29
29
ENGLISH
-
Press
ENTER
to confirm the value entered.
-
Press
ESC
repeatedly until you reach the main menu.
-
Keep
ESC
pressed down for 2 seconds until the 3 mode leds light up in sequence. It is now in
RUN
mode, available for automatic inverter operation.
Step 3. Reconfigure range in sensor
Select the TPD sensor pressure range in accordance with the values in the third column in the table above.
4.3.4 Wiring diagram
Follow the inverter-motor wiring diagram shown in the following illustrations depending on the type of motor used
and whether this motor has thermal protection:
-
Fig.5.1.
Single phase power supply 1/230/50-60, three phase motor 230/400V without thermal protection and
0-10V signal (automatic reset).
-
Fig.5.2.
Three phase power supply 3/400/50-60, three phase motor 230/400 or 400V without thermal
protection and 0-10V signal (automatic reset).
-
Fig.5.3.
Single phase power supply 1/230/50-60, three phase motor 230/400V with thermal protection and 0-
10V signal.
IMPORTANT:
Before carrying out the wiring read the point 2.3 and 2.5 to determine the type of restart to
configure.
-
Fig.5.4.
Three phase power supply 3/400/50-60, three phase motor 230/400 or 400V with thermal protection
and 0-10V signal.
IMPORTANT:
Before carrying out the wiring read the point 2.3 and 2.5 to determine the type of restart to
configure.
Check that the “
SW1
” switch is in the “
SOURCE
” position
.
Install the indicated jumpers in the inverter terminal box.
Power the frequency inverter with suitable voltage for the inverter model in question.
The frequency inverter will start automatically when it receives power and will perform PI controller functions.
Summary of Contents for VFTM Series
Page 1: ...VFTM ...
Page 2: ......
Page 47: ...47 Fig 2 1 Fig 2 2 ...
Page 48: ...48 Fig 2 3 Fig 2 4 ...
Page 49: ...49 Fig 3 1 Fig 3 2 ...
Page 50: ...50 Fig 3 3 Fig 3 4 ...
Page 51: ...51 Fig 4 1 Fig 4 2 ...
Page 52: ...52 Fig 4 3 Fig 4 4 ...
Page 53: ...53 Fig 5 1 Fig 5 2 ...
Page 54: ...54 Fig 5 3 Fig 5 4 ...
Page 55: ......