Installation & Operation Manual                                                                                         Merlin 1000BH 

Rev: 09   03-21

 

 

   Auto Reset Switch

 

 
The panel has a built-in auto reset feature. There is a dipswitch located on the circuit board labelled [AUTO RESET].  
This is factory set in the ‘Off’ position i.e. when power is restored after a power cut or loss, the panel has to be 
restarted manually. When enabled, the system will restart automatically when power is restored and can be reset 
following a fire alarm and when the alarm is cleared. 
 

AUTO SWITCH 

CONDITION 

OFF 

Panel has to be restarted manually following a power cut/loss and/or alarm. 

ON 

Panel will automatically restart when power is restored and can be reset remotely via a fire panel. 

 

   BMS Switch

 

 

The panel can be integrated with a BMS to make or break a circuit on gas on/gas off, (valve open or valve closed). 

This will tell the BMS whether or not electrical power is being sent to the solenoid. There is a dipswitch located on 
the circuit board labelled [BMS SEL]. This is factory set to ‘OFF’ position which signals the BMS on gas on/gas off. 
When switched to ‘ON’, the system will only signal the BMS on a fault, i.e. gas detected, EM Stop pressed, etc.  
 

BMS SWITCH 

BMS SIGNAL 

OFF 

Gas on or off only. 

ON 

Error condition i.e. gas detected, emergency stop pressed. 

 

   Fill & Prove Time Switch

 

 
There are two switches located on the circuit board labelled [FILL TIME] and [PROVE TIME].  

FILL TIME: Amount of time the gas valve opens to fill the gas line on power up or reset. 

PROVE TIME: Amount of time the system tests the gas line for leaks on power up or reset. 

 

FILL TIME 

PROVE TIME 

OFF 

5 Seconds (Default) 

OFF 

30 Seconds (Default) 

ON 

10 Seconds 

ON 

50 Seconds 

 

Once the settings are changed - remove power for 10 seconds. 

 

   General Specification 

 

Model: 

1000BH 

Visual Indication 

LED 

Mains Electrical Power Input  

100-240vac 

Gas Solenoid Valve Output  

100-240vac  

Current Consumption 

12W max (50mA) @ 120VAC 

Internal Fuse 

3.15A 

Operating Temperature 

-10 ~ 40°C 30-80% RH 

Audible Alarm Buzzer dB 

65 dB (300mm distance in quiet conditions) 

Pressure Sensor Operating Pressure 

0 -100mbar  

Housing Material 

Polylac PA-765 

Compliance 

CE / UKCA 

O/All Dimensions (H x W x D) mm / inch 

180 x 255 x 77 mm/ 7.08 x 10.03 x 3” 

 
 

Summary of Contents for Merlin 1000BH

Page 1: ...Installation Operation Maintenance Please read this manual carefully and retain for future use The information contained within this manual should be referenced for typical installation and operation...

Page 2: ...fect the gas sensing elements This device is designed to detect the gas type displayed on the screen only It is not designed to detect smoke fire or other gases and should not be used as such This dev...

Page 3: ...te disposal for consumers of electrical electronic equipment When this product has reached the end of its life it must be treated as Waste Electrical Electronics Equipment WEEE Any WEEE marked product...

Page 4: ...are available PRESSURE SENSOR The terminals marked IN Red Wire Black Wire IN Blue Wire Screw sensor into the downstream port of the gas solenoid valve Operating Pressure 0 100mbar EM REMOTE The termi...

Page 5: ...to OFF position which signals the BMS on gas on gas off When switched to ON the system will only signal the BMS on a fault i e gas detected EM Stop pressed etc BMS SWITCH BMS SIGNAL OFF Gas on or off...

Page 6: ...n upon start up GREEN proving the gas line do NOT operate any appliances Test Fail Under normal working conditions this LED is off When the panel detects a gas leak on start up the LED will illuminate...

Page 7: ...to alarm and all signals outputs activate then the system is working safely If the system fails to operate as intended in an alarm state the gas detector must not be used until a full inspection and s...

Page 8: ...en damage caused by transit installation Every effort is made to ensure the accuracy of this document however S S Northern can assume no responsibility for any errors or omissions in this document or...

Reviews: