Samsung NS 1DXEA Series Installation Manual Download Page 1

Air Conditioner

installation manual

imagine

 the possibilities

Thank you for purchasing this Samsung product. 

Cassette Type Series

NS



1DXEA

AC



FB1DEH

EN

PT

IT

RU

ES

DE

FR

EL

DB98-34507A-05

CAC 유럽향 1way_IM_34507A-05_EN.indd   27

2016-08-02   오후 4:08:21

Summary of Contents for NS 1DXEA Series

Page 1: ...lation manual imagine the possibilities Thank you for purchasing this Samsung product Cassette Type Series NS 1DXEA AC FB1DEH EN PT IT RU ES DE FR EL DB98 34507A 05 CAC 유럽향 1way_IM_34507A 05_EN indd 27 2016 08 02 오후 4 08 21 ...

Page 2: ...theindoorunitisnotsuitabletobe installedinareasusedforlaundry Donotusetheunitsifdamaged Ifproblemsoccur switchtheunitoffanddisconnectitfromthepowersupply Inordertopreventelectricshocks firesorinjuries alwaysstoptheunit disabletheprotectionswitchandcontactSAMSUNG s technicalsupportiftheunitproducessmoke ifthepowercableishotordamagedoriftheunitisverynoisy Alwaysremembertoinspecttheunit electricconne...

Page 3: ...evicesdisconnectedfromthepowersupplyshouldbecompletelydisconnectedintheconditionofovervoltagecategory Besurenottoperformpowercablemodification extensionwiring andmultiplewireconnection Itmaycauseelectricshockorfireduetopoorconnection poorinsulation orcurrentlimitoverride Whenextensionwiringisrequiredduetopowerlinedamage referto Howtoconnectyourextendedpowercables in theinstallationmanual Makesuret...

Page 4: ... consult your dealer Avoid installing the air conditioner In areas where it is exposed to direct sunlight Close to heat sources In damp areas or locations where it could come into contact with water for example rooms used for laundry In areas where curtains and furniture could affect the supply and discharge of air Without leaving the required minimum space around the unit as shown in the drawing ...

Page 5: ...und if the unit has a duct with a well defined length 300mm or more to avoid fan motor blower contact If you install the cassette or duct type indoor unit on the ceiling with temperature over 27 C or humidity over 80 you must apply extra 10mm of polyethylene foam or other insulation with similar material on the body of the indoor unit The units must be installed according to distances declared in ...

Page 6: ...ection ø9 52 3 Drain pipe connection VP20 OD26 ID20 4 Power supply connection 5 Air discharge grille 6 Air suction grille Dimension and weight Net dimension Indoor unit mm 970X135X410 Panel size 1180X25X460 Net weight Indoor unit Panel kg 13 970 135 280 410 460 150 25 1036 1074 1180 Drain hole CAC 유럽향 1way_IM_34507A 05_EN indd 6 2016 08 02 오후 4 08 09 ...

Page 7: ...curely after adjusting level of the unit by using a leveler 4 Remove the pattern sheet connect the other cables and install the front panel Since the diagram is made of paper it may shrink or stretch slightly due to temperature or humidity For this reason before drilling the holes maintain the correct dimensions between the markings Piping must be laid and connected inside the ceiling when suspend...

Page 8: ...g the assembly piping Unscrew the pinch pipe at the end of each refrigerant pipe Result All inert gas escapes from the indoor unit To prevent dirt or foreign objects from getting into the pipes during installation do NOT remove the pinch pipe completely until you are ready to connect the piping If the pipes must be shortened refer to page 9 Connect the indoor and outdoor units using pipes with fla...

Page 9: ...ign the pipes and tighten the flare nuts first manually and then with a torque wrench applying the following torque In case of welding the pipe you must weld with nitrogen gas blowing Oblique Rough Burr Pipe cutter Pipe Outer Diameter D Depth A ø6 35 mm 1 4 1 3 mm ø9 52 mm 3 8 1 8 mm ø12 70 mm 1 2 2 0 mm ø15 88 mm 5 8 2 2 mm ø19 05 mm 3 4 2 2 mm Pipe Flare Uneven Thickness Cracked Damaged Surface ...

Page 10: ...le ducts 5 Selecttheinsulationoftherefrigerantpipe Insulate the gas side and liquid side pipe referring to the thickness according to the pipe size Less than indoor temperature of 30 C and humidity of 85 is the standard condition If installing in a high humidity condition use one grade thicker insulator by referring to the table below If installing in an unfavorable conditions use thicker one Insu...

Page 11: ...nd then fix it as indicated When installing insulation in places and conditions below use the same insulation that is used for high humidity conditions Geological condition High humidity places such as shoreline hot spring near lake or river and ridge when the part of the building is covered by earth and sand Operation purpose condition Restaurant ceiling sauna swimming pool etc Building construct...

Page 12: ...ce to the piping on the unit side when connecting the drain hose The hose should not be allowed to hang loose from its connection to the unit Fasten the hose to a wall frame or other support as close to the unit as possible Support pieces 1 1 5m Ceiling 1 100 or more If it is necessary to increase the height of the drainpipe install the drainpipe straightly within 300 mm from the drain hose port I...

Page 13: ...e control box cover and turn on the indoor unit 3 Check whether the drain pump works correctly 4 Check whether the drainage is performing correctly at the end of the drain pipe 5 Check for leakage at the drain pipe and drain pipe connection part 6 When leakage occurs check whether the indoor unit is level and check the drain hose connection part drainpipe connection part and drain pump connection ...

Page 14: ...ationinsyntheticrubberandjacketinpolychloroprene neoprene inaccordancewiththerequirementsofstandardEN60335 2 40 1 Removethescrewontheelectricalcomponentboxandremovethecoverplate 2 Routetheconnectioncordthroughthesideoftheindoorunitandconnectthecabletoterminals refertothefigurebelow 3 Routetheotherendofthecabletotheoutdoorunitthroughtheceiling theholeonthewall 4 Reassembletheelectricalcomponentboxc...

Page 15: ...erminal block must not be unscrewed with the torque less than 12 kgf cm Since it has the external power supply refer to the outdoor unit installation manual for MAIN POWER Between Indoor and Outdoor Connection cable Specifications Common in use Terminal Block SPEC Indoor When installing the indoor unit in a computer room use the double shielded Tape aluminum polyester braid copper cable of FROHH2R...

Page 16: ...be CAUTION Unit mm 120 60 20 20 20 180 Power cable 20 Pre installed tube for the power cable 3 Insert both sides of core wire of the power cable into the connection sleeve f f Method 1 Push the core wire into the sleeve from both sides Connection sleeve f f Method 2 Twist the wire cores together and push it into the sleeve Connection sleeve 4 Using a crimping tool compress the two points and flip ...

Page 17: ...wrap it with the insulation tape to finish Make sure that the connection parts are not exposed to outside Be sure to use insulation tape and a contraction tube made of approved reinforced insulating materials that have the same level of withstand voltage with the power cable Comply with the local regulations on extensions CAUTION Insulation tape In case of extending the electric wire please DO NOT...

Page 18: ...SEG21 SEG22 SEG23 SEG24 2 X X X X X 3 X X X X X The procedure of setting option Set the indoor unit address and installation option with remote controller option Set the each option separately since you cannot set the ADDRESS setting and indoor unit installation setting option at the same time You need to set twice when setting indoor unit address and installation option On SEG1 12 Off SEG13 24 Se...

Page 19: ...otation 6 Setting Fan mode Press Mode button to be changed to FAN mode in the ON status 7 Setting SEG9 SEG10 option Press Low Fan button to enter SEG9 value Press High Fan button to enter SEG10 value Each time you press the button will be selected in rotation 8 Setting Heat mode Press Mode button to be changed to HEAT mode in the ON status 9 Setting SEG11 SEG12 option Press Low Fan button to enter...

Page 20: ...ess the button will be selected in rotation 18 Setting Heat mode Press Mode button to be change to HEAT mode in the OFF status 19 Setting SEG23 SEG24 mode Press Low Fan button to enter SEG23 value Press High Fan button to enter SEG24 value Each time you press the button will be selected in rotation SEG16 SEG18 SEG21 SEG23 SEG17 SEG20 SEG22 SEG24 Step 4 Input option Press operation button with the ...

Page 21: ...in address RESERVED RESERVED The unit digit of an indoor unit Remote Controller Display Indication andDetails Indication Details Indication Details Indication Details Indication Details 0 A 0 No Main address 0 3 A single digit 1 Main address setting mode Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Explanation PAGE RESERVED Setting RMC address RESERVED Group channel 16 Group address Remote Controller D...

Page 22: ... Settinganindoorunitinstallationoption suitablefortheconditionofeachinstallationlocation SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 0 2 RESERVED Exterior temperature sensor Central control RESERVED SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 1 Drain pump RESERVED RESERVED RESERVED Master Slave SEG13 SEG14 SEG15 SEG16 SEG17 SEG18 2 External control External control output S Plasma ion Buzzer Number of hours using filter S...

Page 23: ...Explanation PAGE Useofexternal control Setting the output of external control S Plasma ion Buzzer control Number of hours using filter Remote Controller Display Indication and Details Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details 2 0 Disuse 0 Thermo on 0 Disuse 0 Useofbuzzer 2 1000Hour 1 ON OFF Control 1 Operation on 1 Use 1 Nonus...

Page 24: ...dication Details Indication Details Indication Details 0 D Option mode 0 F Tens digit ofSEG 0 9 Unitdigit ofSEG 0 9 The changed value 0 F When changing a digit of an indoor unit address setting option set the SEG3 as A When changing a digit of indoor unit installation option set the SEG3 as 2 Ex When setting the buzzer control into disuse status Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6 Explanation PAG...

Page 25: ...n for 2 minutes between indoor units Communication error for more than 2 minutes 2 Indoor unit receiving the communication error from outdoor unit 3 Outdoor unit tracking 3 minutes error 4 When sending the communication error from the outdoor unit the mismatching of the communication numbers and installed numbers after completion of tracking Communication error for more than 2 minutes X X X 1 Indo...

Page 26: ... gu Gwangju si Korea 62218 Samsung Electronics UK Ltd Euro QA Lab Blackbushe Business Park Saxony Way Yateley Hampshire GU46 6GG United Kingdom AEEE Yönetmeliğine Uygundur This product is RoHS compliant CAC 유럽향 1way_IM_34507A 05_EN indd 26 2016 08 02 오후 4 08 21 ...