Wired Remote Controller Installation/Service Mode
20
Se
rvic
e Mode
Main
menu
Sub
menu
Function
Data
bit
Factory
setting
Description
Unit
6
1
ERV Plus setting/checking
Use of cold air prevention
1
0
0-No use, 1-Use
-
Use of humidification when
heating thermo off
2
0
0-No use, 1-Use
-
Use of fan operation in
Defrost operation
3
0
0-No use, 1-Use
-
Use of humidification when
Heating
4
0
0-No use, 1-Use
-
2
ERV Plus set temperature
setting/checking
Cooling
1,2
25
15~30°C
1°C
Heating
3,4
25
15~30°C
1°C
3
ERV Plus Auto mode
temperature setting/
checking
Set temperature
1,2
25
15~30°C
1°C
Set temperature difference 3,4
10
5~15°C
1°C
4
Setting/checking the compensating temperature A
under the Heating EEV control for ERV Plus
1,2
8
0~10°C
1°C
Checking the compensating temperature B under the
Heating EEV control for ERV Plus
3
0
0 – No use of humidifier(0 °C)
1 – Use humidifier(10 °C)
-
5
ERV Plus fan RPM setting/
checking
Air supply RPM
1,2
-
10~27 Step
1 Step
Air exhaustion RPM
3,4
-
10~27 Step
1 Step
7
1
Status of Automatic Air-Volume setting
1
0
0 - OFF (No use or Cancelled)
1 - Complete(Normal complete)
2 - Running
-
2
Automatic Air-Volume Operation
1
0
0 - Disable(Cancel)
1 - Enable (Running)
-
3
Automatic Air-Volume Voltage Setting
1
2
1 - 220V
2 - 230V (Default)
3 - 240V
-
0
Factory setting
1
0
0 – No use, 1– Factory setting
-