background image

Installation, Operation & Maintenance Manual                                                                  Merlin Detector i-S 

 

 

 Iss: 1  170322 

10  

Why is it important?  

A detector may visually appear in good working order, but its sensitivity and accuracy can be inhibited by external 
factors. Dust, humidity, temperature fluctuations, cleaning products, contaminants, exposure to its target gas or 
sensor drift (ageing) can cause a decline in sensitivity, accuracy, and eventual failure.

 

 

How often?  

Regular bump tests are important to make sure the detector can detect a release of gas as early as possible and 
usually takes seconds (gas type dependant i.e., CO sensors will take over a minute) and is often completed alongside 
a scheduled fire alarm test, however the frequency should be determined following an appropriate risk assessment by 
the end user. We recommend testing detectors every 12-18 months along with the regular fire test procedures and 
coincide with the annual service message prompted on the detection system after each year of service/operation. 
 

What do I need?  

Contact your S&S representative for details of suitable bump testing kits and gases. Kits usually consist of a certified 
gas cylinder or spray. We recommend only using S&S calibration gas kits to ensure correct flow rates meet S&S 
technical requirements. A bump testing gas is usually a concentration mix that exceeds the highest alarm set point.  
 

Bump Test Procedure 

 

To increase reaction time, cover the escape vents at the sides of the device.  

 

Always remove the regulator/valve if using a cylinder after use! 

 

Always give at least five (5) minutes between testing the same unit or until gas has fully dispersed! 

 

Always consider safety and use equipment in accordance with Safety Data Sheets! 

 

Reference should always be given to any applicable national & local law and industry codes. 

 

Generally, the gas concentration should be greater than the alarm threshold of the device. 

 

Always remove the regulator/valve after use if using a cylinder!  

 

All cylinders will re-seal upon removal of the regulator/valve! 

 

Deviating from this test process is deemed improper and may affect the functional safety of your device!  

 

Exposure to chemicals, smoke, or any other materials other than the gases intended to be monitored can seriously damage 
the gas sensing elements! 

 

Always allow a minimum of 5 minutes before testing the same unit! 

 

1.

 

Ensure you have the correct gas for the device type prior to application. 

2.

 

Offer up the applicator hose/cone or spray and apply to the small vents of the device located underneath. 

3.

 

Apply gas. 

4.

 

The device will enter alarm status after reaching alarm set point. 

5.

 

The device will activate all configured outputs/relays. 

 

At this point…

 

 

6.

 

Remove applicator hose/ cone or spray. 

7.

 

Reset by pressing the touch sensor. 

8.

 

Test complete.  

9.

 

Record your test details. 

 

 
 

End of Operational Life (EOL) 

 

The EOL is approximate from the first five (5) hours of continuous power! 

 

The EOL will depend on the type of gas your detector is targeting and may vary depending on its application and 
environmental conditions such as the frequency of exposure to the target gas, poisons, or inhibitors! 

 
The typical life of a gas detector depends on its application and intended target gas, in addition the 
operational life can be prolonged if the system and equipment is installed and maintained in accordance 

the instructions stated within this manual. At the end of its predicted operational life 

 

the detector will display an ‘End 

of Life’ screen. 

This message indicates that the detector has reached its expected operational lifecycle and no gas 

levels are displayed. You must contact your supplier immediately for replacement.  

Summary of Contents for Merlin Detector i-S

Page 1: ...170322 1 Merlin Gas Detector i S Installation Operation Maintenance Please read this manual carefully and retain for future use For specific requirements that may deviate from the information in this...

Page 2: ...Power Input 6 Wiring Alarm Relays 7 Alarm Relay Setting Switch Latch On Off 7 Wiring 0 10V Analogue Output 7 CO2 Selection Switches 7 Audible Buzzer Switch 8 Factory Set Condition 8 Operation 8 Initia...

Page 3: ...nufacturer s Warranty Warranty coverage The manufacturer warrants to the original consumer purchaser that this product will be free of defects in material and workmanship for a period of three 3 years...

Page 4: ...is also relevant to toxic gas detection Recommended heights may vary based on air flow and temperature conditions in addition to the proposed application and location Locations for detectors will var...

Page 5: ...wo gang electrical box Restrain the hazardous live wiring from accidental loosening to prevent wires from moving after installation and touching parts of opposite polarity or at low voltages Isolate t...

Page 6: ...d any warranty Wiring Power Input Standalone Power 12 24V power inputs can be either AC or DC Terminals are pluggable type to ease connections Merlin GDP Power Connection Power is supplied via the GDP...

Page 7: ...a red dot on the screen when the alarm relay has latched The alarm will beep every 10 seconds to alert the user that the detector entered an alarm state To reset the Detector press and hold the touch...

Page 8: ...tors are shipped pre calibrated and configured Buzzer On Off Switch On Alarm Relay Setting Switch On CO2 Selection Pre Alarm 800ppm Alarm 1000ppm 0 2000ppm 0 10V Output Range Operation Initial Power U...

Page 9: ...rly using a slightly damp cloth Never use detergents or solvents to clean your device Never spray air fresheners hair spray paint or other aerosols near the device Never paint the device Paint will se...

Page 10: ...uld always be given to any applicable national local law and industry codes Generally the gas concentration should be greater than the alarm threshold of the device Always remove the regulator valve a...

Page 11: ...Evaluated Operating 10 50 C 20 90 RH non condensing Storage 0 50 C 30 80 RH no condensation Altitude Rating 2000m Wiring Typical Min 2 5mm2 75 C min Tinned copper Approvals Electrical Safety and Elec...

Page 12: ...om any unforeseen damage caused by transit installation Every effort is made to ensure the accuracy of this document however S S Northern can assume no responsibility for any errors or omissions in th...

Reviews: