Page 3: ...27 6 6 4 1 1 04 to 27 models Manual adjustment by REB ECOWATT accessory 27 6 6 4 1 2 33 to 100 models Manual adjustment by REB ECOWATT accessory 28 6 6 4 2 VAV Control variable air ow with CO2 sensor...
Page 4: ...proof of the product s conformity with current EU regulations 3 GENERAL INSTRUCTIONS A hazard analysis of the product has been carried out as provided in the Machine Directive This manual contains inf...
Page 5: ...ied without pallets The unit can be handled by a pallet transporter a forklift or a crane The handling machines will be adapted to the load and the lifting conditions In all cases the lifting will be...
Page 6: ...Model A B C 4 1558 798 8 894 1788 948 12 869 1738 1088 16 994 1988 1278 21 1169 2338 1678 27 1169 2338 1678 33 1169 2338 1678 The model 04 does not have central support The installer must make sure t...
Page 7: ...t the ceiling structure and the securing elements can bear the weight of the unit taking into account that it is a dynamic load Models 04 to 33 Model Weight kg 4 139 8 175 12 182 16 227 21 325 33 412...
Page 8: ...e securing elements can bear the weight of the unit taking into account that it is a dynamic load Model Weight kg 45 577 60 710 For all con gurations Once secured the device in correct position the in...
Page 9: ...by 3 pieces a Drainpipe b Female screw c Joint ring posar aquesta frase a sota d aquest punt a Horizontal versions of CADB T HE 04 to 33 b Horizontal versions of CADB T HE 45 and 60 c Vertical version...
Page 10: ...tical versions LV RV for outdoor installation In addition these versions have feet that allow direct placement on the ground In horizontal version models 04 to 33 ensure the suf cient space below the...
Page 11: ...33 TPP HE V 21 27 CADB T HE D DI DC 27 TPP HE H 21 27 33 TPP HE V 21 27 CADT HE D DI DC 33 TPP HE H 21 27 33 TPP HE V 33 CADT HE D DI DC 45 TPP HE H 45 TPP HE V 45 CADT HE D DI DC 60 TPP HE H 60 TPP H...
Page 12: ...0 400 860 400 250 400 950 173 12 1050 425 1700 500 400 1000 400 315 400 900 180 16 1240 450 1950 600 500 1190 425 315 400 1150 225 21 27 1640 550 2300 800 700 1590 525 400 500 1300 323 33 1640 650 230...
Page 13: ...0 400 315 227 21 970 1270 1750 400 500 400 325 33 1170 1270 1750 400 500 400 412 45 1120 1580 2100 400 600 600 400 577 60 1500 1630 2250 400 800 700 500 710 100 2050 1630 2250 400 1000 1100 650 842 6...
Page 14: ...5 1 230V 50Hz 1580 2 2 12 6 7 8 CADB HE DC 27 ECOWATT 400 2 700 83 8 1 230V 50Hz 2450 3 6 16 2 10 0 CADT HE DC 33 ECOWATT 400 3 300 88 4 3 400V 50Hz 2600 2 0 18 2 11 1 CADT HE DC 45 ECOWATT 400x600 4...
Page 15: ...n damage it The following table indicate the size and type o thread used on water coils for DC versions CADB T HE MODEL THREAD 04 08 12 16 21 27 and 33 1 2 45 60 and 100 1 To ensure the installation o...
Page 16: ...the pressure provided by the fan The horizontal sections should have a minimum slope of 2 Condensation connection 6 6 ELECTRICAL CONNECTIONS The CADB T HE ECOWATT range are supplied without a complet...
Page 17: ...g fans with EC motors 230V supply voltage OUTDOOR SWITCH ELECTRICAL SUPPLY 230V 1 50Hz Control connector Speed regulation 0V Stop 10V max speed Make the bridge between OUT and IN for Vmax Control conn...
Page 18: ...18 Horizontal version CADB T HE 33 LH RH In this size the units have plug fans equipped with EC motors with power supply to three phase 400V...
Page 19: ...motors with power supply to three phase 400V OUTDOOR SWITCH ELECTRICAL SUPPLY 400V III 50Hz Control connector Speed regulation 0V Stop 10V max speed Make the bridge between OUT and IN for Vmax Contro...
Page 20: ...he resistances must be carried out by the electric installer 6 6 2 Connecting the By pass All heat recovery units of the CADB T HE ECOWATT range have an internal by pass The by pass damper is supplied...
Page 21: ...rm an external electrical operation control board The installer is responsible for the correct operation of the electrical control specially re garding those safety requirements to avoid re risk due t...
Page 22: ...22 CADB HE DI 08 2kW 230V CADB HE DI 12 3kW 230V D HEATER REGULATOR E ON OFF SWITCH F RELAY G LINE PROTECTION H TEMPERATURE PROBE TG K330 J FLOW DETECTOR KM FAN RELAY X TIMER MCR 1...
Page 23: ...23 CADB HE DI 16 3 5kW 230V CADB HE DI 21 27 6kW 400V D HEATER REGULATOR E ON OFF SWITCH F RELAY G LINE PROTECTION H TEMPERATURE PROBE TG K330 J FLOW DETECTOR KM FAN RELAY X TIMER MCR 1...
Page 24: ...24 CADB HE DI 33 7 5kW 400V CADB HE DI 45 9kW 400V D HEATER REGULATOR E ON OFF SWITCH F RELAY G LINE PROTECTION H TEMPERATURE PROBE TG K330 J FLOW DETECTOR KM FAN RELAY X TIMER MCR 1...
Page 25: ...2kW 400V t s s t Khd Khd Khd E E E dd y D z E s ZD ZD dW dW Z Z CADT HE 100 24kW 400V D HEATER REGULATOR E ON OFF SWITCH F RELAY G LINE PROTECTION H TEMPERATURE PROBE TG K330 J FLOW DETECTOR KM FAN RE...
Page 26: ...AV mode Recommended accessories depending on the unit size and the control mode Model Accessories for VAV via CO2 Accessories for COP Accessories for CAV Converter Sensor Converter Sensor Electronic r...
Page 27: ...ons with electrical resistances The direct stop of the fans without a temporized stop would cause a high temperatu re rise of the resistances and the consequent risk of re inside the unit 6 6 4 1 1 04...
Page 28: ...ls Manual adjustment by REB ECOWATT accessory Simultaneous control of the supply and extract fans Supply fan Extract fan ZK K Z h h D Z K z Kt D Z K z Kt h h ZK K Z E ZK Z Z z D Z K s Z z Kt Z E D ZZK...
Page 29: ...ed 0 10V The 0V signal corresponds to the fan stop while the signal of 10V corresponds to fan maximum speed To perform the speed regulation in VAV with speed control with external sensor of CO2 or si...
Page 30: ...onnection of the different components 1 Connect the pressure transmitter TDP D accessory to the speci c pressure taps there are in the heat recovery unit Ensure that pressure taps and Same sign in the...
Page 31: ...the pressure must be constant in the duct system The value of this pressure must be determined by experimenting during the system start up process All CADB HE are equipped with EC motors single phase...
Page 32: ...32 AERO REG CONTROL Accessory TDP D Accessory EXTRACTION DUCTS SYSTEM SUPPLY DUCTS SYSTEM TDP D Accessory EXTRACTION DUCTS SYSTEM SUPPLY DUCTS SYSTEM AERO REG CONTROL Accessory...
Page 33: ...he position of the pressure taps depends on the model HORIZONTAL MODELS Horizontal models CADB T HE 04 to 33 LH RH on the side of inlet conection panel Horizontal models CADB T HE 45 to 60 LH RH on su...
Page 34: ...carefully the bypass g 2 4 Disconnect the electrical connector that feeds the bypass 5 Turn the bypass according to image g 3 and 4 6 Reconnect the electrical power connector of bypass 7 Place the by...
Page 35: ...35 Horizontal Factory con guration LH RH Examples of some of the con gurations that is possible to obtain from factory con guration EXHAUST AIR FRESH AIR Conf LV Conf LH Conf RV Conf RH...
Page 36: ...E 08 LH BA DX HE 08 LH BA AFC HE 08 LH FBL HE 08 H FB CA HE 08 H RH BA AF HE 08 RH BA DX HE 08 RH BA AFC HE 08 RH CADB HE D DI DC 12 LH BA AF HE 12 LH BA DX HE 12 LH BA AFC HE 12 LH FBL HE 12 H FB CA...
Page 37: ...X HE 21 27 RV BA AFC HE 21 27 RV CADT HE D DI DC 33 LV BA AF HE 33 LV BA DX HE 33 LV BA AFC HE 33 LV FBL HE 33 V FB CA HE 33 V RV BA AF HE 33 RV BA DX HE 33 RV BA AFC HE 33 RV CADT HE D DI DC 45 LV BA...
Page 38: ...ing frame verify that the locating lip in the frame is positioned in the top side Centering frame locating lip 3 Put the self adhesive sealing strip delivered in a bag included with the module around...
Page 39: ...its own weight Fix the module to the heat recovery unit permanently The access to xing points is performed by the side of the unit removing one of the side panes from the CADB or from the module maint...
Page 40: ...el to the CADB HE 6 Particularities of the modules with coils In the installation of external modules accessories with water coil or refrigerant coil the assembly of the module should be done in the w...
Page 41: ...LV RV 2 400 83 2 2 42 9 22 3798 16 1 BA AF HE 45 3 400 88 2 5 41 29 3 5045 13 2 BA AF HE 60 4 400 56 1 9 42 7 31 5345 10 3 6 9 2 2 Cold water coils for for 4 pipes installation Model Air Fresh Air Exh...
Page 42: ...04 320 56 1 8 16 18 33 4 8 1 8 33 1 2 0 7 BA DX HE 08 600 47 1 7 33 6 3 5 64 6 1 1 2 BA DX HE 12 900 105 2 4 33 2 6 5 3 92 4 7 1 7 BA DX HE 16 1 200 117 2 5 33 7 6 7 2 134 4 8 1 8 BA DX HE 21 1 600 76...
Page 43: ...f CADB T HE 45 and 60 The access to lters can be done by the side panels Vertical con gurations of CADB T HE 45 60 and 100 The access to lters can be done by two sides of the unit removing the speci c...
Page 44: ...3 G4 AFR HE 400 33 M5 AFR HE 400 33 F7 AFR HE 400 33 F9 CADT HE D DI DC 45 600x400 AFR HE 450 45 G4 AFR HE 450 45 M5 AFR HE 450 45 F7 AFR HE 450 45 F9 CADT HE D DI DC 60 700x500 AFR HE 500 60 G4 AFR H...
Page 45: ...the heat exchanger from the side panels Alternatively it is possible to disassemble the heat exchanger from the bottom panels However it is necessary to perform a major number of operations to procee...
Page 46: ...ased remove it Clean the heat exchanger with blowing with compressed air Vertical models CADB T HE 04 to 100 Due to the dimensions and weight of heat exchanger the cleaning of it has to be perform in...
Page 47: ...Contact the S P post sales service Reset by pushing the button RESET all the thermal protectors of the resistance Insuf cient performance of the exchanger Fins dirty Clean the exchanger Formation of f...