background image

Appendix D

Coordination

The S&C Overcurrent Control provides the flexibility required to meet the critical needs 
of protective device coordination between upstream and downstream devices such as 
cir cuit breakers and fuses. The example below shows how well the U.S. U4 time­overcur­
rent curve coordinates with both an upstream protective relay and downstream power 
fuse. The reference document used for these curve families and their equations is IEEE 
Stan dard C37.112­1996 IEEE Standard Inverse­Time Characteristic Equations for Over­
current Relays.

As shown in this instruction sheet and as seen on the overcurrent control’s user inter­

face, all pickup­current settings selections for E, K, Coordinating­Tap, Coordinating­Main, 
ANSI/U.S. U1 through U5, and IEC C1 through C5 are expressed in terms of primary amperes. 
However, in IEEE Standard C37.112­1996, U.S. and IEC curve families are expressed in 
terms of “multiples of pickup” where 1.0 on this axis represents the pickup setting. The 
standard uses this method of illustrating time versus current response because different 
current transformer ratios may be used for each specific application. In Vista SD switch­
gear, the CT ratio is fixed at 660:1. Consequently, we will refer to the “multiples­of­pickup” 
nomenclature for this example.

Based on the desired application, any of the 10 curve families can be selected to 

meet the coordination requirements. Adjusting the minimum pickup setting in terms 
of primary amperes moves the desired time­overcurrent curve to the left or right on 
the TCC coordi nation plot. In addition to the minimum pickup setting, a “time dial” 
feature is used to move the desired time­overcurrent curve up or down in time (in  
seconds) to meet the spe cific coordination requirements.

Example:

Referring to the coordination plot in Figure 2 on page 30, a Vista SD switchgear assembly 
with 600­ampere fault interrupt ers is placed into an electrical system where the upstream 
protective device is controlled by an overcurrent relay whose phase time­overcurrent curve 
family is set for a “CO­9” Very Inverse curve. The relay’s phase overcurrent pickup is set for  
960 amperes with a “time dial” setting of 2. There are two curves shown that take into 
account the operating time tolerance of the “CO­9” overcurrent relay. Downstream of the 
switchgear assembly is an S&C SMU­20 power fuse with a 200K­ampere rating. Its mini­
mum melt and total clearing curves are shown on the TCC coordination plot.

It is desired to coordinate the switchgear assembly with the upstream and downstream 

devices. A review of the ANSI/U.S. and IEC curve families resulted in the selection of the 
ANSI/U.S. “U4” curve. See Figure 3 on page 31. Its curve shape is similar to the other two 
devices’ curves. Using a TCC coordination program, it is possible to “fit” a time­overcurrent 
curve “between” the curves of the upstream source­side and downstream load­side devices. 
Note that the Vista SD curve selected is shown starting at 150% of the actual pickup setting 
in primary amperes (880 amperes 

×

 1.5 = 1320 amperes). The 

Time Dial 

setting selection 

of 0.8 was selected to maintain an acceptable coordinating time interval (CTI) between the 
upstream protec tive relay phase setting, the power fuse, and the Vista SD unit. Because of 
the extremely fine reso lution of pickup current and 

Time Dial 

settings selections within 

the ANSI/U.S. and IEC curve families, it is obvious there are other 

Pickup Current

 and 

Time Dial

 settings within the U4 family that could accomplish proper device coordina­

tion; in this example the S&C Overcurrent Control’s time­overcurrent curves are placed 
equidistant between the upstream and downstream device time­overcurrent curves.

  

S&C Instruction Sheet 695-515

  

27

Summary of Contents for Vista SD

Page 1: ...onfigure Menu 14 Test Trip Menu 16 Self Test Report Viewing of Self Test Report 17 Response to Self Test Failure 17 Self Test Failures and Warnings 18 Specifications Port Power 19 CT Power 19 Steady S...

Page 2: ...ranty provisions as set forth in the applicable product line specification bulletin are exclusive The remedies provided in the former for breach of these warranties shall constitute the immediate purc...

Page 3: ...OTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If you do not understand any p...

Page 4: ...G Hazardous voltage inside can shock burn or cause death Safety Information DANGER Never disconnect current transformer secondary circuits without de energizing the switchgear Hazardous voltage will s...

Page 5: ...ounted style Vista SD units the overcurrent control enclosure is fully submersible The elec tronics module is removable for programming in the shop Programming A personal computer furnished by the use...

Page 6: ...TCC curves can be customized into hundreds of dif ferent curves using a variety of instantaneous pickup settings discrete choices from 0 2 kA through 6 kA and definite time delay settings discrete ch...

Page 7: ...rmation can be accessed via a personal computer con nected to the data port of the control Self Testing Whenever the overcurrent control is powered up and then periodically thereafter it automatically...

Page 8: ...A for connecting thecontrolto auser furnished personal computer in the field These cables provide for both communications and power For Microsoft Windows users no special software is requiredtocommu n...

Page 9: ...areas of the menu system The User Password must be entered to change control settings test trip the solenoids and change the User Password The Group Configure Password is required to change the global...

Page 10: ...the Enter button View Menu INTERRUPTER 1 select number 1 View event report last 12 events 2 View load current 3 View relay settings 4 View relay self test 9 Switch to Main Menu View FI 1 1 View Event...

Page 11: ...n 10 of the maximum phase current 4 If only one target is declared from the previous logic target the faulted pole of the remaining three with the highest cur rent The primary RMS magnitude of each po...

Page 12: ...for menu Configure Menu 1 or 2 The Configure Menu option allows review and changes to the TCC curve set tings for the selected fault inter rupter The Configure Menu box below is for Fault Interrupter...

Page 13: ...rt discussed in View Event Report on page 10 will be reset Press Q to return to menu Phase TCC Curve E K TAP MAIN U1 U2 U3 U4 U5 C1 C2 C3 C4 C5 E tap Minimum Pickup Amps 50 65 80 100 150 200 250 300 3...

Page 14: ...m the new password re enter it after the third prompt USER PASSWORD CHANGE USER PASSWORD Enter new password four digits blank for no change Re enter new password Group Configure Menu The Group Configu...

Page 15: ...n to menu ID for Interrupter 1 20 characters INTERRUPTER 1 interrupter pole 1 ID for Interrupter 2 20 characters INTERRUPTER 2 interrupter pole 2 1 pole or 3 pole trip mode for Interrupter 1 1 3 1 3 1...

Page 16: ...of firmware Refer to the nearest S C Sales Office for instructions Test Trip Menu The Test Trip Menu option allows test tripping of the fault interrupters all three poles or single poles Step 1 Selec...

Page 17: ...on and firmware date code Trip Caps The status of the trip capacitors is reported for each fault interrupter pole If the trip capacitors are not charged to at least 50 volts a low condition is reporte...

Page 18: ...ion is enabled The message Relay enabled using default settings is displayed at the top of each menu If the EEPROM failure persists i e if default settings cannot be stored in EEPROM a self test failu...

Page 19: ...C Curves 5 A primary and 5 of setting Time Overcurrent Response E K Coordinating Tap and Coordinating Main Curves 0 to 10 in terms of current OR 0 to 20 in terms of time OR 0 to 6 ms whichever gives t...

Page 20: ...rs Terminal numbers are identified by labels on the electronics module or terminal block Trip outputs Electronics module Trip Outputs Terminal Number 1 2 Pole Mating Connector Part Number 1 2 Fault In...

Page 21: ...Fault Interrupter 2 Pole 1 18 Fault Interrupter 2 Pole 2 19 Fault Interrupter 2 Pole 3 20 Fault Interrupter 2 Residual Power Inputs Terminal Number Power Pole 21 Fault Interrupter 1 Pole 1 22 Fault I...

Page 22: ...onics module Communication Port Pin Out Electronics Module Pin Function 1 Power in 2 RXD Data In 3 TXD Data Out 4 No connection 5 Signal reference 6 No connection 7 No connection 8 No connection 9 Pow...

Page 23: ...current control enclosure Pad mounted style shown 2 1 4 5 3 FACE VIEW Data Port Pin Out Control Enclosure Pin Function 1 Power return 2 RXD Data In 3 TXD Data Out 4 Power in 5 Signal reference S C Ins...

Page 24: ...None Data Bits 8 Stop Bits 1 Flow Control XON XOFF The overcurrent control does not use hardware flow control RTS CTS AcSELerator Quickset SEL 5030 Parameter Setting Device Data Speed 9600 Data Bits...

Page 25: ...rTerminal Website www hilgraeve com hyperterminal html Note This software is the same software supplied with previous versions of Microsoft Windows It is available for purchase Basic instructions for...

Page 26: ...nnecting click on the Reconnect button on the toolbar Again this function is located under the Call menu Step 6 To exit this session select File Exit or click on the X button in the upper right hand c...

Page 27: ...ents Example Referring to the coordination plot in Figure 2 on page 30 a Vista SD switchgear assembly with 600 ampere fault interrupt ers is placed into an electrical system where the upstream protect...

Page 28: ...rity Characteristic Time s Current kA Maximum Rating 20 15 10 5 0 25 10 5 0 Figure 1 S C Overcurrent Control maximum current rating adjusted for C T saturation Table 1 on page 29 should be used to det...

Page 29: ...ow the limits shown for the operation of the I2t security characteristic during fault levels up to 14 5 kA The Time Dial setting is below the threshold of 10 0 at a Pickup setting of 1200 amperes If t...

Page 30: ...U4 Pick Up 880 00 A TD 0 800 0 1 51 Vista 200K fuse 0 01 0 4 1 10 1000 100 10000 Fuse S C SMU20 K 14 4kV Rating 200 0 A 12 47 kV Phase Relay Relay WEST CO 9 Tap Range Tap 0 Pick Up 960 00 A TD 2 CT 6...

Page 31: ...0 1 00 0 50 6000 5000 3000 2500 1500 1250 600 500 300 250 150 125 60 50 30 25 15 12 5 6 5 3 2 5 100 90 80 40 70 60 50 30 20 10 9 8 4 7 6 5 3 2 1 9 8 4 7 6 5 3 2 1 09 08 04 07 06 05 03 02 01 100 90 80...

Page 32: ...r Coordinating Main Curves Minimum Pickup Amperes 100 150 200 250 300 350 400 450 500 600 700 800 For Curves U1 U5 and C1 C5 Minimum Pickup Amperes 50 1200 1 A steps Time Dial Multiplier U Curves 0 5...

Page 33: ...steps For Coordinating Tap and U1 U5 and C1 C5 Curves Definite Time Delay ms 60 Hz OFF 32 48 64 80 96 Definite Time Delay ms 50 Hz OFF 40 60 80 100 120 For Coordinating Main Curves Definite Time Dela...

Page 34: ......

Reviews: