S&C Instruction Sheet 659-520
41
Table 9. PureWave SMS-250 Trip Offline Alarms—continued
Alarm
Description
Reset Type
Execution Frame
Overrun
Indicates the software has a second loop that is executed
during the first loop, which can result in unexpected current
Troubleshooting Tip: Reset the alarm and contact S&C
Electric Company.
MANUAL
IGBT 1 Over
Current
Indicates the IGBT 1 current went beyond 880 A
Troubleshooting Tip: It is possible that a utility transient
caused the alarm. Check the broken thermistor alarms
for all phases. If they are clear, the system can be reset. If
the broken thermistor alarms are present, do not reset the
alarm. Contact S&C Electric Company.
MANUAL
IGBT 2 Over
Current
Indicates the IGBT 2 current went beyond 880 A
Troubleshooting Tip: It is possible that a utility transient
caused the alarm. Check the broken thermistor alarms
for all phases. If they are clear, the system can be reset. If
the broken thermistor alarms are present, do not reset the
alarm. Contact S&C Electric Company.
MANUAL
IGBT 3 Over
Current
Indicates the IGBT 3 current went beyond 880 A
Troubleshooting Tip: It is possible that a utility transient
caused the alarm. Check the broken thermistor alarms
for all phases. If they are clear, the system can be reset. If
the broken thermistor alarms are present, do not reset the
alarm. Contact S&C Electric Company.
MANUAL
Inverter Stop
Indicates the inverter has stopped operating (The battery and
utility are disconnected .)
Troubleshooting Tip: Twist the inverter stop button
clockwise to clear this alarm.
SELF
Parameter Cal Nv
Error
Indicates the main processor found corrupt data where the
parameter and calibration values are stored
Troubleshooting Tip: Power cycle the PureWave SMS-250.
If the alarm still remains, contact S&C Electric Company.
MANUAL
Reverse Phase
Rotation
Indicates the inverter is connected to a utility that is rotating
L1-L3-L2 instead of L1-L2-L3, with the voltage rising zero
crossing occurring on L1, then L2, and finally L3, as expected
Troubleshooting Tip: If this alarm is on and stays on, the
phase rotation should be corrected by swapping the
utility connection wires on L2 and L3.
SELF
SCADA or HMI
Trip Offline
Indicates SCADA or the HMI commanded a trip offline to take
the PureWave SMS-250 system offline
Troubleshooting Tip: SCADA must send a 0 to the SCADA
trip offline bit register or the local HMI must send a 0 to
the HMI trip offline bit register to clear this alarm.
MANUAL
Operation