background image

Instruction Sheet  465-501

June 1, 2020
©  S&C Electric Company 2020, all rights reserved

VacuFuse™ Self-Resetting Interrupter—Quick Operation Guide

Outdoor Distribution (5 kV, 15 kV, and 25 kV)

Opening and Closing the VacuFuse Interrupter

The VacuFuse interrupter can be open or closed using the yellow OPEN/CLOSE lever. See 
Figure 2. The VacuFuse interrupter will not drop out of the cutout mounting when in the 

Open

 position. It will remain upright until removed manually. Read and understand the 

WARNING message in the “If the VacuFuse Self-Resetting Interrupter is Found Open” 
section.

To Open 

Push the notched side of the yellow OPEN/CLOSE lever up fi rmly using the straight 
prong of the Talon tool or a distribution prong. The vacuum interrupter inside the 
VacuFuse interrupter will open, and the green position indicator will display. See Figures 
2 and 6.

To Close

Pull the ring of the yellow OPEN/CLOSE lever down fi rmly using the straight prong of 
the Talon tool or a distribution prong. The vacuum interrupter inside the VacuFuse 
interrupter will close, and the red position indicator will display. See Figures 2 and 5. 
If the VacuFuse interrupter is closed into a fault, it will trip open independently of any 
force still applied to the OPEN/CLOSE lever.

To Reset the OPEN/CLOSE lever after Manually Closing into Fault Current

If the VacuFuse interrupter is manually closed into fault current, it will trip open, leaving 
the lever in the 

Closed

 position and the vacuum interrupter in the 

Open

 position. The 

lever can be reset by operating it into the 

Open

 position. Then, if desired, close the 

VacuFuse interrupter by pulling down on the OPEN/CLOSE lever.

Setting the MODE SELECTOR Lever

Before leaving the VacuFuse interrupter, verify the MODE SELECTOR lever is in the 
desired position for the installation. The MODE SELECTOR lever has two positions. 
When the lever is up, it is in 

Auto

 mode. When the lever is down, it in 

NR

 (Non-Reclose) 

mode. To set the MODE SELECTOR lever, rotate it to the desired position with the straight 
prong of a Talon tool or distribution prong.

Auto Mode

In 

Auto

 mode, the VacuFuse interrupter will respond to fault current in accordance with 

its preset TCC curve. The VacuFuse interrupter will perform one 

Reclosing

 operation 

(two 

Trip

 operations total) to lock open. The open interval between operations is a 

user-specifi ed time between 0.5 and 5 seconds. The protection sequence reset time is a 
user-specifi ed interval between 30 seconds and 15 minutes. If a fault persists to the end 
of the protection sequence, the VacuFuse interrupter will remain in the 

Open

 position 

until manually closed. The VacuFuse interrupter will not drop out and will remain 
upright in the cutout mounting. The interrupter is in 

Auto

 mode when the curved label 

on the MODE SELECTOR lever side of the housing is fully covered and when the label on 
the base of the lever matches with the label on the bottom of the housing. See Figure 6.

NR Mode

In 

NR

 (Non-Reclose) mode, the VacuFuse interrupter will operate using the instantaneous 

curve.

The VacuFuse interrupter will open and lock open and not attempt to reclose. The 

VacuFuse interrupter is in 

NR

 mode when the red curved line on the side of the housing 

is visible and the amber NR LED on the base of the interrupter is blinking at a 2-second 
interval. See Figures 1 and 5 and the “Understanding the LED Indicators and Position 
Indicators” section.

 WARNING

VacuFuse Self-Resetting Interrupters must be installed, operated, and maintained 
by qualified persons who are knowledgeable in overhead electric power distribution 
equipment and the associated hazards. This guide is not a replacement for 
adequate training and experience in safety procedures for this product. Read S&C 
Instruction Sheet 465-500 thoroughly and carefully before installing or operating 
your VacuFuse Self-Resetting Interrupter.

 DANGER

VacuFuse Self-Resetting Interrupters may be energized from either side and in any 
position. Always consider all parts live until de-energized, tested, and grounded.

If the VacuFuse Self-Resetting Interrupter is Found Open

 WARNING

The VacuFuse Self-Resetting Interrupter is designed to protect distribution 
transformers from internal and external fault current. A VacuFuse interrupter found 
in the 

Open position should not be closed using the OPEN/CLOSE lever until 

the cause of the fault current has been determined and repaired. Closing without 
repairing the fault could result in equipment damage, injury, or death.

After responding to an overcurrent event, in either the 

Auto

 or the 

NR

 mode, the 

VacuFuse interrupter’s vacuum interrupter will open and the position indicator will 
show a green target. See Figure 6. Opening the vacuum interrupter disconnects the 
VacuFuse interrupter’s sensing and display functions from line power, and all LEDs 
will be inoperative after one minute. If the VacuFuse interrupter is found in the 

Open

position:

STEP  1.  

Open and drop open, or remove the VacuFuse interrupter from its mounting if 
required by utility practice, following the steps in “Installing and Removing a 
VacuFuse Interrupter from the Cutout Mounting” section.

STEP  2.  

Determine and resolve the cause of the fault.

STEP  3.  

After determining the cause for the fault and making necessary repairs, install 
the VacuFuse interrupter into its mounting as described in the “Closing the 
VacuFuse Interrupter into the Cutout Mounting” section.

If Maintenance is to be Performed on the Transformer

STEP  1.  

Open the VacuFuse interrupter by pushing up on the OPEN/CLOSE lever using 
the straight prong of a Talon™ Handling Tool.

STEP  2.  

Open and drop open or remove the VacuFuse interrupter from its mounting, if 
required by utility practice, following the steps in “Installing and Removing 
the VacuFuse Interrupter from the Cutout Mounting” section. This creates an 
open gap. Depending on your utility’s standard practices, additional testing 
or grounds may be required.

STEP  3.  

Follow the utility’s standard practice for performing transformer maintenance.

After maintenance has been completed, install the VacuFuse interrupter into its 

mounting following the steps in “Installing and Removing a VacuFuse Interrupter from 
the Cutout Mounting” section.

Figure 1. The VacuFuse Self-Resetting Interrupter—MODE SELECTOR lever side

Figure 2. The VacuFuse Self-Resetting Interrupter—OPEN/CLOSE lever side.

Pull-ring

Jaw-end

contact

Hinge-end 

contact

Trunnion

Hand grip

To open, push the 
OPEN/ CLOSE lever up 
until the green indicator 
displays.

To close, pull the 
ring down until the red 
indicator displays.

MODE SELECTOR

Lever in NR mode

OPEN/CLOSE lever 
(Open shown)

Reviews: