background image

SAMWON ENG                                              SU-105 Instrument for Automatic Control of Temperature                                              Page 

1/4

 

Instruction Manual of Instrument for Automatic Control of 

Temperature

 SU-105 

Model 

Kinds of Sensor 

Output 

SU-105KRR 

K (-200.0℃~999.0℃) 

OUT1,2:RELAY   

SU-105PRR 

Pt100 (-200.0℃~400.0℃) 

OUT1,2:RELAY 

SU-105DA 

NTC(-40.0℃~99℃) 

OUT1,2:RELAY 

 

 
 
 
 
 

 

  Thank for purchasing Products of SAMWON ENG. 

Instruction  Manual  is  provided  to  prevent  Products  from  being 
damaged or defected by user’s mistake and to inform user the accurate 
how to use. Please keep it in safe place. Thank you.

 

!

     

Warning

   

 

It’ s not guaranteed to prevent any hazards in personal, property, and 
expensive peripheral, as it’ s not provided for the purpose of safety. 
Please utilize additional duplex safety instruments.   

 
 

Danger

   

 

①Electrical shock –  Please do not access to any AC terminal, while 
in use. Electrical shock is expected. 
②Please  shut  down  the  electrical  power,  whenever  you  check  the 
power input.   

 
 
 

!

 

   

Caution

   

 

1.

 

A  terminal  (M3.5,  Wide  7.2mm  in  maximum)  shall  be  used  to 

connect AC power.

 

2.

 

A  hazard  in  personal  and  property  is  expected,  when  you  do  not 

follow the instructional recommendation by manufacturer.

 

3.

 

A  keen  attention  shall  be  expected  to  ensure  that  any  ingress  of 

dirt, water, oil and debris of cable do not exist inside the product, in 
order to prevent any damage on product and a fire hazard

4.

 

Any modification and disassembly are not allowed. It may cause a 

critical damage on product.

 

5.

 

Relay  durability  depends  on  the  load  capacity  and  the  on-off 

frequency.  *  durability  :  mechanical  durability  (a  million  times),   
electrical durability (0.1 million times at AC250VAC 2A)

 

6.

 

Connect the terminal by confirming the polarity and usage.

 

7.

 

Isolate the wiring from the cable of high-voltage, electrical power 

and motor in order to prevent any derived noise.

 

8.

 

Avoid the followings. 

①dirt, corrosion gas, oil, humidity. 
②danger of high humidity and freeze. 
③radiant heat of sun shine.   
④vibration impact.   
⑤altitude higher than 2,000M.   
⑥less than grade 2 environment.

 

9.

 

Power switch or a circuit breaker are recommended for shut-down. 

10.

 

Utilize  a  switch  or  a  circuit  breaker  equivalent  to  IEC947-1  or 

IEC947-3 to be attached to panel.

 

11.

 

An authorized  Compensating Lead Wires shall  be used  as a extension  wire 

which connects Thermo Couple and Controller.    Normal Lead Wire may cause 
a  differential  in  temperature  at  the  wiring  connection  between  Thermo 
Coupleand  Normal  Lead  Wires. 

A  sensor  cable  longer  than  3M  may 

cause a variation of temperature.

 

Correct it by using compensation 

feature(rSt).

 

12.

 

When RTD sensor is selected, ① extension of wire shall be connected in 3 

wires,  which  have  the  same  thickness  and  length.  A  different  resist  in  wire 
may cause a differential in temperature. ②

 A sensor cable longer than 3M 

may  cause  a  variation  of  temperature/humidity.  Correct  it  by  using 
compensation feature(rSt).

 

13.

 

Isolate the product from the power cable to prevent any noise.

 

14.

 

Avoid the equipment which creates a strong high frequency noise, 

such as welding machine, a sewing machine and SCR controller.

 

15.

 

Utilize additional terminal to be used in solenoid valve.

 

16.

 

Turn controller off when lighting and thunder.

 

17.

 

Mobile radio may cause a defect. Please refrain.

 

* Please pay keen attention to above. It may cause a defect to product.

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 

 
 
 
▶on-off control or PI control for cooler/heater only. 

Variation(dIF)  0.1~25.0℃,  Delay  timer  of  power-on  switch  for  0~300 
seconds. Selectable in right/opposite direction. 

Proportional,  Integral  compensation,  Period  timer  (1~120seconds)  to  be 
selectable. 

▶Digital period timer inside for Defreeze.    999minutes in max.   

(controllable by every minute/second.) 

▶Lock feature for installer. / Allowance of range. 
  ˚ Preset temperature could be regulated in range.⇒  Allowance of range 
  ˚ Feature  shall  be  locked.  (Hysteria,  Delayed  time,  direction..)⇒LOCK 

feature 

▶In case of error in sensor, output leveling feature.(applied to TH, IC, HUM, 

A only) 

 
 
 
 
▶  Supply power to controller to display current Temperature. 
▶Set key only once. Set indicator blinks. 
▶  Use Up(Up),Down(Dn) key to reset Temperature.도를 
      Up/Down key for longer than 1 second will   

speed up its feature. 

※If 

Allowance of range

 is on state,     

reset range will be limited in the   
dedicated range. 
▶Set key once more again will 
    Memorize the reset value. 
    Even if power is turned-off, its set 
    Set value will not be erased. 
▶Current temperature is displayed   

And controller will be active. 

▶Main output shall be connected   

to terminal 6~7. 

 
※  Terminal 5 is not available, only for OFF use. 
※For Aux output(Alarm/Timer), please refer to 
<9. reset alarm output> and <10. set period timer>. 

Display 

Display the current & set temperature. 

Main/AuxOutput  Display on-off state of main/aux output. 

SET 

Up 

Down 

 

    Temperature to be set.   

    Up to amend preset. 

    Down to amend preset. 

 

1. Picture

 

 

2. Feature

 

 

3. S

et Control

 

 

set 

up 
dn 

< Terminal in back> 

Coil 

Terminal

코일단자 

Magnet 

메인 
전원 

작동   
기계 

AC 

220V 

Main

Pwr 

Mac
hine 

<current temp.> 

Sensor 

input 

 

Main 

output 

Aux 

output 

Power 

 

 
 

RELAY 

5A 

RELAY 

2A 

AC 

220V 

① ② ③ ④ ⑤ ⑥ ⑦ ⑧ ⑨ ⑩ ⑪

 

 

 

SET 

up 

dn 

OUT1

 

OUT2

 

set 

Up button    Main Output 

시  창 

Aux Output 

시  창 

Down button 

Display 

Reviews: