

Para cerrar la válvula usar los pulsos de excitac-
ión (tabla 1) de la posición 8 a la 1.

Pour fermer la vanne, utiliser la table d’excitation 1 
(table 1) de la position 8 à 1

8e

El motor de pasos con imán permanente tiene 
una función de automanteni-miento y no 
necesita energia para mantenerse en posición.

Le moteur pas à pas avec aimants permanents à un 
phénomène d’auto maintien et n’a pas besoin d’être 
alimenté pour laisser la vanne ouverte.

9

ATENCION: No alimentar la bobina eléctrica con 
tensión cuando ésta no está montada sobre la 
válvula.

ATTENTION: Ne pas alimenter la bobine si elle n’est 
pas montée sur la vanne.

ELECTRONIC EXPANSION VALVE  

SERIES LPF 

INSTRUCTIONS

Applicable to fluids and refrigerants of Group 1 and 2 as defined in article 13 (1) (b)  

of Directive 2014/68/EU.

Temperature Allowed Range:

 -40°F to +158°F (-40°C to +70°C)

Design Pressure (PS):

 

     42 bar (609 psi) / 60 bar (870psi)

GENERAL SPECIFICATIONS

LPF series Electric Expansion Valves are designed for use in 
refrigeration systems. The valve port is designed with PTFE 
(Teflon™), creating a tight seat equivalent to a solenoid valve 
thus preventing liquid refrigerant from migrating to the 
evaporator and compressor.

1

Respect the indicated installation position into the refrigerant circuit of the valve and of the sensors 
required for the calculation of superheat.

2

3

INSTALLATION INSTRUCTIONS: 

EEV 

SERIES LPF

TECHNICAL SUPPORT

For additional technical information and to learn more about 
Sanhua’s full product line, please visit:

sanhuausa.com

II-LPF-MU-R1909-NA
Sanhua©2020 All rights reserved. Subject to change without notice.

WANT THE LATEST SANHUA NEWS?

FOLLOW US

SANHUA

 INTERNATIONAL

[email protected]

Technical information

 

sanhuausa.com

ADDITIONAL LANGUAGES CONTINUED

EEV 

SERIES LPF 

CONTINUED

1

3

A

B

100 Mesh Sieve

Flow direction “A” is good. Do not flow in direction “B”. 
Do not use this valve on heat pumps. Install a filter 
drier and 100 mesh sieve before the inlet of the valve. 

Respect the indicated mounting position (pos.1). 
It is prohibited installation with stator pointed 
downwards (pos.2 and 3).

2